background image

ML6874 

SPECIFICATIONS •INSTALLATION 

FIG. 1 -- DIMENSIONS OF ML6874 VALVE ACTUATOR IN MM (INCHES). 

Installation 

FIG.2 -- MINIMUM MOUNTING CLEARANCE. 

CAUTION 

1. Installer must be a trained service technician. 
2. DO NOT electrically operate the ML6874 

before assembly  to the valve because damage 
not apparent to the installer may occur. 

Mounting: 

1.  Ensure that the valve body is installed correctly, that is, the 

arrow points in the direction of the flow. 

2.  Although the actuator can be mounted in any position, it is 

preferable that the ML6874 is mounted above the valve 
body. This will minimize the risk of damage to the 
ML6874 in the event of condensation or a valve gland 
leak. 

3.  Remove the stem button (Fig. 3) from the valve stem. Save 

the set screw inside the stem button for later installation. 
The button itself is not needed. 

4.  Slide the position indicator (plastic  disk or rubber O-ring) 

over the valve stem. (See inset, Fig. 3) Indicator will self­
align to the marking on the yoke after one complete 
operating cycle. 

Assembly of ML6874 to the valve: 

1. The drive shaft of the ML6874 has a threaded hole to link 

with the valve stem. Slide the yoke over the valve bonnet 
(Fig. 4) 

2. Thread the ML6874 drive shaft onto the valve stem all the 

way, until it is completely attached (with no threads 
showing)
, by turning the valve actuator in a clockwise 
direction, as viewed from above (depending on the valve 
models, use a pin or wrench to keep valve stem from 
turning). Note that the valve actuator is shipped with drive 
shaft in the mid-position. 

3. Care should be exercised when using tools on the valve 

stem during tightening. (Fig.4) DO NOT damage the 
threads or other parts of the stem. 

4.  Orient the conduit hole to the most desirable direction, then 

tighten the LOCKNUTS on the U-bolt. 

Содержание ML6874

Страница 1: ... Self contained motorized valve linkage Linkage self adjusts to valve stroke of up to 19mm 3 4 Multipose mounting Strong valve seat closing force 710 Newton 160 lbs Compact size for easy installation in confined area Field configurable DIP switches for Direct Reverse action One device for either Vac or Vdc power supply application Electronic current sensing provides internal protection and positiv...

Страница 2: ...s for 3 4 stroke Closing Force 710N 160 lbs Nominal Rating applies to both directions Performance Specifications Life Expectancy at rated load and power conditions 50 000 full stroke cycles plus 1 000 000 repositions at 10 stem travel or 10 years whichever occurs first Note rapid cycling repositioning will result in reduced service life of the actuator Ordering Information When purchasing replacem...

Страница 3: ...ion The button itself is not needed 4 Slide the position indicator plastic disk or rubber O ring over the valve stem See inset Fig 3 Indicator will self align to the marking on the yoke after one complete operating cycle Assembly of ML6874 to the valve 1 The drive shaft of the ML6874 has a threaded hole to link with the valve stem Slide the yoke over the valve bonnet Fig 4 2 Thread the ML6874 driv...

Страница 4: ...of set screw both are included in the plastic bag into the top of the shaft slotted Hexed side up Or use the set screw from the valve stem button 6 Depending on which type of set screw was used with a 5 mm 3 16 Slotted screwdriver or 1 8 x 6 Allen wrench included in the plastic bag tighten the set screw to lock valve stem in place Fig 6 WARNING g FIG 5 U BOLT ASSEMBLY 4 FIG 4 ASSEMBLY OF ML6874A T...

Страница 5: ...g of the transformer is not exceeded and proper phasing is observed Use configuration DIP switches to select device functions Direct acting function actuator stem moves upwards with R B closed or Reverse acting function actuator stem moves downwards with R B closed DO NOT reverse wiring SPDT controller can be a low voltage Series 20 on off or Series 60 floating center off type Configuration FUNCTI...

Страница 6: ...onfigured with the DIP switches which are located beside the terminal block see wiring diagrams for details Turn power off before setting the DIP switches 2 There is a short delay in actuator response upon every signal change It is to screen any unwanted incoming signals 3 For proper operation voltage on the T5 T6 must not be less than 22Vac or 24Vdc during running or force generating stages REPLA...

Отзывы: