background image

ML6874 

OPERATION AND CHECKOUT 

Operation and checkout 

Operation: 

The recommended valve actuator power source is a class 
2, 24V transformer or 28Vdc across terminals T5 &T6. 
Internal circuitry provides dc power for the electronic 
sensing and drive motor circuits. 

The motor is controlled by a microprocessor. Connecting 
B to R tells the microprocessor to cause the actuator to 
drive open, i.e. UP, in the Direct Acting Mode. 
Connecting W & R will cause the actuator to drive closed, 
i.e. DOWN, in the Direct Acting Mode. For "floating" 
control, if R remains open, the actuator will remain in the 
last position. The DIP switches are scanned only on power 
up, and tell the microprocessor if Direct or Reverse mode 
is desired. Changes in the DIP switch setting will only 
take effect if the power is off while the change is made. 

At the end of the valve stroke, the actuator will develop 
the  necessary force for positive valve close-off. As forces 
are developed, the current to the motor increases. The 
microprocessor stops the actuator automatically when the 
motor current, and forces reach the predetermined level. 

CAUTION: 

1. Disconnect power supply before beginning installation 

to prevent electrical shock and equipment damage. 

2. All wiring must comply with applicable local electrical 

codes, ordinances and regulations. 

3. Make certain that the voltage and frequency of the 

power supply  correspond to the rating of the device. 

4. DO NOT connect 24 Vac between any signal input 

terminals. 

5. DO NOT electrically operate the ML6874 before 

assembly to the valve because damage not apparent 
to the installer  may occur. 

GENERAL NOTE

1. For correct valve operation, the ML6874 must be field 

configured with the DIP switches which are located 
beside the terminal block, see wiring diagrams for 
details. Turn power off  before setting  the DIP 
switches . 

2. There is a short delay in actuator response upon every 

signal change. It is to screen any unwanted incoming 
signals. 

3. For proper operation,  voltage on the T5 & T6 must not 

be less than 22Vac or 24Vdc during running or force 
generating stages. 

REPLACEMENT NOTE: 

1.  The   old ML684 actuators cannot be used with new 

ML6874 valve actuators in the same circuitry, unless they 
are isolated by an isolation relay to prevent cross-talking. 

2. The ML6874 is a direct replacement for the old 

ML684A1025 (160 lbs) in single actuator hook-up, 
except when replacing the old reverse acting models, the 
signal input wires to the new devices are no longer 
needed to be reversed. Just set the DIP switch as shown in 
Fig.7. 

3. DO NOT replace the ML684A1009 (80 lbs ) with this 

new ML6874 on the V5045 valve. 

Checkout:( see General & Replacement Note ) 

1. Make sure the valve stem is completely screwed into the 

actuator drive shaft with no threads showing. 

2. Make sure the valve stem is locked in place with the set 

screw. 

3. Check DIP switches for proper setting for Direct or 

Reverse Acting mode. 

4. Connect R & B. Valves stem should move up, in Direct 

Acting mode. 

5. Connect R & W. Valves stem should move down, in 

Direct Acting mode. 

6. For Floating operation, open R connection. Valve stem 

should remain in position. 

7. Operate the system ( valve, actuator and controller ) for 

several cycles to ensure proper installation. 

8. When checkout is complete, return the controller to the 

desired setting. 

Home and Building Control 
Honeywell Limited/Limitee 

Home and Building Control 
Honeywell Inc. 

Helping You Control Your World 

155 Gordon Baker Road 

1985 Douglas Drive North 

North York , ON 

Golden Valley, MN 55422 

Canada  M2H 3N7

                                                                                                          www.honeywell.com/building/components 

Содержание ML6874

Страница 1: ... Self contained motorized valve linkage Linkage self adjusts to valve stroke of up to 19mm 3 4 Multipose mounting Strong valve seat closing force 710 Newton 160 lbs Compact size for easy installation in confined area Field configurable DIP switches for Direct Reverse action One device for either Vac or Vdc power supply application Electronic current sensing provides internal protection and positiv...

Страница 2: ...s for 3 4 stroke Closing Force 710N 160 lbs Nominal Rating applies to both directions Performance Specifications Life Expectancy at rated load and power conditions 50 000 full stroke cycles plus 1 000 000 repositions at 10 stem travel or 10 years whichever occurs first Note rapid cycling repositioning will result in reduced service life of the actuator Ordering Information When purchasing replacem...

Страница 3: ...ion The button itself is not needed 4 Slide the position indicator plastic disk or rubber O ring over the valve stem See inset Fig 3 Indicator will self align to the marking on the yoke after one complete operating cycle Assembly of ML6874 to the valve 1 The drive shaft of the ML6874 has a threaded hole to link with the valve stem Slide the yoke over the valve bonnet Fig 4 2 Thread the ML6874 driv...

Страница 4: ...of set screw both are included in the plastic bag into the top of the shaft slotted Hexed side up Or use the set screw from the valve stem button 6 Depending on which type of set screw was used with a 5 mm 3 16 Slotted screwdriver or 1 8 x 6 Allen wrench included in the plastic bag tighten the set screw to lock valve stem in place Fig 6 WARNING g FIG 5 U BOLT ASSEMBLY 4 FIG 4 ASSEMBLY OF ML6874A T...

Страница 5: ...g of the transformer is not exceeded and proper phasing is observed Use configuration DIP switches to select device functions Direct acting function actuator stem moves upwards with R B closed or Reverse acting function actuator stem moves downwards with R B closed DO NOT reverse wiring SPDT controller can be a low voltage Series 20 on off or Series 60 floating center off type Configuration FUNCTI...

Страница 6: ...onfigured with the DIP switches which are located beside the terminal block see wiring diagrams for details Turn power off before setting the DIP switches 2 There is a short delay in actuator response upon every signal change It is to screen any unwanted incoming signals 3 For proper operation voltage on the T5 T6 must not be less than 22Vac or 24Vdc during running or force generating stages REPLA...

Отзывы: