background image

ML6284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR

63-2505

4

Environmental Protection Ratings: 

NEMA1 standard with 

damper shaft in horizontal position.

Accessories:

205617 Hub Insert, 3/4 in. round.

205753 Hub Insert, 3/8 in.

205758 Hub Insert, 5/8 in.

205820A 3-Point Mounting Kit.

205685 Crank-Arm Accessory.

205850B End Stop Kit.

INSTALLATION

When Installing this Product…

1.

Read instructions carefully. Failure to follow them could 

damage the product or cause a hazardous condition.

2.

Check ratings and description given in the specifications 

to make sure the product is suitable for your application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property 

damage.

Disconnect power before installation to prevent 

electrical shock or equipment damage.

CAUTION

Equipment Damage Hazard.

Can cause equipment damage or failure.

1.

 Never turn motor output hub by hand or wrench.

2.

 Do not install actuator in areas with acid fumes or 

other deteriorating vapors that might attack the 

metal parts of the actuator. 

WARNING

Fire or Explosion Hazard.

Can cause severe injury, death or property 

damage.

Do not install actuator in areas with escaping gas or 

other explosive vapors that could be ignited by a spark 

from the actuator or attached accessories.

Location

Install the actuator in any location free from acid fumes or 

other deteriorating vapors that might attack the metal parts of 

the actuator. Make sure the location is not subject to escaping 

gas or other explosive vapors that could accidentally be 

ignited by a spark from the actuator or its attached parts.

Install the actuator in a location that allows enough clearance 

for mounting accessories and for servicing.

Mounting

The ML6284 Non-Spring Return Direct Coupled Damper 

Actuator is designed to operate a damper by driving the 

damper shaft either cw 

 or ccw

 depending on 

damper design. All actuators are shipped in the fully closed 

position.

The ML6284 Non-Spring Return Direct Coupled Damper 

Actuator is designed with removable hub inserts to 

accommodate specific damper shaft sizes. Proper sleeve 

selection is necessary when three-point mounting is used to 

avoid excessive strain on the output gear. Most ML6284 

Actuators are shipped with a 1/2 in. hub insert. For field use, 

two hub insert sizes are available. See the Accessories listing 

in the Specifications section. Shaft sizes are stamped on the 

inserts.

The ML6284 Non-Spring Return Direct Coupled Damper 

Actuator is designed for single-point mounting when using a 

mounting bracket. Single-point mounting is typically used 

when the actuator is mounted on the damper shaft.

The ML6284 Non-Spring Return Direct Coupled Damper 

Actuator can be mounted directly on the damper shaft with the 

actuator in any position.

A mounting bracket (see Fig. 1) is provided with some models 

to aid in installing the actuator. The bracket can be bent to any 

shape to allow the bracket tab to be centered in the actuator 

slot.

CAUTION

Equipment Damage Hazard.

Improper mounting can damage the equipment or 

interfere with proper operation.

The mounting bracket must not bind or clamp the 

actuator to the duct. The mounting bracket only 

prevents the actuator housing from rotating.

The ML6284 Direct Coupled Damper Actuator has a 

reversible output hub. The hub is factory mounted on the top 

of the actuator gear housing. When attaching to damper 

shafts less than 2.5 in. (64 mm) long, or for ease of mounting, 

the output hub may be mounted to the back of the actuator 

gear housing. See Fig. 3. Be careful when removing the 

retaining ring which secures the output hub sleeve to the 

actuator housing. Use a flat headed screwdriver to pry the 

retaining ring loose.

Содержание ML6284

Страница 1: ...it switch adjustments by limiting stall torque to 250 lb in 28 3 N m maximum 95 stroke provides necessary compression of rubber neoprene gaskets commonly used on 90 low leakage dampers Manual clutch allows for manual adjustment 92 second synchronous timing can eliminate need for feedback position indication in closed loop temperature control applications Removable splined output hub permits premou...

Страница 2: ...t Duty Feedback Resistor 500 ohm linear potentiometer Cable Ratings Control Standard models include nonplenum UL CSA rated 30V 60 C 20 gauge cable Auxiliary Switch UL CSA rated 300V 90 C 18 gauge Controller Type Floating spdt Torque Ratings at Rated Voltages Lift and Hold Minimum 150 lb in 17 N m Breakaway Minimum 150 lb in 17 N m Stall Minimum 150 lb in 17 N m Stall Maximum 250 lb in 28 3 N m Tor...

Страница 3: ...or and mounting bracket in in mm 9 32 7 3 PLACES 1 17 32 39 3 3 32 79 4 102 7 16 11 1 1 4 32 7 11 16 196 8 7 16 215 36 914 1 2 12 5 8 17 13 32 10 1 2 13 3 4 19 7 8 22 1 25 3 5 32 80 1 2 13 1 2 13 1 11 16 43 2 1 2 63 3 5 16 84 4 1 2 114 5 127 6 152 1 4 6 1 1 REMOVABLE RETAINING RING FOR REMOVAL OF HUB SLEEVE M7618B 1 4 6 1 8 3 2 51 15 16 24 1 29 32 48 ...

Страница 4: ...ing accessories and for servicing Mounting The ML6284 Non Spring Return Direct Coupled Damper Actuator is designed to operate a damper by driving the damper shaft either cw or ccw depending on damper design All actuators are shipped in the fully closed position The ML6284 Non Spring Return Direct Coupled Damper Actuator is designed with removable hub inserts to accommodate specific damper shaft si...

Страница 5: ...e bracket tab is midway in the actuator slot Mark the screw holes for installing the mounting bracket on the damper housing 4 Remove the mounting bracket and actuator 5 Drill or center punch the starting holes for the mounting bracket screws or use no 10 self tapping sheet metal screws not supplied 6 Place the actuator and mounting bracket back into position over the damper shaft and install the m...

Страница 6: ...act It stops when neither contact is made IMPORTANT The ML6284 can operate with DDC controller that emulates an spdt break before make switch Do not short cycle the actuator Short cycling of the actuator can cause premature failure The actuator has a position indicator to show shaft position As the indicator moves with the shaft it gives an angular representation of the damper position There are f...

Страница 7: ...NS AND OVERLOAD PROTECTION AS REQUIRED 500 OHM POTENTIOMETER ORANGE OPEN TAN GREEN CLOSED L1 HOT L2 1 1 2 2 3 3 MOTOR TIME OUT 24 VAC B BLUE W YELLOW T2 RED T1 BLACK ML6284 M4884A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TIME OUT FUNCTION AVAILABLE WITH ML6284D F MODELS 500 OHM POTENTIOMETER ORANGE OPEN TAN GREEN CLOSED 12 82 M7877A COMMON COMMON NO NO NC NC WHITE ...

Страница 8: ...s low check power supply and controller 3 If the actuator does not drive in the correct direction when a control signal is applied reverse the yellow and blue wires 4 Remove power and fully depress and hold disengage button down while turning damper shaft clockwise and counterclockwise If the damper shaft turns freely through the entire 90 stroke and the actuator is installed correctly replace the...