background image

ML6284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR

5

63-2505

Fig. 2. Installing mounting bracket on ML6284 Non-Spring 

Return Direct Coupled Damper Actuator. NOTE: Install 

mounting bracket so mounting bracket tab is centered in 

actuator slot.

A typical actuator mechanical connection is shown in Fig. 4; 

wiring diagrams in Fig. 5 through 10.

The ML6284 Non-Spring Return Direct Coupled Damper 

Actuator can also be three-point mounted using the two front 

gear housing slots and the adapter bracket. Two screws are 

secured through the two front gear housing slots and the 

adapter bracket positioned to secure the rear of the actuator. 

Three point mounting is used for foot mounting the actuator or 

internally mounting the actuator in the duct when direct shaft 

coupling is not possible.

CAUTION

Equipment Damage Hazard.

Improper mounting will damage the actuator.

Do not use the actuator as a shaft bearing. The 

actuator must be used only to supply rotational torque. 

To prevent damage to the actuator, avoid any side 

loads to the actuator output coupling bearings.

Preparation

Before installing the ML6284 on the damper shaft, determine 

the opening direction of the damper shaft (see Fig. 2) to 

correctly connect the wiring. 

Installation

Installing Actuator and Mounting Bracket 
(Single Point Mounting)

1.

Place the ML6284 Non-Spring Return Direct Coupled 

Damper Actuator over the damper shaft.

2.

Position the actuator for best access to the actuator 

damper shaft locking screw.

3.

Install the mounting bracket (see Fig. 2) and adjust it so 

the bracket tab is midway in the actuator slot. Mark the 

screw holes for installing the mounting bracket on the 

damper housing.

4.

Remove the mounting bracket and actuator.

5.

Drill or center punch the starting holes for the mounting 

bracket screws (or use no.10 self-tapping sheet metal 

screws—not  supplied).

6.

Place the actuator and mounting bracket back into 

position over the damper shaft and install the mounting 

bracket screws.

7.

Move damper shaft either fully clockwise 

or fully 

counterclockwise

8.

Fully depress and hold disengage button while moving 

the actuator hub either fully clockwise

or fully 

counterclockwise

to match the damper shaft. 

Release disengage button.

9.

Tighten the two 8 mm by 12 mm long set screws firmly 

against the damper shaft (maximum tightening torque is 

100 lb-in.).

Wiring

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property 

damage.

Disconnect power supply before wiring to prevent 

electrical shock or equipment damage.

All wiring must comply with local electrical codes, ordinances 

and regulations. The ML6284 is designed for use with a Class 

2 power supply. Voltage and frequency of the transformer 

used must correspond with the characteristics of the motor 

and those of the power supply. Standard electrical connection 

is shown in Fig. 4. See Fig. 5 and 6 for typical wiring 

connections.

The ML6284 has a plastic housing with two taped holes  on 

the end of the device for 1/2 in. conduit fittings.

ML6284 Models with Factory-mounted Auxiliary Switches 

(See Fig. 7)

ML6284C,F models have two nonadjustable low voltage rated 

spdt auxiliary switches that are factory set to make common to 

normally open at 12° and 82° rotation from the closed  

counter-clockwise stop. See Fig. 7.

M7876

ACTUATOR 

SLOT

Содержание ML6284

Страница 1: ...it switch adjustments by limiting stall torque to 250 lb in 28 3 N m maximum 95 stroke provides necessary compression of rubber neoprene gaskets commonly used on 90 low leakage dampers Manual clutch allows for manual adjustment 92 second synchronous timing can eliminate need for feedback position indication in closed loop temperature control applications Removable splined output hub permits premou...

Страница 2: ...t Duty Feedback Resistor 500 ohm linear potentiometer Cable Ratings Control Standard models include nonplenum UL CSA rated 30V 60 C 20 gauge cable Auxiliary Switch UL CSA rated 300V 90 C 18 gauge Controller Type Floating spdt Torque Ratings at Rated Voltages Lift and Hold Minimum 150 lb in 17 N m Breakaway Minimum 150 lb in 17 N m Stall Minimum 150 lb in 17 N m Stall Maximum 250 lb in 28 3 N m Tor...

Страница 3: ...or and mounting bracket in in mm 9 32 7 3 PLACES 1 17 32 39 3 3 32 79 4 102 7 16 11 1 1 4 32 7 11 16 196 8 7 16 215 36 914 1 2 12 5 8 17 13 32 10 1 2 13 3 4 19 7 8 22 1 25 3 5 32 80 1 2 13 1 2 13 1 11 16 43 2 1 2 63 3 5 16 84 4 1 2 114 5 127 6 152 1 4 6 1 1 REMOVABLE RETAINING RING FOR REMOVAL OF HUB SLEEVE M7618B 1 4 6 1 8 3 2 51 15 16 24 1 29 32 48 ...

Страница 4: ...ing accessories and for servicing Mounting The ML6284 Non Spring Return Direct Coupled Damper Actuator is designed to operate a damper by driving the damper shaft either cw or ccw depending on damper design All actuators are shipped in the fully closed position The ML6284 Non Spring Return Direct Coupled Damper Actuator is designed with removable hub inserts to accommodate specific damper shaft si...

Страница 5: ...e bracket tab is midway in the actuator slot Mark the screw holes for installing the mounting bracket on the damper housing 4 Remove the mounting bracket and actuator 5 Drill or center punch the starting holes for the mounting bracket screws or use no 10 self tapping sheet metal screws not supplied 6 Place the actuator and mounting bracket back into position over the damper shaft and install the m...

Страница 6: ...act It stops when neither contact is made IMPORTANT The ML6284 can operate with DDC controller that emulates an spdt break before make switch Do not short cycle the actuator Short cycling of the actuator can cause premature failure The actuator has a position indicator to show shaft position As the indicator moves with the shaft it gives an angular representation of the damper position There are f...

Страница 7: ...NS AND OVERLOAD PROTECTION AS REQUIRED 500 OHM POTENTIOMETER ORANGE OPEN TAN GREEN CLOSED L1 HOT L2 1 1 2 2 3 3 MOTOR TIME OUT 24 VAC B BLUE W YELLOW T2 RED T1 BLACK ML6284 M4884A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TIME OUT FUNCTION AVAILABLE WITH ML6284D F MODELS 500 OHM POTENTIOMETER ORANGE OPEN TAN GREEN CLOSED 12 82 M7877A COMMON COMMON NO NO NC NC WHITE ...

Страница 8: ...s low check power supply and controller 3 If the actuator does not drive in the correct direction when a control signal is applied reverse the yellow and blue wires 4 Remove power and fully depress and hold disengage button down while turning damper shaft clockwise and counterclockwise If the damper shaft turns freely through the entire 90 stroke and the actuator is installed correctly replace the...

Отзывы: