VAN · Edition 05.22
EN-5
d
10
Position new actuator.
11
Follow the reverse procedure when reassembling.
12
Fit the M20 cable gland or plug and socket.
13
Connect the VAN to the electrical power supply,
7 MAIntenAnCe
CAUtIon
In order to ensure smooth operation, check the
tightness and function of the unit:
– Once per year, twice per year in the case of
biogas; check for internal and external
tightness, see page 4 (5 Tightness test).
– Check electrical installations once a year in line
with local regulations; pay particular attention to
the PE wire, see page 2 (4 Wiring).
➔
If the flow rate has dropped, clean the strainer.
➔
We recommend replacing the seals, see accesso-
ries, page 6 (8.2 Seal set VA 1–2).
1
Disconnect the system from the electrical power
supply.
2
Shut off the gas supply.
3
Undo connection parts.
4
5
6
7
8
9
Once the seals have been replaced, follow the
reverse procedure to reassemble the unit. Note
the recommended tightening torques for the con-
nection parts.
Connection parts
tightening
torque
[ncm]
VAx 1: M5
500 ± 50
VAx 2: M6
800 ± 50
VAx 3: M8
1400 ± 100
10
Then check the unit for internal and external tight-
ness, see page 4 (5 Tightness test).
8 ACCessoRIes
8.1 Pressure switch for gas DG..VC
The pressure switch for gas monitors the inlet pres-
sure p
u
and the outlet pressure p
d
.
➔
Monitoring the inlet pressure p
u
: the pressure
switch for gas is mounted on the inlet side.
Monitoring the outlet pressure p
d
: the pressure
switch for gas is mounted on the outlet side.
p
u
p
d
Scope of delivery:
1 x pressure switch for gas,
2 x self-tapping retaining screws,
2 x sealing rings.
Also available with gold-plated contacts for voltages
of 5 to 250 V.
➔
When retrofitting the pressure switch for gas, see
enclosed operating instructions “Pressure switch-
es for gas DG..C”, section entitled “Mounting the
DG..C.. on valVario gas solenoid valves”.
➔
The switching point is adjustable via hand wheel.
1
2
3
type
Adjusting range
(adjusting
tolerance =
± 15% of the
scale value)
Mean switching
differential at
min. and max.
setting
[mbar]
["WC]
[mbar]
["WC]
DG 17VC
2–17
0.8–6.8 0.7–1.7 0.3–0.8
DG 40VC
5–40
2–16
1–2
0.4–1
DG 110VC 30–110
12–44
3–8
0.8–3.2
DG 300VC
100–
300
40–120
6–15
2.4–8
➔
Deviation from the switching point during testing
pursuant to EN 1854 Gas pressure switches:
± 15%.