background image

SERIES 71, 72, AND 76 MODUTROL IV™ MOTORS

11

63-2640—07

Fig. 12. Auxiliary switch adjustment.

OPERATION AND CHECKOUT

Operation

The internal shaft position feedback potentiometer in 

conjunction with the actuator microprocessor and modulating 

input circuit form a control loop. When the external controller’s 

output remains at a fixed amplitude the actuator’s shaft 

position is held at a position proportional to that input 

amplitude. When the value of the external controllers output 

changes the actuator responds by initiating movement of the 

motor to proportionately compensate for the change in input 

amplitude. When the motor reaches the control loop balance 

point the system is again in a static state and the actuator 

holds position until the next change of input from the external 

controller. 

M7685 motor also have a minimum position feature. An 

external 130 ohm potentiometer wired to terminals 3 and 4 

establishes a position beyond which the control input cannot 

close the motor. If power to the T1-T2 is interrupted the M7685 

motor will spring close.

Checkout

After installation and linkage adjustment, operate the motor 

through the controller. Make sure that:

• The motor properly operates the damper or valve.

• The motor responds properly as the input is varied.

• The auxiliary switch, if used, operates at the desired point of 

motor rotation.

Inspect the motor, linkage, and valve or damper to see that all 

mechanical connections are correct and secure.

In damper installations, the pushrod should not extend more 

than a few inches past the ball joints. Check to see that there is 

adequate clearance for the linkage to move through its stroke 

without binding or striking other objects.

See controller or system instructions for additional checkout 

procedures.

Motor Operation Checkout

For motors with F, + and - terminals:

To close the motor, open ter, -, and F.

To open the motor connect terminal F to positive (+) or 

negative (-).

NOTE: DO NOT SHORT + to -

M7164A1017 and M7164G1030 do not have + or – 
terminals, and operate as follows:

The motor closes if it does not receive an input to F.

To open the motor, short F to C.

M7685A1025 is a normally open motor, and operates as 
follows:

To close the motor, short 3 to 4 or short 3 to C.

The motor opens if it does not have an input to 3.

RIGHT/INNER 

AUXILIARY

SWITCH 

FAST RISE

PORTION

(APPROX. 

1  DIFF.)

SLOW RISE

PORTION

(APPROX. 

10  DIFF.)

INNER

AUXILIARY

CAM

(BLUE)

NOTE: CAMS ARE OFFSET 

VERTICALLY TO PROVIDE 

BETTER VIEW OF BACK CAM.

FAST RISE

PORTION

(APPROX. 

1  DIFF.)

SLOW RISE

PORTION

(APPROX. 

10  DIFF.)

MOTOR 

OPEN

MOTOR 

CLOSE

POWER 

END

OUTER

AUXILIARY

CAM

(RED)

LEFT/OUTER

AUXILIARY

SWITCH

M17101

POWER END

OF MOTOR

OUTER AUXILIARY 

CAM (RED) 

INNER AUXILIARY 

CAM (BLUE) 

RIGHT/INNER

AUXILIARY SWITCH

LEFT/OUTER

AUXILIARY 

SWITCH

MOVE SCREWDRIVER AT 

TOP ONLY TO ADJUST CAM.

1/8 INCH 

STRAIGHT-BLADE 

SCREWDRIVER

Содержание Modutrol IV 71 Series

Страница 1: ...crew terminal adapter is available Adapter bracket for matching shaft height of older motors is available Most motors have field adjustable stroke 90 to 160 Die cast aluminum housing Integral auxiliary switches are available factory mounted or can be field added Nominal timing standard of 30 seconds 90 stroke and 60 seconds 160 stroke Other timings available Spring return motors can operate valve ...

Страница 2: ...ny electronic controller that provides a stable noise free proportional current output as specified in Electrical Ratings Input Range below Electrical Ratings Power Consumption See Table 1 Input Range Current Nonadjustable 4 to 20 mA nominal 25 mA maximum Current Adjustable 4 to 20 mA adjustable 50 mA maximum Zero Null Motor Closed 0 0 to 18 mA Span 1 8 to 20 mA Voltage Nonadjustable 2 to 10 Vdc I...

Страница 3: ...ual ended shaft Normally Closed Spring Return 4 Non Spring Return 5 Normally Closed Spring Return A 0 Auxiliary Switches Adjustable Stroke Normally Closed B 1 Auxiliary Switch C 2 Auxiliary Switches D 0 Auxiliary Switch Qa 2 Auxiliary Switches M 72 8 4 A XXXX See Tradeline Catalog for Complete Model Number FULLY OPEN 90 DEGREE STROKE 160 DEGREE STROKE M31079 VERTICAL REFERENCE FULLY CLOSED 160 10 ...

Страница 4: ...Y END POWER END ADAPTER BRACKET 2 9 16 66 5 3 8 137 6 7 16 164 9 16 15 3 4 19 TOP VIEW OF BRACKET TOP VIEW 4 5 8 116 4 1 4 107 2 5 16 58 11 16 17 4 7 8 124 5 9 16 141 1 4 7 5 13 16 148 1 POWER END 2 3 1 1 2 37 3 4 19 SPRING RETURN MODEL SHOWN FOR 60 LB IN SPRING RETURN MODELS 8 3 4 222 FOR NON SPRING RETUIRN MODELS 7 5 16 185 FOR 60 LB IN SPRING RETURN MODELS SHOWN FOR NON SPRING RETURN MODELS 1 2...

Страница 5: ...After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect all power supplies before installation Motors with auxiliary switches can have more than one disconnect CAUTION Equipment Damage Hazard Can damage the motor beyond repair Never turn the motor s...

Страница 6: ...er Bracket for all valve applications Applications with the Q5001 Valve Linkage do not require the 220738A Adapter Bracket see Fig 4 For detailed instructions on specific linkage assemblies refer to the instruction sheet packed with the linkage In general check the following points when installing a motor and linkage Adjust valve and louver type damper linkages so the damper or valve moves through...

Страница 7: ...iring Wire the motor as follows 1 Remove the wiring box cover by removing the four screws holding the cover to the motor 2 Wire motor to system using quick connect terminals in wiring box 3 Replace wiring box cover Fig 5 Typical system wiring Fig 6 Series 71 optional override switches to drive motor open or closed Fig 7 M7685 Typical application wiring 1 4 20 UNC 1 in LONG MOUNTING BOLTS Q5001 VAL...

Страница 8: ...y turning the motor shaft damages the gear train and stroke limit contacts Adjustable Stroke All models except for M7284C1083 M7284C1091 M7284Q1082 and M7284Q1090 When viewing from the power end of the motor the stroke potentiometer is to the far left To set the stroke to 160 maximum position turn the potentiometer fully clockwise using a 1 8 in straight blade screwdriver To set the stroke at 90 m...

Страница 9: ...ce between the fully open span position current and the zero position current is defined as the operating span 6 Recheck the start and readjust the span potentiometer if necessary Turn the start potentiometer clockwise to increase the zero position 7 Recheck the span and readjust the span potentiometer if necessary Turn it clockwise to increase the full span position 8 For sequential operation as ...

Страница 10: ...ngs 1 Remove the top cover from the motor to gain access to the motor terminals and auxiliary cams 2 Disconnect the controller from the motor 3 Connect a current source to the positive and negative terminals 4 Drive the motor to the position where the auxiliary equip ment is to be switched by increasing or decreasing the current 5 For a switch differential of 1 check continuity of auxiliary switch...

Страница 11: ... at the desired point of motor rotation Inspect the motor linkage and valve or damper to see that all mechanical connections are correct and secure In damper installations the pushrod should not extend more than a few inches past the ball joints Check to see that there is adequate clearance for the linkage to move through its stroke without binding or striking other objects See controller or syste...

Страница 12: ...oneywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 63 2640 07 M S Rev 05 10 Printed in U S A ...

Отзывы: