S7810M MODBUS™ MODULE
7
65-0249—4
Table 11. ModBus™ R7999 Register Assignments.
Address
(hex)
Register
(dec)
Parameter Name
0x0C
Format
Notes
0080
40129
R7999 reserved
U16
Not used—always zero.
0081
40130
R7999 program mode
3
U16
0—Initiate State.
1—Normal Operation.
2—Alarm Initiate State.
3—Lockout.
4—Not Configured.
5—Factory Test.
6—Low Voltage.
7—Commissioning.
8—Reset.
0082
40131
R7999 fault code
4
U16
See Table 26.
0083
40132
R7999 operational status
5
U16
00—Standby Hold.
01—Standby Stop Position.
02—Standby Main Valve.
03—Standby Low Fire Main Valve.
04—Standby Purge.
05—Fault 1.
06—Standby Hi Fire Main Valve.
07—Fault 2.
08—Processing Demand.
09—Light Off.
10—Modulate.
11—Light Off Low Fire Main Valve.
12—Purge.
13—Fault 3.
14—Purge Main Valve.
15—Fault 4.
16—Initialize.
17—Post Purge.
0084
40133
R7999 air position
6-7
U16
0-4095
0085
40134
R7999 active fuel position
8-9
U16
0-4095
0086
40135
R7999 fgr position
10-11
U16
0-4095
0087
40136
R7999 fuel id
3.7
U16
0 = Fuel 1
1 = Fuel 2
0088-
0089
40137-
40138
R7999 cycles
10-13
U32
008A
40139
R7999 diagnostic bits.
6, 8,
10, 12
U16
Bit Meaning
15— LCO state
14—HFP state
13—LFP state
12—ALARM state
11—LCI state
10—HF state
9—MV state
8—LF state
7—LCO Relay Drive 2 feedback
6—LCO Relay Drive 1 feedback
5—LCM state
4—AUTO/MAN select
3—Selected Fuel
2—Fuel Select 2 Input
1—Fuel Select 1 Input
0—Hold State
008B
40140
R7999 firing rate input
12
U16
0-255 = 0-21.1 mA.
008C
40141
R7999 manual pot input
13
U16
0-255 = 2.1-44.1 mA.
008D
40142
R7999 auxiliary input
14
U16
0-255 = 0-21.1 mA.
008E
40143
Unused
008F
40144
R7999 Hold
3,4
U16
Same as register 40139 bit 0
0090-
009E
40145-
40159
Unused