Honeywell MAXON 4760 Series Скачать руководство пользователя страница 9

E - i - 05/22

9

32M-95002-03

ACTUATOR ASSEMBLY ROTATION

WARNING

MAXON electro-mechanical valves should be 

ordered in a configuration compatible with 

planned piping. If valve orientation is not correct, 

the actuator assembly can be rotated in 90° 

increments around the valve body centerline axis 

using the procedure below.

1.

Shut off all electrical power and close off upstream 

manual cock.

2.

Remove terminal block cover plate and disconnect 

power lead wires. (Tag carefully for later re-assembly.)

3.

Remove conduit and electrical leads.

4.

Note physical position of any signal switch actuator 

wands on auxiliary signal switches.

5.

Unscrew the two actuator bolts screwed up from the 

bottom to 1/4 inch. DO NOT completely remove. 

These bolts secure the valve body to the valve’s top 

assembly housing.

6.

Gently lift the top assembly (not more than 1/4” in 

height); just enough to break the seal between the 

valve body assembly and the rubber gasket adhering 

to the bottom of the top housing.

WARNING

 Lifting too far may dislodge some small parts 

inside the top housing, requiring complex re-

assembly and retesting by trained factory 

personnel.

7.

Remove the two actuator bolts screwed up from the 

bottom (were partially unscrewed in step 5).

8.

Carefully rotate top assembly to the desired position in 

a plane parallel to the top of the valve body casting. 

Rotate the top housing about 30° beyond this posi

-

tion, and then rotate it back. Reposition the top hous

-

ing back down onto the valve body casting. This 

should align the open/shut indicator with its window 

and provide proper alignment of the internal mecha

-

nism.

9.

Realign holes in valve body casting with the corre

-

sponding tapped holes in the bottom of the top 

assembly housing. Be sure the gasket is still in place 

between the body and top housing.

10.

Reinsert the actuator bolts up from the bottom 

through the body and carefully engage threads of the 

top assembly. Tighten securely.

11.

Reconnect conduit and electrical leads, then check 

that signal switch wands are properly positioned and 

that the open/shut indicator moves freely. Failure to 

correct any such misalignment can result in extensive 

damage to the internal mechanism of your valve.

12.

Energize valve and cycle several times from closed to 

full open position. Also electrically trip the valve in a 

partially opened position to prove valve operates prop

-

erly.

13.

Replace and secure terminal block cover plate and 

place valve in service.

FIELD INSTALLATION OF VALVE 

POSITION SWITCH

General

• Shut off fuel supply upstream of valve, then de-ener

-

gize valve electrically.

• Remove terminal block and access cover to provide 

access, being careful not to damage gaskets.

• Compare with illustrations below to identify your 

valve type.

Replacement switches

• Note wand position and mounting hole location 

carefully, then remove 2 screws and lift existing 

switch. 

• Install replacement switch in same mounting holes 

on bracket and verify correct wand position.

• Replace existing wiring one connection at a time, fol

-

lowing original route and placement.

Add switches

• Check illustrations below. If your valve uses a switch 

mounting bracket as in Fig. 1 & 2, mount switches to 

bracket using the mounting holes appropriate for 

valve type and size. For high capacity valves, mount 

switches on the support stand.

• Position bracket so VCS wand just touches top of 

actuator, then move downward slightly, depressing 

wand until switch clicks, then tighten mounting 

screws to hold this position.

• Pin bracket by drilling 1/8” diameter holes 1/4” deep 

into bracket mounting pad through drive pin holes, 

then tap drive pin in until flush (not required for high 

capacity valves).

• Route wires to wiring compartment as shown, then 

complete wiring connections and clean out metal 

drilling chips from previous procedure.

• Cycle valve, checking switch actuation points care

-

fully. (VCS actuates at top of stem stroke, VOS at bot

-

tom.) Simultaneously the valve body must be tested 

for switch continuity and seat leakage. Bend VOS 

switch wands slightly if necessary to insure valve is 

opening fully.

• Replace covers, then return valve to service.

Содержание MAXON 4760 Series

Страница 1: ...ORTER BELGIUM Maxon International BVBA Luchthavenlaan 16 18 1800 Vilvoorde Belgium Tel 32 2 255 09 09 Fax 32 2 251 82 41 Please read the operating and mounting instructions before using the equipment Install the equipment in compliance with the prevailing regulations Bedrijfs en montagehandleiding voor gebruik goed lezen Apparaat moet volgens de geldende voorschriften worden geïnstalleerd Lire les...

Страница 2: ...ult the nameplate of your valve This lists the maximum operating pressure temperature limitations voltage requirements and service conditions of your specific valve Do not exceed nameplate ratings Abbreviation or symbol Description M O P Maximum operating pressure OPENING Valve opening time for automatic valves only Units shown in seconds Solenoid clutch voltage and frequency Motor voltage and fre...

Страница 3: ...y top assembly or motor drive unit Any alterations void all warranties To determine suggested spare parts identify series designation and serial number from the valve s nameplate Refer to the illustration and legend below to identify suggested spare parts To order specify 1 Quantity 2 Assembly part number if available 3 Description 4 Electrical specification 5 Full nameplate information from exist...

Страница 4: ...ch locations are noted on sketch Fig 1 Table 11 Torque Specifications Valve Type Item Number Description Torque 8700 1 Adaptor Base Mounting Screws 3 8 16 x 2 UNC 239 in lbs 2 Cover Mounting Screws 1 4 20 x 625 UNC 71 in lbs 3 Nameplate Mounting Screws 8 32 x 25 10 in lbs 4 Actuator Adaptor Screws 3 8 16 x 1 5 239 in lbs 4700 33479 5 Adaptor Base Mounting Screws 3 8 16 x 2 UNC 239 in lbs 6 Namepla...

Страница 5: ...verted snap switch mounted on rear of switch bracket VCS 1 is an SPDT single pole double throw switch VCS 2 is a DPDT double pole double throw switch All contacts are available for external circuitry VOS Valve Open Switch is actuated when valve reaches full open It is the lower snap switch mounted on front of switch bracket VOS 1 is an SPDT switch On automatic reset valves its normally closed cont...

Страница 6: ...40 VAC must be segregated from lower voltage 24 VDC signal wiring when both are required To eliminate any potential for gas to enter the electrical wiring system install a conduit seal fitting at the actuator conduit hub 5 Maintain integrity of the electro mechanical actuator enclosures by using the appropriate electrical connec tors for the 2 3 4 NPT conduit threaded connec tions 6 All access cov...

Страница 7: ...60 C T3C Ta 60 C UL UL 429 Not Applicable Not Applicable CSA CSA 6 5 CSA 22 2 No 139 CSA 22 2 No 0 CSA 22 2 No 0 4 CSA 22 2 No 25 CSA 22 2 No 94 CSA 22 2 No 142 CSA 22 2 No 213 Class I Div 2 Groups ABCD Class II Div 2 Groups FG Class III T4 AC 60 C T3C DC 60 C IEC Approvals Not Applicable Not Applicable IEC 60079 0 IEC 60079 15 IEC 60079 31 Ex nA nC IIC T4A AC T3 DC Gc Ex tc IIIC T135 C Dc IP65 29...

Страница 8: ...2P 2D with PEEK backed Disc for lower actuation friction Solenoid Voltage 0 None A 115V 50HZ B 115V 60HZ C 230V 50HZ D 230V 60HZ E 208V 50HZ F 24VDC G 120VDC Clutch Voltage 0 None B 115V 60Hz Motor Voltage A 115V 50Hz B 115V 60Hz G 230V 50Hz H 230V 60Hz Motor Timing 6 6 Sec 7 Sec on 50Hz VOS Switch 1 VOS 1Switch 2 VOS 2 Switch VCS Switch 0 NoSwitchOrdered 1 VCS 1 Switch 2 VCS 2 Switch Enclosure Ra...

Страница 9: ...it and electrical leads then check that signal switch wands are properly positioned and that the open shut indicator moves freely Failure to correct any such misalignment can result in extensive damage to the internal mechanism of your valve 12 Energize valve and cycle several times from closed to full open position Also electrically trip the valve in a partially opened position to prove valve ope...

Страница 10: ...Testing of MAXON Shut off Valves 10 35 2 at www docuthek com Any valve that exceeds the allowable leakage as set forth by your local codes or insurance requirements should be removed from service and your MAXON representative should be contacted Actuator assemblycomponents require no field lubrication and should never be oiled Auxiliary switches solenoids motors clutches or circuit boards may be r...

Страница 11: ...E i 05 22 11 32M 95002 03 ...

Страница 12: ...alSolutions honeywell com or contact your Honeywell Sales Engineer Honeywell MAXON branded products 201 E 18th Street Muncie IN 47302 USA www maxoncorp com Honeywell Process Solutions Honeywell Thermal Solutions HTS 2101 CityWest Blvd Houston TX 77042 ThermalSolutions honeywell U S Registered Trademark 2022 Honeywell International Inc 32M 95002 03 e05 22 EAS 50116777 001 rev B Printed in United St...

Отзывы: