background image

M7215 DAMPER MOTOR

3

63-2556

Table 1. M7215 Accessories.

Fig. 2. Limits of crank arm rotation.

INSTALLATION

When Installing this Product...

1.

Read instructions carefully. Failure to follow them could 

damage the product or cause a hazardous condition.

2.

Check ratings and description given in the specifications 

to make sure the product is suitable for your application.

3.

Installer must be a trained, experienced service technician.

4.

After installation is complete, check out product 

 

operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage Hazard.

 

Can shock individuals or short equipment 

 

circuitry.

Disconnect power supply before installation.

CAUTION

Personal Injury Hazard.

 

Spring-return assembly can release.

Leave end covers attached to the motor.

Location and Mounting

Locate motor as close as possible to the equipment to be 

 

controlled. Refer to Fig. 1 for mounting dimensions.

1.

Mount motor with the shaft horizontal to ensure 

 

maximum life.

NOTE: Operation in other positions is possible when 

required by the application.

2.

Remove crank arm (secured with two screws) from the 

motor hub.

IMPORTANT

Position crank arm on hub so it does not strike motor 

mounting surface during any portion of full stroke. 

See Fig. 2.

4074EHB Screw Terminal Adapter—converts quick-connect 

terminals to screw terminals. Adapter can be used with or without 

7640QF Terminal Enclosure.

7640QF Terminal Enclosure—provides wiring enclosure for 

electrical terminal connections. Enclosure can be used with or 

without 40784EHB Screw Terminal Adapter. Bag assembly 

includes: terminal housing, cover plate and mounting screws.

4074EGR Crank Arm Assembly.

Q298B Linkage Hardware—enables linking the motor to an 

additional damper. Consists of two crank arm assemblies, two ball 

joint assemblies, and variable length push rods (in 10, 16, or 24 

inch lengths)

4074EKV Auxiliary Switch—provides switching capability for 

controlling auxiliary equipment. The switch acts as a function of the 

motor shaft position.

M17363

M3855

M3856

M17364

M3852

1

1 CRANK ARM FIELD ADJUSTABLE IN 7.5 DEGREE INCREMENTS.

MOTOR MOUNTING SURFACE

M3850

MAXIMUM

OPEN

POSITION

MAXIMUM

CLOSED

POSITION

Содержание M7215

Страница 1: ...on air dampers used in residential or commercial HVAC equipment FEATURES M7215 Damper Motors provide modulating control of economizer dampers from a 2 10 Vdc controller Quiet high efficiency drive motor High impact glass fiber reinforced plastic case is rugged lightweight and corrosion resistant Provides 2 10 Vdc output signal proportional to the shaft position Contents Application 1 Features 1 Sp...

Страница 2: ... Power Consumption 24 Vac 60 Hz 8 7 VA 24 Vac 50 Hz 8 4 VA Torque Lift and Hold 25 lb in 2 8 N m Spring Return 25 lb in 2 8 N m Breakaway 40 lb in 4 5 N m IMPORTANT Never use motor continuously at the breakaway torque rating NOTE Breakaway torque available to overcome occasional large loads such as a seized damper Stroke Travel 90 Timing Driving 86 5 seconds Spring Return 13 5 seconds Motor Rotati...

Страница 3: ...peration in other positions is possible when required by the application 2 Remove crank arm secured with two screws from the motor hub IMPORTANT Position crank arm on hub so it does not strike motor mounting surface during any portion of full stroke See Fig 2 4074EHB Screw Terminal Adapter converts quick connect terminals to screw terminals Adapter can be used with or without 7640QF Terminal Enclo...

Страница 4: ...If questions arise regarding this product contact your distributor or local Honeywell representative Fig 4 Three M7215 Damper Motors connected in parallel Direct Checkout 1 Mount the motor for the required application 2 Check the damper position and make sure 24 Vac is present across TR and TR1 3 Apply 10 Vdc to IN and IN to move damper to the opposite position The motor should drive the damper 4 ...

Отзывы: