background image

HP400ULM Installation Document  P/N 52390:A  1/05/06

3

b)

 JL OFF

 will cause the unit to latch 

ON

 until manually reset.  Install the 2.2K Ohm (EOL) resistor provided at a 

Key Switch or Push Button to perform this manual reset operation and to supervise this connection as shown in Fig 
1a.

6. Alarm/Trouble Output

a) Power Fail

: When DC Power fails or PTC activates this will cause the dry contact “Form C” relay to de-energize.

b) Fire Alarm

:  When the FACP activates this will cause the dry contact “Form C” relay to de-energize.

7. Cascade Connection

Two (2) or more HPMOM6 units can be connected together as follows;  Connect the Fire Alarm relay C and NC terminals 
from the 1st unit to the “FIRE INTRFC” of the 2nd unit (not polarity sensitive) and remove jumper 

JR

 of the 1st unit. If a 

3rd HPMOM6 is used,

 JR

 must be removed from 2nd unit and so on for each new addition. See Fig. 1a.

8. Power Board Connections

Connect the “AC Fail” output “Form C” dry contacts to the monitoring device.  In case of AC loss the relay, which is Fail 
Safe, will de-energize within one (1) minute.  Connect the Battery Fail output “Form C” dry contacts to the monitoring 
device. If a Battery is not connected or improperly connected, the Yellow LED (L3) will turn ON within one (1) minute 
and the Battery Fault output relay, which is Fail Safe, will de-energize. 

9. Power Up

When all wiring is complete and checked, switch ON the AC Power.  The Green Led (L1) will come ON indicating AC 
presence and the AC relay will be energized.  Connect Battery observing the correct polarity.  For 24VDC use the battery 
link provided to connect the two (2) 12 Volt Batteries in series.  Secure the enclosure with the 4 screws and with the Key 
Lock provided.  

NOTE: For UL603 or UL294 applications use a Tamper Switch (Catalog number HPVM3 available separately), and 
included enclosure key lock. Connect the tamper switch NC outputs to monitoring device to notify of enclosure tampering.

4 LED Indications

Power Board  

Distribution Board 

LED Number

Power Board Status When Lit

L1

Green LED - AC present

L2

Red LED - PTC activated

L3

Yellow LED - battery low or disconnected

L4

Red LED - DC power failure

L5

Red LED - DC output present

LED Number

Distribution Board Status When Lit

L0

Red LED - Power ON

L1 - L6

Green LED - PTC activated

L7

Yellow LED - FACP alarm activated

Continued on next page...

Содержание HP400ULM

Страница 1: ...Triggered The unit has not been evaluated as elevator equipment and is not authorized for bell output in Mercantile applications 2 Specifications A Power Supply Board 1 Input voltage 120VAC 60Hz Current 2 50A max 2 Output Voltage 12VDC or 24VDC jumper selectable Current 4 0A continuous output maximum 3 5A plus battery charger not supervised 3 Fail safe dry contact output on AC Failure within one m...

Страница 2: ...tput Connections There are 6 outputs selectable together as Switched Normally Open NO or Switched Normally Closed NC There are 2 possible output type connections in either case connect device negative to Neg terminal on HPMOM6 1 For Fail Safe operation connect device positive to DC STANDBY OUTPUT on HPMOM6 DC power is present in normal condition and will switch OFF when the FACP is triggered Fail ...

Страница 3: ...ute Connect the Battery Fail output Form C dry contacts to the monitoring device If a Battery is not connected or improperly connected the Yellow LED L3 will turn ON within one 1 minute and the Battery Fault output relay which is Fail Safe will de energize 9 Power Up When all wiring is complete and checked switch ON the AC Power The Green Led L1 will come ON indicating AC presence and the AC relay...

Страница 4: ...Hr Stand By 15Mins ALRM 60Hr Stand By 5Mins ALRM 12Ah 12V STBY 2 00A N A N A ALRM 3 50A N A N A 17Ah 12V STBY 2 00A 200mA N A ALRM 3 50A 2 00A N A 55Ah 12V STBY 3 50A 1 50A 300mA ALRM 3 50A 3 50A 3 50A 12Ah 24V STBY 2 00A N A N A ALRM 3 50A N A N A 17Ah 24V STBY 2 00A 200mA N A ALRM 3 50A 3 50A N A 55Ah 24V STBY 3 50A 1 50A 300mA ALRM 3 50A 3 50A 3 50A UL Listing UL294 UL603 UL294 UL603 UL1481 UL1...

Страница 5: ...HP400ULM Installation Document P N 52390 A 1 05 06 5 Continued on next page ...

Страница 6: ...00ULM Installation Document P N 52390 A 1 05 06 For additional information Visit our website at http www honeywellpower com Contact Technical Support at 1 877 HPP POWR E mail us at hpp techserv honeywell com ...

Отзывы: