S7810M MODBUS™ MODULE

65-0249—4

4

Table 1. S7810M Terminal Identification.

MODE LED Light Patterns

Table 2 explains the MODE LED light patterns.

Table 2. Explanation of MODE LED light patterns. 

OPERATION

The S7810M ModBus™ Data ControlBus™ Module has two 

communications ports. The ControlBus™ communications port allows 

communications on a bus that contains a 7800 SERIES burner 

controller and an S7800 Keyboard Display Module and/or an S7830 

Expanded Annunciator and/or an R7999 ControLinks™ Controller.

A second communications port supports RS-485 communications 

using ModBus

TM 

protocol. The following tables provide ModBus™ 

mapping information.

Table 10 provides register mapping. It identifies the mapping of the 

7800 SERIES parameters to ModBus™ registers.  These codes are 

transmitted by the relay modules and the S7830 Expanded 

Annunciator.

Function Codes

Supported function codes of Modbus Protocol Reference Guide 

(PI-MBUS-300 Rev. J) are 3, 4, 6, and 17. Function codes 3 and  4 

are treated the same by the S7810M. Two registers need to be read 

when the data format is a U32 value (4 bytes); if both registers are 

not read, then a data value of 0 (zero) is returned. U32 values are in 

little endian format. The maximum number of addresses that can be 

queried is 127 (0x7F) for each query message.

Tables 3 through 7 provide information on the function codes.

NOTE:

All Query and Response cells below are 1 byte.

Table 3. Query Message Format for Function Codes 3 and 4.

Table 4. Response Message Format for Function Codes 3 and 4.

Table 5. Query Message Format for Function Code 6 (Broadcast is supported by using a slave address of 00).

Table 6. Response Message Format for Function Code 6 (There is no response if the query was broadcast.)

Table 7. Query Message Format for Function Code 17.

NOTE:

See Table 20 for function code 17 response format.

Table 8. Exception Response Message Format.

Signal

S7810M Terminal

ControlBus™ Data +

1

ControlBus™ Data -

2

Common

ControlBus™ Common

+13 Vdc Common

Remote Reset Common

3

+13 Vdc

4

Remote Reset

5

ModBus™ Common

6

ModBus™ Data +

7

ModBus™ Data -

8

LED Code/

Behavior

Pulse Period

Interval

Meaning

Always OFF

OFF

Not powered or device 

failure.

Always ON

ON

S7810M device failure.

Mostly ON 

with 1 blink

50 ms (OFF)

second

Both ControlBus™ and 

Modbus are active

Mostly OFF 

with 1 flash

50 ms (ON)

3.85 

seconds

ControlBus™ is active, 

and Modbus is not active.

Mostly OFF 

with 2 pulses

2 x (200 ms ON, 

200 ms OFF)

1.75 

seconds 

Program CRC error.

Mostly OFF 

with 3 pulses

3 x (200 ms ON, 

200 ms OFF)

2.15 

seconds

No ControlBus™ signal 

from the Burner Control

Slave Address

Function Code

Starting 

Address High

Starting 

Address Low

Number of 

Addresses High

Number of 

Addresses Low

CRC

CRC

01

03

00

0A

00

01

A4

08

Slave Address

Function Code

Byte Count

Data High

Data Low

CRC

CRC

01

03

02

00

22

38

5D

Slave Address Function Code

Starting 

Address High

Starting 

Address Low

Preset Data 

High

Preset Data 

Low

CRC

CRC

01

06

00

7F

00

04

B9

D1

Slave Address Function Code

Starting 

Address High

Starting 

Address Low

Preset Data 

High

Preset Data 

Low

CRC

CRC

01

06

00

7F

00

04

B9

D1

Slave Address Function Code

CRC

CRC

03

11

C1

4C

Slave 

Address

Function 

Code 

+ 80h

Exception 

Code

CRC

CRC

Содержание ModBus S7810M

Страница 1: ...t of a 7800 SERIES Relay Module FEATURES Multi dropped communications bus interface Remote control capabilities Standby Hold Drive to High Fire Drive to Low Fire Reset Ability to remotely mount a Keyboard Display Module S7810M1029 meets Gastec approval cannot be reset through data highway SPECIFICATIONS Model S7810M ModBus Module Electrical Ratings Voltage and Frequency 13 Vdc peak full wave recti...

Страница 2: ...ply with the limits for a Class B computing device pursuant to Subpart J of Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is likely to cause interference in which case users at their own expense will be required to take whatever measures may be required t...

Страница 3: ...2 1 7800 SERIES RELAY MODULE 8 7 6 5 4 3 2 1 7800 SERIES RELAY MODULE INPUT OUTPUT GND GND 1 2 3 4 5 A B C MOMENTARY PUSHBUTTON SWITCH S7800 REMOTE KEYBOARD DISPLAY MODULE S7830 EXPANDED ANNUNCIATOR A B C R7999 CONTROLINKS CONTROLLER RS 485 REPEATER A WITHOUT RS 485 REPEATER LOCAL RS 485 COMMUNICATION BUS THE DEVICES ON THIS BUS MUST BE WIRED IN A DAISY CHAIN CONFIGURATION THE ORDER OF INTERCONNEC...

Страница 4: ... for Function Codes 3 and 4 Table 5 Query Message Format for Function Code 6 Broadcast is supported by using a slave address of 00 Table 6 Response Message Format for Function Code 6 There is no response if the query was broadcast Table 7 Query Message Format for Function Code 17 NOTE See Table 20 for function code 17 response format Table 8 Exception Response Message Format Signal S7810M Terminal...

Страница 5: ...ENOSE PLIERS M17650 Table 10 ModBus Register Assignments Address hex Register dec Parameter Name Read Write Format Notes 0000 40001 Burner Control BC Fault Code R U16 See Table 17 0001 40002 BC Fault String Code R U16 See Table 16 0002 40003 BC Sequence State R U16 See Table 15 valid only if Fault code 0 0003 40004 BC State String Code line 1 R U16 See Table 16 0004 40005 BC State String Code line...

Страница 6: ... control command 0055 40086 BC Flame Amplifier type R U16 0 Standard 1 Unknown 2 Amplicheck or missing amplifier 3 Shutter 0056 40087 BC Purge Time R U16 Seconds 0057 0065 40088 40102 BC Diagnostics R U16 String codes indicating terminal jumper state See Table 16 There are 15 codes Not all are used for some burner controls 0066 007E 40103 40127 Unused 007F 40128 BC Remote Command W U16 Only one bi...

Страница 7: ...ault 3 14 Purge Main Valve 15 Fault 4 16 Initialize 17 Post Purge 0084 40133 R7999 air position 6 7 U16 0 4095 0085 40134 R7999 active fuel position 8 9 U16 0 4095 0086 40135 R7999 fgr position 10 11 U16 0 4095 0087 40136 R7999 fuel id 3 7 U16 0 Fuel 1 1 Fuel 2 0088 0089 40137 40138 R7999 cycles 10 13 U32 008A 40139 R7999 diagnostic bits 6 8 10 12 U16 Bit Meaning 15 LCO state 14 HFP state 13 LFP s...

Страница 8: ... closed endpoint U16 0 4095 0163 40356 Fuel 2 open endpoint U16 0 4095 0164 40357 Inactive motor position U16 0 4095 0165 40358 Registers 40353 40357 are current U16 0 1 0166 40359 Air closed endpoint position U16 0 4095 0167 40360 Air open endpoint position U16 0 4095 0168 40361 FGR closed endpoint position U16 0 4095 0169 40362 FGR open endpoint position U16 0 4095 016A 40363 Unused U16 016B 403...

Страница 9: ...igured 1 Low Fire Hold Position the FGR Air and Fuel actuators at the Light Off Position 2 Modulate with FGR closed FGR closed Air and fuel modulating 3 Low Fire Hold with FGR closed FGR closed Air and Fuel at Light Off Position Configuration Options U16L If a Bit 1 then the option is configured Bit 0 FGR is set to follow the profile curve during purge Bit 1 Maximum Firing rate is controlled by th...

Страница 10: ...Table 14 for register numbers and variables Table 14 Temperature Data Registers 7800 SERIES Sequence State Codes Sequence state codes are provided by the Burner Control Each code is translated into two string codes for displaying an associated message in two lines Each code is also translated into burner control state bits which may be used to generate and control system diagrams on an operator in...

Страница 11: ...ner Control State Bits Line 1 Line 2 26 PILOT HOLD TEST RUN TEST SWITCH 77 98 4008h 27 PILOT HOLD START SWITCH 77 106 4008h 28 MAIN IGN 66 0 0010h 29 MAIN IG HOLD MANUAL OPEN SWITCH 67 72 4010h 30 RUN 95 0 0020h 31 RUN PV HOLD LOW FIRE SWITCH 96 58 4020h 32 PVHOLD IGN 96 66 4020h 33 PV HOLD PV HOLD SWITCH 96 45 4020h 34 RUN LOWFIRE TEST RUN TEST SWITCH 97 98 4020h 35 POSTPURGE 83 0 0040h 36 STATE ...

Страница 12: ...h 78 RUN HOLD EA 188 Table 19 4020h 79 POSTPURGE HOLD EA 189 Table 19 4040h 80 PREIGNITION HOLD EA 190 Table 19 4080h Table 15 7800 SERIES Sequence State Codes and Associated register code values Continued cb_sqst Value 7800 SERIES Sequence State String Code Uses mm ss Burner Control State Bits Line 1 Line 2 Table 16 7800 SERIES String codes String Code String 0 blank 1 1 2 1 1 3 1 2 4 1 3 5 1 4 6...

Страница 13: ...TE CONTROL Table 16 7800 SERIES String codes Continued String Code String 95 RUN 96 RUN HOLD 97 RUN LOWFIRE 98 RUN TEST SWITCH 99 RUNNING ILK 100 RUNNING ILK ON 101 RUNNING INTERLOCK 102 SAFETY CHECK 103 STANDBY 104 STANDBY HOLD 105 START 106 START SWITCH 107 START SWITCH ON 108 TEST STATE 109 VALVE CLOSURE 110 ALL SWITCHES ON 111 RESET ALARM TEST 112 Run Test Switch RUN 113 Run Test Switch TEST 1...

Страница 14: ...HOLD EA 190 PREIGNITION HOLD EA Table 16 7800 SERIES String codes Continued String Code String Table 17 7800 SERIES Fault Codes Fault Code Reg 40001 Fault Message NOTE FAULT n is not in the Fault and Strings Code Fault String Code Table 16 0 Blank no fault 0 1 FAULT 1 NO PURGE CARD 73 2 FAULT 2 AC FREQUENY NOISE 8 3 FAULT 3 AC LINE DROPOUT 9 4 FAULT 4 AC FREQUENCY 7 5 FAULT 5 LOW LINE VOLTAGE 60 6...

Страница 15: ...A 16 Table 17 7800 SERIES Fault Codes Continued Fault Code Reg 40001 Fault Message NOTE FAULT n is not in the Fault and Strings Code Fault String Code Table 16 166 FAULT 30q AUX INTERLOCK 4EA 15 167 FAULT 30p AIRFLOW SWITCHEA 13 168 FAULT 30o LOW GAS PRESSUREEA 59 169 FAULT 30n HIGH GAS PRESSUREEA 41 170 FAULT 30m ATOMIZING SWEA 14 171 FAULT 30k LOW OIL TEMPEA 62 172 FAULT 30j HIGH OIL TEMPEA 44 1...

Страница 16: ...21s OTHER INTERLOCKSEA 74 237 FAULT 21r AUX INTERLOCK 5EA 16 238 FAULT 21q AUX INTERLOCK 4EA 15 239 FAULT 21p AIRFLOW SWITCHEA 13 240 FAULT 21o LOW GAS PRESSUREEA 59 241 FAULT 21n HIGH GAS PRESSUREEA 41 242 FAULT 21m ATOMIZING SWEA 14 243 FAULT 21k LOW OIL TEMPEA 62 244 FAULT 21j HIGH OIL TEMPEA 44 245 FAULT 21i LOW OIL PRESSUREEA 61 246 FAULT 21h HIGH OIL PRESSUREEA 43 247 FAULT 21g BOTH FUELS SE...

Страница 17: ...ILK 4 15 0xx 10011 Aux ILK 5 16 0xx 10100 All Switches On or Other PII if hold or lockout condition exists 110 75 0x1 XXXX Valve Closure 109 00XX XXXX Oil Select N A 01XX XXXX Gas Select N A If the BC is in Standby and the 5LSB value is 1 16 then the cause of the Standby Hold is the 5LSB value otherwise the hold is Circuit Fault Table 19 Expanded Annunciator First Out Code Continued EA Status Valu...

Страница 18: ...text enumeration as R7999 Status Message 0x0C byte 5 Register 40132 4 Not implemented U16H 1 6 Unused U16L 255 5 Data in the previous 5 registers is current U16 0 1 Table 25 R7999 Status Message Byte s Description R7999 circular buffer data structure of registers 40161 40208 Some of this data is interpreted by the S7810M and is available in registers 40129 40144 0 Program Mode Selected Fuel Bits D...

Страница 19: ...4 FGR Pot Feedback 0x45 Air Wiper Resistance 0x46 F1 Wiper Resistance 0x47 F2 Wiper Resistance 0x48 FGR Wiper Resistance 0x49 Air Total Resistance 0x51 F1 Total Resistance 0x52 F2 Total Resistance 0x53 FGR Total Resistance 0x58 Stuck Reset 0x61 Initiate Timeout 0x67 Fuel Off Curve 0x68 FGR Off Curve 0x69 Air Off Curve 0x71 Air Offline 0x72 F1 Offline 0x73 F1 Offline 0x74 FGR Offline 0x82 Motor Spe...

Страница 20: ...e North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers Contact Esys for more information about this product Esys The Energy Control Company website http www esys us 4520 Stine Road Ste 7 Bakersfield CA 93313 661 833 1902 email esys us ...

Отзывы: