background image

11

63-2483—2

ML6185

CHECKOUT

Checkout

The ML6185 Direct Coupled Actuator can be checked

out either directly or by using a controller.

IMPORTANT: When power is interrupted, the actuator

returns to the normal starting position using the spring
mechanism. When power is restored, the controller
input will not operate the actuator until the spring is
fully wound and locked. The spring winding process
takes approximately 100 seconds, depending on the
number of degrees of spring return remaining at power
interrupt (i.e., 10

°

 of spring return remaining takes 10

seconds). (If the actuator is not in the closed position,
it will run to the closed position as the spring is
winding.) Once the spring is locked in its fully wound
position, the actuator  responds to inputs to the red-to-
blue or red-to-yellow leadwires.

DIRECT CHECKOUT

1. Mount the actuator for the required application (either

cw           or ccw           rotation to open the damper).

2. Check the damper position and make sure that 24 Vac is

present on the red and black leadwires.

3. Make sure the actuator spring is fully wound and

locked by applying power for at least 100 seconds.

4. Connect 24 Vac to the appropriate leadwires (red to

blue or red to yellow) to move the damper to the opposite
position. The ML6185 should drive the damper.

5. If the actuator does not run, verify that the actuator is

properly installed for either cw            or ccw             rotation.

6. If the actuator operates in the opposite direction than

desired, reverse the blue and yellow leadwires.

7. If the actuator is correctly installed and still does not

run, replace the actuator.

CONTROLLER CHECKOUT

1. Adjust the setpoint of the controller to call for cooling.

Observe the actuator.

2. If the damper is closed, it should begin to open.
3. If the damper remains closed, move the setpoint of the

controller farther below the room temperature.

4. If the damper still does not move, check for the

presence of 24 Vac in the input.

5. Make sure the actuator spring is fully wound by

applying power for at least 100 seconds.

6. If 24 Vac is present and the actuator does not operate,

reverse the controller leadwires to determine if the device
was miswired.

7. If the wiring is correct and 24 Vac is present on the input

terminals but the actuator does not run, replace the actuator.

Содержание ML6185

Страница 1: ...onindicationinclosed looptem perature control applications Removablesplinedoutputhubpermitspremounting ofthehubonthedampershaft providinginstallation flexibility Reversible mounting allows actuator to be used for either clockwise cw or counterclockwise ccw spring rotation Designedforbothsingle pointandthree pointmount ing providing installation flexibility Availablewithorwithoutatime outfeature Mo...

Страница 2: ...z 120 seconds at 50 Hz Spring Return Timing 10 seconds minimum per 90 at 72 F no load 30 seconds maximum per 90 at 72 F at rated load 5 minutes maximum at 30 F at rated load AMBIENT TEMPERATURE RANGE 30 F to 140 F 35 C to 60 C STORAGE TEMPERATURE 30 F to 150 F 35 C to 65 C HUMIDITY 5to95 percentrelativehumidity noncondensing MOUNTING Mounts directly on horizontal 3 8 in to 5 8 in 12 to 16 mm round...

Страница 3: ... in in mm M8257 135o 15o 1 3 32 28 1 13 32 36 5 16 8 13 32 10 10 13 32 264 3 4 19 1 5 8 41 1 13 32 36 4 13 32 112 3 8 10 CLEARANCE REQUIRED FOR SPLINED HUB MOUNTING 1 5 32 29 3 1 2 89 13 64 5 MOUNTING BRACKET 1 2 13 1 9 32 32 3 15 16 100 23 32 18 8 9 32 210 3 29 32 99 1 21 32 42 1 5 8 41 3 29 32 99 3 1 16 79 1 17 32 39 6 25 32 173 ...

Страница 4: ...n that allows enough clear ance for mounting accessories and for servicing MOUNTING The ML6185 Direct Coupled Actuator is designed to operate a damper by driving the damper shaft either cw or ccw depending on damper design All actuators are shipped in the fully closed position The ML6185 Direct Coupled Actuator is designed for single pointmountingwhenusinganadapterbracket Single pointmountingistyp...

Страница 5: ...ar Most ML6185 Actuators are shipped with a 1 2 in hub sleeve For field use several hub sleeve sizes are available See the Accessories listing in the Specifications section Shaft sizes are stamped on the sleeves The ML6185 Direct Coupled Actuator can be mounted directly on the motor shaft with the actuator in any position when the actuator housing is parallel with the damper housing or frame See F...

Страница 6: ... are shown in Fig 4 through 7 30 30 0 60 60 90 M7230A INDICATOR DETENTS 1 1 COUNTER CLOCKWISE SPRING ROTATION ARROW Fig 4 ML6185 Actuator mounted for counterclockwise spring rotation with the output hub inside the actuator NOTE NEMA rating applies only with damper shaft in the horizontal position ...

Страница 7: ...7 63 2483 2 ML6185 INSTALLATION Fig 5 Standard direct coupled mounting of ML6185 to a damper with counterclockwise spring rotation 500 5 0 0 30 30 60 60 90 M7229 ...

Страница 8: ...ith a water seal in the conduit opening When conduit is needed remove the seal before routing the cable ML6185 models with Factory mounted Auxiliary Switches See Fig 9 ML6185C F models have two nonadjustable line volt age rated spdt auxiliary switches with switches factory set to make common to normally open at 12 and 82 rotation from the counterclockwise stop See Fig 9 IMPORTANT Actuators driving...

Страница 9: ... to provide 7500 springreturns therefore theactuatorcanbeunpowered daily for night shutdown control However rapidly cycling the actuator by removing control voltage will lead to premature spring failure Operation L1 HOT L2 1 1 BLUE YELLOW RED BLACK ML6185 BLUE YELLOW RED BLACK ML6185 M7225A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONTROLLER CONTROLLER R B W R B W ...

Страница 10: ...NDICATOR START POSITIONS FULLY CLOCKWISE SPRING RETURN INDICATOR START POSITIONS DRIVE CLOCKWISE TO CLOSE REVERSE ACTING DRIVE COUNTERCLOCKWISE TO CLOSE REVERSE ACTING DRIVE COUNTERCLOCKWISE TO OPEN DIRECT ACTING DRIVE CLOCKWISE TO OPEN DIRECT ACTING M7235 DETENT IN INSERT DETENT IN INSERT DETENT IN INSERT DETENT IN INSERT POINTER AT 90 POINTER AT 90 POINTER AT 0 POINTER AT 0 M7235B ...

Страница 11: ...tuator spring is fully wound and locked by applying power for at least 100 seconds 4 Connect 24 Vac to the appropriate leadwires red to blue or red to yellow to move the damper to the opposite position The ML6185 should drive the damper 5 If the actuator does not run verify that the actuator is properly installed for either cw or ccw rotation 6 If the actuator operates in the opposite direction th...

Страница 12: ...rol Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...