VAN · Edition 05.22

EN-2

2 CHeCKInG tHe UsAGe

Magnetic relief valve, open when de-energized, for the 
monitoring of gas valves for tightness used in conjunc-
tion with a visual discharge unit. For purging excess 
or leakage gas.

This function is only guaranteed when used within the 

specified limits – see page 6 (9 Technical data). Any 
other use is considered as non-compliant. 

2.1 type code

VAn

 

 Magnetic relief valve 

1–2

 

 Sizes 

10–50

 

 Inlet and outlet flange nominal size 

R

 

 Rp internal thread 

/n

 

 Quick opening, quick closing 

W

 

 Mains voltage 230 V AC, 50/60 Hz 

Q

 

 Mains voltage 120 V AC, 50/60 Hz 

K

 

 Mains voltage 24 V DC 

P

 

 Mains voltage 100 V AC, 50/60 Hz 

Y

 

 Mains voltage 200 V AC, 50/60 Hz 

s

 

 Closed position switch with visual posi-

tion indicator 

G

 

 Closed position switch for 24 V with 

visual position indicator 

L

 

 Viewing side: left 

R

 

 Viewing side: right 

 

 

   

2.2 Part designations

VAN..S,

VAN..G

VAN

5

3

1

6
7

4

2

Solenoid actuator

Flow body

Connection box

Connection flange

Closed position indicator

Connection parts

Sealing plug

2.3 type label

Mains voltage, electrical power consumption, ambient 
temperature, enclosure, inlet pressure and installation 
position: see type label.

Elster GmbH

Osnabrück, Germany

 .XXXX

VAN

3 InstALLAtIon

 CAUtIon

Incorrect installation
Please observe the following to ensure that the 
magnetic relief valve is not damaged during instal-
lation and operation:

 

– Sealing material and dirt, e.g. thread cuttings, 

must not be allowed to get into the valve 
housing.

 

– A filter must be installed upstream of every 

system.

 

– Dropping the device can cause permanent 

damage. In this event, replace the entire device 
and associated modules before use.

 

– Do not clamp the unit in a vice. Only secure the 

flange by holding the octagon with a suitable 
spanner. Risk of external leakage.

 

– Solenoid valves with closed position indicator 

VAN..S or VAN..G: actuator cannot be rotated.

 

Install the unit in the pipe free of mechanical stress.

 

Installation position: black solenoid actu-
ator in the vertical upright position or tilt-
ed up to the horizontal, not upside down. 

 

 

The housing must not be in contact with masonry, 

minimum clearance 20 mm (0.79").

 1 

Obey the direction of flow as marked on the hous-

ing.

 2 

 

 3 

 

 4 

4 WIRInG

 WARnInG

Risk of injury!
Please observe the following to ensure that no 
damage occurs:

 

– Electric shocks can be fatal! Before working on 

possible live components, ensure the unit is 
disconnected from the power supply.

 

– The solenoid actuator heats up during 

operation. Surface temperature approx. 85°C 
(approx. 185°F).

 

Use temperature-resistant cable (> 80°C).

Содержание Krom Schroeder VAN Series

Страница 1: ...in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c Action Instruction 1 3 Liability We will not be held liable for damage resulting from non observance of the instructions and non com pliant use 1 4 Safety instructions Information that is relevant for safety is indicated in the instructions as fo...

Страница 2: ...Elster GmbH Osnabrück Germany XXXX VAN 3 INSTALLATION CAUTION Incorrect installation Please observe the following to ensure that the magnetic relief valve is not damaged during instal lation and operation Sealing material and dirt e g thread cuttings must not be allowed to get into the valve housing A filter must be installed upstream of every system Dropping the device can cause permanent damage ...

Страница 3: ...ed white VAN open CAUTION Please observe the following to ensure smooth operation Route valve and closed position indicator cables separately through M20 cable glands or use two separate plugs Otherwise there is a risk of interference between valve voltage and closed position indicator voltage To make wiring easier the connection terminal for the closed position indicator can be removed 1 3 2 LV1 ...

Страница 4: ... coating No additional grease is required 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply Remove the M20 cable gland or other type of connection 3 4 5 6 7 8 9 Dependingontheconstructionstageoftheunit there are two different methods for replacing the actuator If the unit concerned has no O ring in this place arrow replace the actuator as described here Otherwise g...

Страница 5: ...M5 500 50 VAx 2 M6 800 50 VAx 3 M8 1400 100 10 Then check the unit for internal and external tight ness see page 4 5 Tightness test 8 ACCESSORIES 8 1 Pressure switch for gas DG VC The pressure switch for gas monitors the inlet pres sure pu and the outlet pressure pd Monitoring the inlet pressure pu the pressure switch for gas is mounted on the inlet side Monitoring the outlet pressure pd the press...

Страница 6: ...g with a high pressure cleaner and or cleaning products 9 2 Mechanical data Gas types natural gas LPG gaseous biogas max 0 1 by vol H2S or clean air other types of gas on request The gas must be clean and dry in all temperature conditions and must not contain condensate Medium temperature ambient temperature Max inlet pressure pu 500 mbar 7 25 psig Leakage rate 500 cm3 h 0 132 gal h Closing time q...

Страница 7: ... For ther moprocessing equipment observe local regulations 11 CERTIFICATION 11 1 Declaration of conformity We the manufacturer hereby declare that the products VAN with product ID No CE 0063BU1564 comply with the requirements of the listed Directives and Standards Directives 2014 35 EU LVD 2014 30 EU EMC 2011 65 EU RoHS II 2015 863 EU RoHS III Regulation EU 2016 426 GAR Standards EN 161 2011 A3 20...

Страница 8: ...ve At the end of the product life number of op erating cycles reached dispose of the pack aging and product in a corresponding recycling centre Do not dispose of the unit with the usu al domestic refuse Do not burn the product On request old units may be returned carriage paid to the manufacturer in accordance with the relevant waste legislation requirements 2022 Elster GmbH We reserve the right t...

Отзывы: