S7810M MODBUS™ MODULE
65-0249—4
16
7800 SERIES Burner Control Fault History Records
Table 18 describes the registers that are part of a fault history record.
To determine the actual register address for a parameter within the
record, add the register offset to the start address of the record
.
Expanded Annunciator
The codes shown in Table 19 are available in the Expanded
Annunciator First Out Code Register. These codes are normally
translated to the appropriate fault code by the Burner Control. The
fault code will then be translated to the appropriate first and second
line messages as shown in Table 17 for use by the UMC800 Operator
Interface.
207
FAULT 23k: LOW OIL TEMP
EA
62
208
FAULT 23j: HIGH OIL TEMP
EA
44
209
FAULT 23i LOW OIL PRESSURE
EA
61
210
FAULT 23h: HIGH OIL PRESSURE
EA
43
211
FAULT 23g: BOTH FUELS SELECT
EA
21
212
FAULT 23f: FUEL SELECT OFF
EA
38
213
FAULT 23e: AUX LIMIT #3
EA
19
214
FAULT 23d: HIGH LIMIT
EA
42
215
FAULT 23c: LWCO
EA
63
216
FAULT 23b: AUX LIMIT #2
EA
18
217
FAULT 23a: AUX LIMIT #1
EA
17
218
FAULT 22s: OTHER INTERLOCKS
EA
74
219
FAULT 22r: AUX INTERLOCK #5
EA
16
220
FAULT 22q: AUX INTERLOCK #4
EA
15
221
FAULT 22p: AIRFLOW SWITCH
EA
13
222
FAULT 22o: LOW GAS PRESSURE
EA
59
223
FAULT 22n: HIGH GAS PRESSURE
EA
41
224
FAULT 22m: ATOMIZING SW
EA
14
225
FAULT 22k: LOW OIL TEMP
EA
62
226
FAULT 22j: HIGH OIL TEMP
EA
44
227
FAULT 22i: LOW OIL PRESSURE
EA
61
228
FAULT 22h: HIGH OIL PRESSURE
EA
43
229
FAULT 22g: BOTH FUELS SELECT
EA
21
230
FAULT 22f: FUEL SELECT OFF
EA
38
231
FAULT 22e: AUX LIMIT #3
EA
19
232
FAULT 22d: HIGH LIMIT
EA
42
233
FAULT 22c: LWCO
EA
63
234
FAULT 22b: AUX LIMIT #2
EA
18
235
FAULT 22a: AUX LIMIT #1
EA
17
236
FAULT 21s: OTHER INTERLOCKS
EA
74
237
FAULT 21r: AUX INTERLOCK #5
EA
16
238
FAULT 21q: AUX INTERLOCK #4
EA
15
239
FAULT 21p: AIRFLOW SWITCH
EA
13
240
FAULT 21o: LOW GAS PRESSURE
EA
59
241
FAULT 21n: HIGH GAS PRESSURE
EA
41
242
FAULT 21m: ATOMIZING SW
EA
14
243
FAULT 21k: LOW OIL TEMP
EA
62
244
FAULT 21j: HIGH OIL TEMP
EA
44
245
FAULT 21i: LOW OIL PRESSURE
EA
61
246
FAULT 21h: HIGH OIL PRESSURE
EA
43
247
FAULT 21g: BOTH FUELS SELECT
EA
21
Table 17. 7800 SERIES Fault Codes. (Continued)
Fault Code
(Reg 40001)
Fault Message
(NOTE: FAULT n: is not in
the Fault and Strings Code)
Fault String
Code
(Table 16)
248
FAULT 21f: FUEL SELECT OFF
EA
38
249
FAULT 21e: AUX LIMIT #3
EA
19
250
FAULT 21d: HIGH LIMIT
EA
42
251
FAULT 21c: LWCO
EA
63
252
FAULT 21b: AUX LIMIT #2
EA
18
253
FAULT 21a: AUX LIMIT #1
EA
17
254
FAULT 10z: OTHER PREIGN ILK
EA
75
255
FAULT 10y: VALVE CLOSURE
EA
109
Table 18. Fault History Record Format.
Offset
Parameter Name
Access
Format
Notes
0
Fault code
R
U16
See Table 17.
1
Fault String
R
U16
See Table 16.
2
Sequence State
R
U16
See Table 15.
3
First line message
R
U16
See Table16.
4
Second line message R
U16
See Table 16.
5
Sequence time
R
U16
Seconds.
6-7
Total cycles
R
U32
8-9
Total hours
R
U32
Table 19. Expanded Annunciator First Out Code.
EA Status Value
(binary)
Status Message
Line 2 String Code
(Table 16)
0xx 00000
No Expanded Annunciator N/A
0xx 00001
Burner Sw.
23
0xx 00010
Operating Control
72
0xx 00011
Aux. Limit #1
17
0xx 00100
Aux. Limit #2
18
0xx 00101
LWCO
63
0xx 00110
High Limit
42
0xx 00111
Aux. Limit #3
19
0xx 01000
FuelSelect Off
38
0xx 01001
BothFuelSelect
21
0xx 01010
High Oil Pres.
43
0xx 01011
Low Oil Pres.
61
0xx 01100
High Oil Temp
44
0xx 01101
Low Oil Temp.
62
0xx 01110
Atomizing Sw.
14
Table 17. 7800 SERIES Fault Codes. (Continued)
Fault Code
(Reg 40001)
Fault Message
(NOTE: FAULT n: is not in
the Fault and Strings Code)
Fault String
Code
(Table 16)