LP916A-C PNEUMATIC REMOTE BULB THERMOSTATS

3

95-5559

B

Mount Thermostat (Fig. 5 or 6).

Fig. 5. Terminal unit top view with thermostat mounted in

preferred position.

C

Carefully uncoil and extend capillary tubing. Make a
5/8-in. (16 mm) hole in unit wall between end
compartment and filter and coil compartment, or use
existing knockout. Insert sensing bulb, with capillary,
through hole. Locate bulb in appropriate position
between return air filter and coil. Bush hole in unit wall
to protect capillary tubing.
NOTE:

The sensing bulb must not be situated where
is will be affected by any outdoor airflow
across it (e. g., a unit which uses a fixed-
percentage outdoor air damper).

D

Mount two bulb hangers (Fig. 6). Clip to drain pan
or edge of frame member. Tap top end to ensure
firm mounting.

Fig. 6. Alternate mounting of thermostat at bottom front

of end compartment.

E

Snap sensing bulb into position.

F

Before connecting air, leave main line disconnected for
about one minute to clear and dry tubing. Air
connections are 1/4-in. push-on sharp-barb type and
are labeled M and B for Main and Branch.
NOTE:

If air connections are towards back, connect
appropriate lengths of tubing to barb
connectors before mounting.

Duct Mounting

Duct mounting requires a 107324A Duct Bulb Holder (Fig. 7).
The sensing bulb should be located in the duct where air of
representative temperature can freely circulate around it.
Avoid mounting the bulb close to hot pipes, cooling coils, and
other places where air temperature is not representative.

Fig. 7. 107324A duct bulb holder.

A

Cut a 3/4-in. (19 mm) diameter hole in duct wall to admit
sensing bulb and bulb holder.

B

Mount the Thermostat near the hole in the duct.
NOTE:

Mount either on top of duct or on a bracket or
angle iron; obtain locally.

C

Using bulb holder as a template, mark and drill holes for
bulb holder and mounting screws.

D

Break off bulb holder to desired length as shown in
Figure 8.
NOTE:

Bulb holder should be long enough to hold
sensing bulb in freely circulating air away from
duct wall. Neatly coil any excess capillary
tubing at Thermostat case or at bulb holder.

Fig. 8. Shortening bulb holder.

S3879

S3880-2

S24102

C7866

Содержание LP916A-C

Страница 1: ...an two revolutions clockwise from the original position as received Rotating the shaft more than two revolutions from the original position can cause permanent damage to the Thermostat This warning is also on a removeable tag Fig 1 attached to the Thermostat and should remain attached until the system is ready to start up Fig 1 LP916 caution label O O L E R W A R M E M B H O N E Y W E L L CAUTION ...

Страница 2: ... 14 4 5 8 117 2 3 4 70 3 77 Fig 3 Typical terminal unit mounting locations B Mount Thermostat in location where mounting screws are readily accessible setpoint knob easily reached and scale visible preferably from top of unit through access hatch or from front of unit when front panel is removed C Locate air connections in accessible area If necessary add 1 4 in plastic elbow and or tubing extensi...

Страница 3: ...dry tubing Air connections are 1 4 in push on sharp barb type and are labeled M and B for Main and Branch NOTE If air connections are towards back connect appropriate lengths of tubing to barb connectors before mounting Duct Mounting Duct mounting requires a 107324A Duct Bulb Holder Fig 7 The sensing bulb should be located in the duct where air of representative temperature can freely circulate ar...

Страница 4: ... wall Mounting Kit Model The LP916 mounting kit model is shown in Figure 12 This model can be either panel mounted or mounted in a terminal unit using a bracket Fig 12 LP916 mounting kit model dimensions in inches millimeters Panel Mounting Mounting LP916 Mounting Kit Model directly on a panel requires a 306016C Bag Assembly which includes a scale plate knob and mounting screws A Drill holes in pa...

Страница 5: ...red Bracket Mounting The LP916 Mounting Kit Model is installed in terminal units similar to Figure 5 or 6 using a 306016A or B Bag Assembly These assemblies include a mounting bracket screws nuts clips bulb hangers scale plate and knob The two bag assemblies are similar except for the length of the mounting bracket and the centers of the bracket mounting holes Fig 15 and 16 The two sets of holes i...

Страница 6: ...alibration C Hold Thermostat in place in the terminal unit and mark screw hole centers Fig 17 Punch or drill pilot holes in the mounting surface for sheet metal screws Alternately Tinnerman nuts can be used by making clearance holes for the screws D Mount Thermostat in unit E Mount sensing bulb in unit using hangers see Fig 6 Fig 17 Assembling thermostat mounting bracket and scale plate bracket fr...

Страница 7: ...B Measure temperature at bulb location C Remove setpoint knob D Rotate control shaft to achieve 8 psi 55 kPa branchline pressure Do not rotate shaft more than two revolutions clockwise from original position as received and allow enough time up to three minutes for branch pressure to build up WARNING Rotating shaft more than two revolutions clockwise from original position can cause permanent dama...

Страница 8: ...aft clockwise Allow enough time up to three minutes for branch pressure to build up C Lower main line pressure to 16 5 psi 113 kPa Tighten switchover spring adjusting nut until branchline pressure begins to increase Allow enough time up to three minutes for branch pressure to build up and observe WARNING in LP916A and C calibration D Except LP916B1058 lower main line pressure to 13 psi 90 kPa Adju...

Отзывы: