Honeywell MAXON 4760 Series Скачать руководство пользователя страница 5

E - i - 05/22

5

32M-95002-03

AUXILIARY SIGNAL SWITCHES 4700(NI) & 33479 SERIES

All Maxon valves may be equipped with internally-

mounted signal switch(es) to provide a “proof-of-open” or 

“proof-of-closure” valve position indication.

Auxiliary signal switches indicate when valve is open or 

closed and are normally connected electrically into your 

control panel lights or warning device circuit(s).

VCS (Valve Closed Switch) is actuated when valve is fully 

shut. It is the upper, inverted snap-switch mounted on rear 

of switch bracket. VCS-1 is an SPDT (single-pole, double-

throw) switch. VCS-2 is a DPDT (double-pole, double-

throw) switch. All contacts are available for external 

circuitry.

VOS (Valve Open Switch) is actuated when valve reaches 

full-open. It is the lower snap-switch mounted on front of 

switch bracket. VOS-1 is an SPDT switch. On automatic 

reset valves, its normally closed contact serves as a motor 

limit switch and is not available for external circuitry VOS-

2 is DPDT, used in lieu of VOS-1 for additional contacts.

Valve Open

Valve Shut

VOS

(VOS-2 shown)

VOS wands

VOS actuator

VCS actuator

VCS actuator

VOS actuator

VCS wand

VCS

(VCS-2 shown)

Содержание MAXON 4760 Series

Страница 1: ...ORTER BELGIUM Maxon International BVBA Luchthavenlaan 16 18 1800 Vilvoorde Belgium Tel 32 2 255 09 09 Fax 32 2 251 82 41 Please read the operating and mounting instructions before using the equipment Install the equipment in compliance with the prevailing regulations Bedrijfs en montagehandleiding voor gebruik goed lezen Apparaat moet volgens de geldende voorschriften worden geïnstalleerd Lire les...

Страница 2: ...ult the nameplate of your valve This lists the maximum operating pressure temperature limitations voltage requirements and service conditions of your specific valve Do not exceed nameplate ratings Abbreviation or symbol Description M O P Maximum operating pressure OPENING Valve opening time for automatic valves only Units shown in seconds Solenoid clutch voltage and frequency Motor voltage and fre...

Страница 3: ...y top assembly or motor drive unit Any alterations void all warranties To determine suggested spare parts identify series designation and serial number from the valve s nameplate Refer to the illustration and legend below to identify suggested spare parts To order specify 1 Quantity 2 Assembly part number if available 3 Description 4 Electrical specification 5 Full nameplate information from exist...

Страница 4: ...ch locations are noted on sketch Fig 1 Table 11 Torque Specifications Valve Type Item Number Description Torque 8700 1 Adaptor Base Mounting Screws 3 8 16 x 2 UNC 239 in lbs 2 Cover Mounting Screws 1 4 20 x 625 UNC 71 in lbs 3 Nameplate Mounting Screws 8 32 x 25 10 in lbs 4 Actuator Adaptor Screws 3 8 16 x 1 5 239 in lbs 4700 33479 5 Adaptor Base Mounting Screws 3 8 16 x 2 UNC 239 in lbs 6 Namepla...

Страница 5: ...verted snap switch mounted on rear of switch bracket VCS 1 is an SPDT single pole double throw switch VCS 2 is a DPDT double pole double throw switch All contacts are available for external circuitry VOS Valve Open Switch is actuated when valve reaches full open It is the lower snap switch mounted on front of switch bracket VOS 1 is an SPDT switch On automatic reset valves its normally closed cont...

Страница 6: ...40 VAC must be segregated from lower voltage 24 VDC signal wiring when both are required To eliminate any potential for gas to enter the electrical wiring system install a conduit seal fitting at the actuator conduit hub 5 Maintain integrity of the electro mechanical actuator enclosures by using the appropriate electrical connec tors for the 2 3 4 NPT conduit threaded connec tions 6 All access cov...

Страница 7: ...60 C T3C Ta 60 C UL UL 429 Not Applicable Not Applicable CSA CSA 6 5 CSA 22 2 No 139 CSA 22 2 No 0 CSA 22 2 No 0 4 CSA 22 2 No 25 CSA 22 2 No 94 CSA 22 2 No 142 CSA 22 2 No 213 Class I Div 2 Groups ABCD Class II Div 2 Groups FG Class III T4 AC 60 C T3C DC 60 C IEC Approvals Not Applicable Not Applicable IEC 60079 0 IEC 60079 15 IEC 60079 31 Ex nA nC IIC T4A AC T3 DC Gc Ex tc IIIC T135 C Dc IP65 29...

Страница 8: ...2P 2D with PEEK backed Disc for lower actuation friction Solenoid Voltage 0 None A 115V 50HZ B 115V 60HZ C 230V 50HZ D 230V 60HZ E 208V 50HZ F 24VDC G 120VDC Clutch Voltage 0 None B 115V 60Hz Motor Voltage A 115V 50Hz B 115V 60Hz G 230V 50Hz H 230V 60Hz Motor Timing 6 6 Sec 7 Sec on 50Hz VOS Switch 1 VOS 1Switch 2 VOS 2 Switch VCS Switch 0 NoSwitchOrdered 1 VCS 1 Switch 2 VCS 2 Switch Enclosure Ra...

Страница 9: ...it and electrical leads then check that signal switch wands are properly positioned and that the open shut indicator moves freely Failure to correct any such misalignment can result in extensive damage to the internal mechanism of your valve 12 Energize valve and cycle several times from closed to full open position Also electrically trip the valve in a partially opened position to prove valve ope...

Страница 10: ...Testing of MAXON Shut off Valves 10 35 2 at www docuthek com Any valve that exceeds the allowable leakage as set forth by your local codes or insurance requirements should be removed from service and your MAXON representative should be contacted Actuator assemblycomponents require no field lubrication and should never be oiled Auxiliary switches solenoids motors clutches or circuit boards may be r...

Страница 11: ...E i 05 22 11 32M 95002 03 ...

Страница 12: ...alSolutions honeywell com or contact your Honeywell Sales Engineer Honeywell MAXON branded products 201 E 18th Street Muncie IN 47302 USA www maxoncorp com Honeywell Process Solutions Honeywell Thermal Solutions HTS 2101 CityWest Blvd Houston TX 77042 ThermalSolutions honeywell U S Registered Trademark 2022 Honeywell International Inc 32M 95002 03 e05 22 EAS 50116777 001 rev B Printed in United St...

Отзывы: