background image

2

HPF24S Series Power Supplies —

  P/N 52751:D3  5/11/2010

Fire Alarm System Limitations

While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

An automatic fire alarm system

—typically made up of 

smoke detectors, heat detectors, manual pull stations, audible 
warning devices, and a fire alarm control panel with remote 
notification capability—can provide early warning of a develop-
ing fire.  Such a system, however, does not assure protection 
against property damage or loss of life resulting from a fire.  

The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the 
recommendations of the National Fire Protection Association 
Standard 72-2002 (NFPA 72-2002), manufacturer's recom-
mendations, State and local codes, and the recommendations 
contained in the Guides for Proper Use of System Smoke 
Detectors, which are made available at no charge to all install-
ing dealers.  These documents can be found at http://
www.systemsensor.com/html/applicat.html.  A study by the 
Federal Emergency Management Agency (an agency of the 
United States government) indicated that smoke detectors 
may not go off in as many as 35% of all fires.  While fire alarm 
systems are designed to provide early warning against fire, 
they do not guarantee warning or protection against fire.  A fire 
alarm system may not provide timely or adequate warning, or 
simply may not function, for a variety of reasons: 

Smoke detectors

 may not sense fire where smoke cannot 

reach the detectors such as in chimneys, in or behind walls, on 
roofs, or on the other side of closed doors.  Smoke detectors 
also may not sense a fire on another level or floor of a building.  
A second-floor detector, for example, may not sense a first-
floor or basement fire.  

Particles of combustion or “smoke”

 from a developing fire 

may not reach the sensing chambers of smoke detectors 
because:

• Barriers such as closed or partially closed doors, walls, or 

chimneys may inhibit particle or smoke flow.  

• Smoke particles may become “cold,” stratify, and not reach 

the ceiling or upper walls where detectors are located.  

• Smoke particles may be blown away from detectors by air 

outlets.  

• Smoke particles may be drawn into air returns before 

reaching the detector.  

The amount of “smoke” present may be insufficient to alarm 
smoke detectors.  Smoke detectors are designed to alarm at 
various levels of smoke density.  If such density levels are not 
created by a developing fire at the location of detectors, the 
detectors will not go into alarm.  

Smoke detectors, even when working properly, have sensing 
limitations.  Detectors that have photoelectronic sensing 
chambers tend to detect smoldering fires better than flaming 
fires, which have little visible smoke.  Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires 
better than smoldering fires.  Because fires develop in different 
ways and are often unpredictable in their growth, neither type 
of detector is necessarily best and a given type of detector 
may not provide adequate warning of a fire.  

Smoke detectors cannot be expected to provide adequate 
warning of fires caused by arson, children playing with 
matches (especially in bedrooms), smoking in bed, and violent 
explosions (caused by escaping gas, improper storage of 
flammable materials, etc.).  

Heat detectors

 do not sense particles of combustion and 

alarm only when heat on their sensors increases at a predeter-
mined rate or reaches a predetermined level.  Rate-of-rise 
heat detectors may be subject to reduced sensitivity over time.  
For this reason, the rate-of-rise feature of each detector 
should be tested at least once per year by a qualified fire pro-
tection specialist.  Heat detectors are designed to protect 
property, not life.  

IMPORTANT!  Smoke detectors

 must be installed in the 

same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power.  If detectors are not so 
located, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.  

Audible warning devices

 such as bells may not alert people 

if these devices are located on the other side of closed or 
partly open doors or are located on another floor of a building.  
Any warning device may fail to alert people with a disability or 
those who have recently consumed drugs, alcohol or medica-
tion.  Please note that:

• Strobes can, under certain circumstances, cause seizures 

in people with conditions such as epilepsy.  

• Studies have shown that certain people, even when they 

hear a fire alarm signal, do not respond or comprehend the 
meaning of the signal.  It is the property owner's responsi-
bility to conduct fire drills and other training exercise to 
make people aware of fire alarm signals and instruct them 
on the proper reaction to alarm signals.  

• In rare instances, the sounding of a warning device can 

cause temporary or permanent hearing loss.  

A fire alarm system

 will not operate without any electrical 

power.  If AC power fails, the system will operate from standby 
batteries only for a specified time and only if the batteries have 
been properly maintained and replaced regularly.  

Equipment used in the system

 may not be technically com-

patible with the control panel.  It is essential to use only equip-
ment listed for service with your control panel.  

Telephone lines

 needed to transmit alarm signals from a 

premise to a central monitoring station may be out of service 
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.  

The most common cause

 of fire alarm malfunction is inade-

quate maintenance.  To keep the entire fire alarm system in 
excellent working order, ongoing maintenance is required per 
the manufacturer's recommendations, and UL and NFPA stan-
dards.  At a minimum, the requirements of NFPA 72-2002 shall 
be followed.  Environments with large amounts of dust, dirt or 
high air velocity require more frequent maintenance.  A main-
tenance agreement should be arranged through the local man-
ufacturer's representative.  Maintenance should be scheduled 
monthly or as required by National and/or local fire codes and 
should be performed by authorized professional fire alarm 
installers only.  Adequate written records of all inspections 
should be kept.  

     Limit-C1-2-2007

Содержание HPF24S6

Страница 1: ...INSTALLATION MANUAL HPF24S6 HPF24S8 HPF24S6E HPF24S8E HPF24S6C HPF24S8C FIELD CHARGER POWER SUPPLY P N 52751 D3 ECN 10 282 5 11 2010 ...

Страница 2: ...ke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter mined rate or reaches a predetermined l...

Страница 3: ... do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resu...

Страница 4: ...priate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printe...

Страница 5: ...s 20 3 1 DIP Switch Settings 21 3 2 Programmable Features Description 22 3 2 1 Synchronization Type Selection 22 Maximum Number of Strobes for Synchronization 22 3 2 2 Synchronization Mode Master Slave 22 3 2 3 AC Fail Delay Aux Trouble Relay Function 23 3 2 4 Input Output Function 23 Special Application Auxiliary Power Control 24 3 2 5 Charger Enable Disable 24 3 2 6 Door Closers 24 Section 4 Tro...

Страница 6: ...e Battery Size 40 6 4 1 NFPA Battery Requirements 41 6 4 2 Selecting and Locating Batteries 41 Appendix A Wire Requirements 42 A 1 HPF24S Device Compatibility 43 A 1 1 System Sensor 24VDC 43 System Sensor SpectrAlert Advance 43 System Sensor SpectrAlert Advance Speakers 44 A 1 2 Gentex 24VDC 44 A 1 3 Cooper Wheelock 24VDC 45 A 1 4 Notification Appliances For Canadian Applications 46 System Sensor ...

Страница 7: ...d for Installation of Fire Alarm Systems CAN ULC S527 99 Standard for Control Units for Fire Alarm Systems Other NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction LAHJ Canadian Electrical Code Part 1 Other Honeywell Documents Device Compatibilit...

Страница 8: ...8 HPF24S Series Power Supplies P N 52751 D3 5 11 2010 ...

Страница 9: ...ies and battery chargers to power four noncoded or coded NACs The Main FACP Fire Alarm Control Panel NAC s is connected to the remote power supply input circuit s When the control input circuit activates due to reverse polarity of the NAC from the FACP the power supply will activate its Notification Appliance Circuits During the inactive or nonalarm state the power supply supervises its NAC field ...

Страница 10: ...rocedure 1 Configure the power supply jumpers as described in Jumpers on page 11 2 Install the power supply as described in Section 2 Installation on page 15 3 Program the power supply as described in Section 3 Programming Options on page 20 4 Wire the power supply circuits referring to the options described in Section 4 Trouble Supervision on page 25 and the application examples in Section 5 Appl...

Страница 11: ...on green LED indicates AC power is present Ground Fault yellow LED indicates a ground fault condition zero impedance to ground Battery Trouble yellow LED indicates low or no battery NAC Trouble yellow LED indicates a Notification Appliance Circuit trouble blinks once for Circuit 1 trouble twice for Circuit 2 trouble three times for Circuit 3 trouble and four times for Circuit 4 trouble Note that m...

Страница 12: ...he optional ZNAC 4 Class A converter module OR Four resettable or nonresettable 24 VDC power outputs Refer to the Device Compatibility Document for listed compatible devices For wiring requirements refer to Appendix A Wire Requirements on page 42 Trouble Relay Contact Rating TB5 Fail safe Form C relay normally energized transfers with loss of power 5 0 amps 24 VDC or 5 0 amps 30 VAC Secondary Powe...

Страница 13: ...ntrol Input 2 Out Common Out Trouble Contact Control Input 1 Control Input 1 Sync Input Sync Input NAC Out 1 NAC Out 1 NAC Out 2 NAC Out 2 NAC Out 3 NAC Out 3 NAC Out 4 NAC Out 4 Supervised Earth AC Neutral AC Hot Trouble Relay Form C Fail safe Nonsupervised shown energized Normally Open Normally Closed Common JP1 Ground Fault Detection cut to disable see Note at bottom of the page JP2 JP3 Coded N...

Страница 14: ...le 3 1 on page 21 During the inactive state the remote power supply supervises its NAC field wiring for short and open conditions If a fault is detected the power supply will enter a trouble condition and illuminate the NAC Trouble LED When the NACs are activated the supervision is disabled and the circuits are no longer supervised Supervision of other power supply faults such as low battery batte...

Страница 15: ...the board 2 Mark and predrill holes for the top two keyhole mounting bolts 3 Install two upper fasteners in the wall with the screw heads protruding approximately 4 Using the upper keyholes mount the backbox over the two screws 5 Mark the lower two holes remove the backbox from the wall and drill the mounting holes 6 Mount the backbox install the remaining fasteners and tighten all screws 7 When t...

Страница 16: ...Backbox Mounting Figure 2 2 Backbox Mounting Dimensions Bottom Height 15 00 38 10 cm 10 625 26 99 cm 0 75 1 9 cm 2 875 7 3 cm Backbox 14 5 36 8 cm Depth 3 050 7 75 cm Top 9 1 23 1 cm 2 7 6 86cm 1 125 2 868 cm Mounting Plate Pem Studs Backbox Mounting Holes rcpscabb wmf ...

Страница 17: ...ersion module which mounts to connector J3 on the upper right side of the HPF24S circuit board This module allows the HPF24S6 or HPF24S8 to support Style Z Class A Notification Appliance Circuits Figure 2 3 NAC Style Y Class B 4 7K ELR Horn Strobe Horn Strobe Horn Strobe Alarm Polarity Shown HPF24S Circuit Board 24fsclsb wmf Figure 2 4 Style Z Class A NACs using ZNAC 4 Option Module ZNAC 4 Option ...

Страница 18: ...the power wires outside the cabinet As an example Figure 2 5 illustrates wiring from the Auxiliary power output terminals to a FCM 1 control module s terminals 11 and 10 NOTE The module mounting kit P N 90286 is pre installed on the power supply main circuit board Figure 2 5 Mounting Module In HPF24S Cabinet standoff standoff standoff standoff 24fsmodltpH wmf Module Installation 1 Place addressabl...

Страница 19: ...t through different conduits One such example of this is shown below Your specific application may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional Figure 2 6 Power limited Wiring Example AC Power Nonpower limited Output Circuits Power limited Circuits Relay Contacts Nonpower limited Circuit Input Circuits Po...

Страница 20: ... option DIP switch SW1 which is located in the lower center of the circuit board Refer to the following illustration for switch location and DIP switch placement in the ON and OFF positions Important Change DIP switch settings only when all power AC and DC is removed Figure 3 1 Field Programming DIP Switches Switches 1 through 7 shown in OFF Open position Switch 8 shown in ON Closed position 24fss...

Страница 21: ...C Outputs 1 2 are controlled by Control Input 1 and Outputs 3 42 are controlled by Control Input 2 Sync Input is monitored3 Only nonresettable Auxiliary Power is available from TB4 Terminals 9 10 Output 4 function follows DIP switch 8 setting 5 ON 6 OFF Split Temporal HPF24S configured as Master switch 3 OFF Control Input 1 controls NAC Outputs 1 2 and Control Input 2 controls Outputs 3 42 which w...

Страница 22: ...e In some installations it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by an FACP with synchronization capability When installed at the end of an NAC wire run this power supply can track that is follow the strobe synchronization timing pulses on the exi...

Страница 23: ...ble signal for 2 hours In addition the Aux Trouble Relay will immediately respond to all trouble conditions on the power supply DIP switch 4 set to the OFF position will allow the HPF24S to generate a trouble signal immediately on the loss of AC power In addition the Aux Trouble Relay will respond only to AC power fail brownout conditions Refer to Section 4 1 2 Supervision of HPF24S Faults on page...

Страница 24: ...are controlled by Control Input 1 Sync Input is monitored2 Resettable or nonresettable Auxiliary Power Output is available from TB4 Terminals 9 10 Control Input 2 determines if reset will occur must go from On to Off for a 6 second reset to occur OFF ON Split Alarm HPF24S configured as Master switch 3 OFF NAC Outputs 1 2 are controlled by Control Input 1 and Outputs 3 41 are controlled by Control ...

Страница 25: ...ll cause a general NAC trouble A field wiring fault on the NAC output of the power supply An AC fail condition at the power supply only if SW1 switch 4 is ON and a two 2 hour delay has expired If SW1 switch 4 is OFF the internal trouble contact will not respond to an AC Fail condition A battery fail condition at the power supply A battery charger fail on the power supply A ground fault condition o...

Страница 26: ...s Reporting Delay The reporting of AC loss to a central station is usually delayed in order to prevent multiple transmissions of AC loss and restoral thus allowing AC power to stabilize When a host FACP is programmed to delay AC loss reporting the HPF24S must be configured to delay the reporting of AC fail This is accomplished by setting SW1 DIP switch 4 to the ON position This will prevent AC los...

Страница 27: ...HPF24S Series Power Supplies P N 52751 D3 5 11 2010 27 Notes ...

Страница 28: ...ontrolled from one input such as an addressable control module as illustrated in Figure 5 1 The control module can be powered from the HPF24S auxiliary 24 VDC power output TB4 Terminals 9 10 and supervised by an EOL relay An addressable relay module programmed as an alarm output and a silenceable point can be used as a selective silence input NOTE The Relay Module is required only for this applica...

Страница 29: ...o maintain proper supervision Figure 5 1 Controlling Four Outputs With One Input Control Module Relay Module EOL Power Supervision Relay EOLR 1 energized SLC SLC Style Z Class A Style Y Class B Use listed ELR 4 7K to terminate Style Y Class B NAC Note All NACs are supervised and power limited ZNAC 4 Option Module Output NAC 4 Output NAC 3 Output NAC 2 Output NAC 1 HPF24S has been set for Selective...

Страница 30: ...B4 Terminal 7 IN must be jumpered to Terminal 9 AUX and Terminal 8 IN must be jumpered to Terminal 10 AUX The FACP will control the Selective Silence feature with this configuration If the terminals are not jumpered as indicated the horn portion of the horn strobes will be silenced at all times 5 2 Controlling Three NACs and One Door Holder With One Input In this application the power supply has b...

Страница 31: ...w terminals Break wires to maintain proper supervision 4 An End of Line Resistor must be installed between terminals 5 6 for control module wiring supervision the ELR value is dependent on the module employed 5 For a list of compatible devices refer to the Device Compatibility Document Figure 5 2 Controlling Three NACs and One Door Holder With One Input Style Z Class A Style Y Class B Door Holder ...

Страница 32: ... 5 3 Split Temporal Mode Application Style Z Class A Style Y Class B Temporal Bell Circuit 4 Temporal Bell Circuit 3 Horn Strobe Circuit 2 Horn Strobe Circuit 1 Use listed ELR 4 7K to terminate Style Y Class B NAC ELR not required for Style Z Class A NAC Note All NACs are supervised and power limited ZNAC 4 Option Module SW1 Switch Settings 1 2 sync any setting but OFF OFF 3 OFF master 4 OFF no AC...

Страница 33: ...le devices refer to the Device Compatibility Document 5 4 Remote Supply With Resettable and Nonresettable Power The HPF24S can be used as a remote stand alone power supply to provide power to any devices that require filtered resettable or nonresettable power The HPF24S6 can provide up to 4 amps of continuous current and the HPF24S8 can provide up to 6 amps of continuous current The power supply m...

Страница 34: ...ne power supervision relay must be connected between TB4 Terminals 5 6 The Normally Closed when energized power supervision relay contact must be in series with the End of Line Resistor referred to in note 1 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 For a list of compatible devices refer to the Device Compatibility Document Figure 5 4 Remote Power Suppl...

Страница 35: ...determine the source of the sync signal 4 If the FACP has a dedicated sync output connector wire the sync output connnector to the HPF24S Sync In terminals terminals 1 and 2 on TB4 Refer to the Supervised Master Slave Connections Remote Sync Source in 5 5b Standby Polarity Shown Horn Strobes HPF24S SW1 Switch Settings 1 2 sync any setting but OFF OFF 3 ON slave 4 OFF no AC Fail reporting delay 5 O...

Страница 36: ...chronized output Notes The following notes apply to this Figure 5 6 1 Refer to NFPA 72 Visible Characteristics Public Mode 2 Use only devices from the same manufacturer in each system Standby Polarity Shown Horn Strobes no synchronization HPF24S SW1 Switch Settings 1 2 sync any setting but OFF OFF 3 OFF master 4 OFF no AC Fail reporting delay 5 OFF 6 OFF 7 OFF charger enabled 8 OFF circuit 4 NAC g...

Страница 37: ...st FACP must monitor for all ground fault conditions The Ground Fault Detection circuit on the HPF24S power supply must be disabled by cutting jumper JP1 the negative battery terminal of the HPF24S power supply must be connected to the negative battery terminal of the host FACP Host FACP HPF24S Power Supply Battery Battery NAC Outputs only Cut JP1 24fsCanadiantpH wmf If the SLC device does not mat...

Страница 38: ...cuit must comply with Article 760 of the National Electrical Codes as well as local codes Use 14 AWG 2 00 mm2 wire with 600 volt insulation for this branch circuit Use Table 6 1 to determine the total amount of current in AC amperes that must be supplied to the system 6 3 Calculating the System Current Draw 6 3 1 Overview The power supply must be able to power all internal and external devices con...

Страница 39: ...or each in all columns 4 Sum the total current for each column 5 Copy the totals from Column 2 and Column 3 to Table 6 3 on page 40 Following are the types of current that can be entered into Table 6 3 on page 40 Calculation Column 1 The primary supply current load that the power supply must support during a non fire alarm condition with AC power applied Calculation Column 2 The primary supply cur...

Страница 40: ...lation Columns 2 and 3 where shown 2 Enter the NFPA Standby and Alarm times Refer to NFPA Battery Requirements on page 41 3 Calculate the ampere hours for Standby and Alarm then sum the Standby and Alarm ampere hours 4 Multiply the sum by the derating factor of 1 2 to calculate the proper battery size in AH Device Type Calculate Column 1 Primary Non Fire Alarm Current amps Calculate Column 2 Prima...

Страница 41: ...apable of housing batteries up to 7 AH Batteries larger than 7 AH require the BB 17 or other UL listed external battery cabinet Secondary Standby Load total from Table 6 3 Calculation Column 3 Required Standby Time 24 or 60 hours X AH Primary Alarm Load total from Table 6 3 Calculation Column 2 Required Alarm Time for 5 min enter 0 084 for 10 min enter 0 168 X AH Sum of Standby and Alarm Ampere Ho...

Страница 42: ...llowable total loop resistance ohms CLASS B Max allowable wire pair length feet CLASS A Max allowable wire pair length feet AWG 12 solid AWG 14 solid AWG 16 solid AWG 18 solid AWG 12 solid AWG 14 solid AWG 16 solid AWG 18 solid 0 25 12 80 3316 2085 1309 824 1658 1042 654 412 0 5 6 40 1658 1042 654 412 829 521 327 206 0 75 4 27 1105 695 436 275 553 347 218 137 1 0 3 20 829 521 327 206 415 261 164 1...

Страница 43: ...robe with Fuego lens MASS2415ADA MASS2475ADA MASS24110ADA MASS241575ADA Sounder Signaling Strobe MASS2415ADAS MASS241575ADAS Sounder Signaling Strobe w Synch Ckt MDL MDLW Sync Modules for use with SpectraAlert series P2415 P241575 P2430 P2475 P24110 SpectrAlert Horn Strobe PA400R PA400W PA400B Sounder PC24115 PC24177 SpectrAlert Ceiling Mount Horn Strobe PS24LO Add on Strobe RP2415ADA RP241575ADA ...

Страница 44: ... 60W Electro Mechanical Horn with Strobe GOT 24 Multi Tone Horn GOS 24 15 1 GOS 24 110 1 GOS 24 1575 1 GOS 24 3075 1 Multi Tone Horn Strobe GXS 4RH GXS 4BH GXS 4RL GXS 4BL Strobes GXS 4 15 GXS 4 15 1 GXS 4 1575 GXS 4 30 GXS 4 60 GXS 4 110 GXS 4 110 1 GXS 4 3075 Strobe GX 90 4 Horn GX 90S 4BH GX 90S 4BL GX 90S 4RL GX 90S 4RH GX 90S 4 15 GX 90S 4 15 1 GX 90S 4 110 GX 90S 4 110 1 GX 90S 4 1575 Horn w...

Страница 45: ...H DF1 IS 24 VFR CH DF1 LS 24 VFR CH DF1 LSM 24 VFR CH DF1 MS 24 VFR Chime CH70 24 R W CH90 24 R W Chime CH70 2415W CH70 2430 CH70 2475 CH70 241575 Chime with Strobe CH70 24MCW FR FW Multi Candela Appliance CH90 2475C CH90 24100C Chime with Strobe DSM 12 24 Dual Synchronization Module EH DL1 WM 24 VF R EH EL1 WM 24 VF R Electronic Horn Strobes HSW 24 HFR HSPW 24 HFR HS2W HFR Strobe IS 24 VFR IS1 24...

Страница 46: ... 2430 RS 2475 RS 24110 RS 241575 Strobe RS 2415W RS 241575W Strobe RSS 2415W RSS 2415 75W RSS 2430W RSS 2475W RSS 24110W Strobe RSS 24MCW FR FW Strobe RSS 2415 CR FW RSS 2430 CR FW RSS 2475 CR FW RSS 24100 CR FW Strobe RSS 24150 CR FW RSS 24177 CR FW Strobe RSSP 24MCW FR FW strobe RSSP 2415W RSSP 2415 75W RSSP 2430W RSSP 24185W Strobe SCM 24 R Synchronized Controller Module SHW 24 HFR SH2W 24 HFR ...

Страница 47: ... Models AVS44 and AVSM may be followed by Suffix W or R white or red color Intended for indoor use with Gentex synchronizable strobe lights Horns Models GEH24 GEH12 followed by P R or W indoor use only Models GX91 and GX93 for indoor use Horn strobes Models GEC24 15 15 75 30 60 75 110 177 may be followed by P R or W HS24 15 15 75 30 60 75 110 may be followed by C or W ceiling or wall R or W red or...

Страница 48: ...ry charger trouble LED 11 C cabinet see also backbox 16 capacity battery 12 charge current maximum 12 charger trouble 9 LED 11 circuit board layout 13 Class A Converter Module 17 see also ZNAC 4 9 Class B see also Style Y 9 Coded Input 11 Coded Noncoded Input Selection 11 coding NAC 9 compatibility input circuit 9 control circuit 9 current 12 see also input circuit 12 voltage 12 current maximum co...

Страница 49: ... NAC Trouble LED 11 NACs 10 NEC power limited wiring requirements 19 NFPA Style see also Style 9 nonalarm state 9 Noncoded Input 11 nonresettable power 24 Notification Appliance Circuit see also NAC 9 O output circuit types 12 maximum current 3 0 amps 12 output circuit current 12 maximum current 9 see also NAC output 12 Style 12 voltage rating 12 output power 9 P Power nonresettable 9 resettable 9...

Страница 50: ... 11 2010 T Z Index System Sensor 24VDC 43 T trouble supervision 25 trouble relay 9 10 12 25 contact rating 12 trouble supervision 9 troubles 25 power supply 9 W wiring 10 AC power 12 power limited 19 Z ZNAC 4 17 see also Class A Converter Module 9 ...

Страница 51: ...HPF24S Series Power Supplies P N 52751 D3 5 11 2010 51 ...

Страница 52: ...Automation and Control Solutions Honeywell Power Products l2 Clintonville Road Northford CT 06472 1610 www honeywellpower com U S Registered Trademark 2010 Honeywell International Inc 52751 D3 Rev 05 10 ...

Отзывы: