SERIES 90 MODUTROL IV

 MOTORS

63-2631—07

8

Fig. 5. Typical Series 90 Wiring.

Fig. 6. Wiring for Potentiometer Control

For controlling up to six Series 90s in parallel with a 135 ohm 

pot or slide wire type series 90 controller, add the appropriate 

resistor indicated in the table below to ONE of the Series 90 

motors, from terminal B to terminal W. As an alternative, one 

221508A2 module can be used to provide any of the resistor 

values given below:

Table 7. Resistor Values of Motors in Parallel

Fig. 7. Auxiliary Switch Schematic.

Fig. 8. Series 90 Slave Motor Connection.

Fig. 9. Series 60 Controller.

Number of Motors in 

Parallel

Resistor Value

1

None

2

140 Ohms

3

72 Ohms

4

47 Ohms

5

36 Ohms

6

29 Ohms

L1 

(HOT)

L2

1

1

2

R

W

B

R

W

B

T1

T2

TRANSFORMER

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 

OVERLOAD PROTECTION AS REQUIRED.

TRANSFORMER MAY BE INTERNAL OR EXTERNAL

M770A

SERIES 90

CONTROLLER

MOTOR

L1 

(HOT)

L2

1

1

2

R

W

B

R

W

B

T1

T2

TRANSFORMER

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 

OVERLOAD PROTECTION AS REQUIRED.

TRANSFORMER MAY BE INTERNAL OR EXTERNAL

M13708

 135 OHM

 POTENTIOMETER

MOTOR

BLUE LEAD

YELLOW LEAD

RED LEAD

USE NEC CLASS 1 WIRING UNLESS POWER SUPPLY

MEETS CLASS 2 REQUIREMENTS.  TAPE UNUSED LEADS.  

ENSURE THE CURRENT DRAW OF THE EXTERNAL CIRCUIT 

IS LESS THAN SWITCH CONTACT RATING.

ON TWO-SWITCH MOTORS, SECOND SWITCH HAS BLACK

LEADS WITH BLUE, YELLOW, AND RED TRACERS.

SOME AUXILIARY SWITCH ASSEMBLIES INCLUDE ONLY

RED AND YELLOW LEADS. SOME OTHERS DO NOT INCLUDE 

THE YELLOW LEAD.

M17099

1

1

1

2

2

2

2

3

3

T1 T2 R(-)

B W1 W1 W(+)

T1 T2 R

B

W

M27085A

5 4 3 2 1

5 4 3 2 1

SET DIP 

SWITCH 

TO TWO 

MOTORS 

24 VOLT 4-20–

4-20+

24 VOLT

SERIES 90 SLAVE MOTOR CONNECTION FROM 4-20MA

INTERFACE

MODULE

221508A2 

M27035

R

1

2

T

G

Y

3

4

M6284

W

R

B

T1

T2

M9184

R (HOT)

C

R (HOT)

R

B

W

SERIES 60 

CONTROLLER

C

Содержание Modutrol IV M9175D 1014

Страница 1: ...eight of older motors is available Motors have field adjustable stroke 90 to 160 Die cast aluminum housing Integral auxiliary switches are available factory mounted or can be field added Nominal timing standard of 30 seconds 90 stroke and 60 seconds 160 stroke Other timings available Spring return motors can operate valve linkages form power end or auxiliary end shafts for normally closed or norma...

Страница 2: ...Number Guide See Table 1 Table 1 Modutrol IV Series 2 and 3 Model Number Guide NOTE Torque designation corresponds to torque rating at standard timing nominally 60 sec for 160 and 30 sec for 90 except for 300 lb in motors which have timings of 2 or 4 min Dimensions Refer to Fig 2 Electrical Ratings Refer to Table 2 Control Inputs Proportional Series 90 NOTE Motor Series 90 control can be either El...

Страница 3: ...ROKE 160 DEGREE STROKE NON SPRING RETURN MOTORS 160 10 90 45 SPRING RETURN MOTORS AND NON SPRING RETURN MOTORS ASYMMETRICAL MOTORS SYMMETRICAL MOTORS M18998D 4 7 8 124 5 1 2 140 13 16 20 4 1 16 103 1 4 7 1 1 2 37 5 1 2 140 JUNCTION BOX MOTOR AUXILIARY END POWER END ADAPTER BRACKET 2 9 16 66 5 3 8 137 6 7 16 164 9 16 15 3 4 19 TOP VIEW OF BRACKET TOP VIEW 4 5 8 116 4 1 4 107 2 5 16 58 11 16 17 4 7 ...

Страница 4: ...stor Board plugs onto Series 90 Motor quick connect wire terminals Provides same functionality as 4074BYK 4074EAU 4074EDC or 4074EED Resistor Kits 4074BYK Series 90 Resistor Kit provides for unison control of up to six Series 90 Motors 4074EAU W973 Resister Kit provides for control of two or three Series 90 Motors from a W973 Single zone Logic Panel or W7100 Discharge Air Controller 4074EDC 4 20 m...

Страница 5: ...ns and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect all power supplies before installation Motors wi...

Страница 6: ... except the Q5001 To mount the motor with the bracket See Fig 3 1 Mount the bracket to the equipment with existing or stan dard bolts 2 Using the provided bolts mount the motor to the bracket threaded holes For valve linkage applications other than the Q5001 1 Mount the bracket to the linkage 2 Position the motor on the bracket to align the motor shaft with the linkage 3 Attach the motor to the br...

Страница 7: ...pply VA rating is large enough to provide power to all motors used without overloading 3 Fig 11 shows that the motor terminals are quick connects located on top of the printed circuit board 4 To access the wiring compartment a Remove the four screws from the junction box top b Lift off the cover 5 Refer to Fig 5 for typical wiring and Fig 7 for internal auxiliary switch connections NOTE Reverse mo...

Страница 8: ...PROTECTION AS REQUIRED TRANSFORMER MAY BE INTERNAL OR EXTERNAL M770A SERIES 90 CONTROLLER MOTOR L1 HOT L2 1 1 2 R W B R W B T1 T2 TRANSFORMER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANSFORMER MAY BE INTERNAL OR EXTERNAL M13708 135 OHM POTENTIOMETER MOTOR BLUE LEAD YELLOW LEAD RED LEAD USE NEC CLASS 1 WIRING UNLESS POWER SUPPLY MEETS CLASS 2 REQUIREMENTS TAPE UNU...

Страница 9: ...6284D4004 S M6285A1005 S M6285A1054 S M6285A4009 S 600 Ohms No Yes No 187 Ohm M6274F1009 F M6284F1070 F M6284F1078 F M6285F1001 F M6294F1009 F M6294F1017 F M6284D1032 F 10 K Ohms No No Yes Not Available M6284A1071 S M6284A1089 S M6284C1028 S 196 346 Ohms Yes Yes No 274 Ohm M6284A1030 S M6284A1055 S M6284A1097 S M6284B1004 S M6284C1010 S M6284C1044 S M6284F1013 S M6284F1039 S M6285A1039 S M6285A104...

Страница 10: ... Motors Adjustable timing for M9182D1023 The timing potentiometer the second from the right Refer to Fig 10 sets the timing to 1minute if turned fully CCW 2 minutes if turned to its middle point and 4 minutes if turned fully CW CAUTION Careless Installation Hazard Use of excessive force while adjusting cams damages the motor To avoid damaging motor end switches set cams by moving only the top of t...

Страница 11: ...oth directions 9 Disconnect the potentiometer reconnect the controller and replace the motor top cover NOTE Changing the differential from 1 to 10 reverses the switching action For example with a 10 dif ferential switch contacts R B make and R W break on a counterclockwise closed rotation With a 1 differential switch contacts R W make and R B break on a counterclockwise closed rotation OPERATION U...

Страница 12: ...IFF MOTOR OPEN MOTOR CLOSE POWER END OUTER AUXILIARY CAM BLUE LEFT OUTER AUXILIARY SWITCH FAST RISEPORTION APPROX 1 DIFF 1 8 INCH STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED FAST RISE PORTION APPROX 1 DIFF FAST RISE PORTION APPROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF MOTOR OPEN MOTOR CLOSE POWER END OUTER AUXILIARY CAM RED LEF...

Страница 13: ...the old motor 2 Remove the crank arm from shaft of old motor and remove the old motor 3 Determine necessity of the mounting bracket If the link age can reach the new motor shaft position and the crank arm has clearance for the necessary rotation the bracket is not required Use the 220738A Adapter Bracket or the 221455A Crank Arm if the crank arm must rotate through the bottom plane of the motor a ...

Страница 14: ...SERIES 90 MODUTROL IV MOTORS 63 2631 07 14 ...

Страница 15: ...SERIES 90 MODUTROL IV MOTORS 15 63 2631 07 ...

Страница 16: ... liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the literature by you ...

Отзывы: