HP400ULM Installation Document  P/N 52390:A  1/05/06

5 Battery Stand-By Mode Specification Chart  

6 Maintenance

This unit should be tested at least once a year to verify correct operation in accordance with the following 
recommendations;

Output Voltage Test -

  Voltage output should be tested under normal load conditions to verify correct levels. 

Battery Test -

 Battery should be checked for full charge under normal load conditions.  This check should verify correct 

voltage at both battery terminals and also at the Battery output point on the board to ensure the integrity of all connecting 
wiring.  It is recommended to replace the battery at least every 4 years.

LED Test 

(distribution board only)

 -

 Verify yellow LED operation by pushing LED test button.  All yellow LED’s should 

illuminate.

 

Output Battery 

Capacity

STBY/ALRM

4Hr Stand-By 

15Mins/ALRM

24Hr Stand-By 

15Mins/ALRM

60Hr Stand-By 

5Mins/ALRM

12Ah-12V

STBY

2.00A

N/A

N/A

ALRM

3.50A

N/A

N/A

17Ah-12V

STBY

2.00A

200mA

N/A

ALRM

3.50A

2.00A

N/A

55Ah-12V

STBY

3.50A

1.50A

300mA

ALRM

3.50A

3.50A

3.50A

12Ah-24V

STBY

2.00A

N/A

N/A

ALRM

3.50A

N/A

N/A

17Ah-24V

STBY

2.00A

200mA

N/A

ALRM

3.50A

3.50A

N/A

55Ah-24V

STBY

3.50A

1.50A

300mA

ALRM

3.50A

3.50A

3.50A

UL Listing

UL294
UL603

UL294
UL603

UL1481

UL1481

!

WARNING: To reduce risk of electric shock, do not expose unit to rain or excess moisture, and disconnect 
power before servicing unit.

For continuous protection against hazard, replace fuses only with exact type and rating.  A readily accessible 
switched circuit breaker must be available to disconnect main power as required.  All power limited wiring should 
be routed so that it cannot touch non-power limited wiring; minimum spacing 1/4”.  Installation and servicing 
should only be made by qualified personnel; contains no user-serviceable parts.  Install in accordance with all local 
regulations and the National Electrical Code.

Continued on next page...

Содержание HP400ULM

Страница 1: ...Triggered The unit has not been evaluated as elevator equipment and is not authorized for bell output in Mercantile applications 2 Specifications A Power Supply Board 1 Input voltage 120VAC 60Hz Current 2 50A max 2 Output Voltage 12VDC or 24VDC jumper selectable Current 4 0A continuous output maximum 3 5A plus battery charger not supervised 3 Fail safe dry contact output on AC Failure within one m...

Страница 2: ...tput Connections There are 6 outputs selectable together as Switched Normally Open NO or Switched Normally Closed NC There are 2 possible output type connections in either case connect device negative to Neg terminal on HPMOM6 1 For Fail Safe operation connect device positive to DC STANDBY OUTPUT on HPMOM6 DC power is present in normal condition and will switch OFF when the FACP is triggered Fail ...

Страница 3: ...ute Connect the Battery Fail output Form C dry contacts to the monitoring device If a Battery is not connected or improperly connected the Yellow LED L3 will turn ON within one 1 minute and the Battery Fault output relay which is Fail Safe will de energize 9 Power Up When all wiring is complete and checked switch ON the AC Power The Green Led L1 will come ON indicating AC presence and the AC relay...

Страница 4: ...Hr Stand By 15Mins ALRM 60Hr Stand By 5Mins ALRM 12Ah 12V STBY 2 00A N A N A ALRM 3 50A N A N A 17Ah 12V STBY 2 00A 200mA N A ALRM 3 50A 2 00A N A 55Ah 12V STBY 3 50A 1 50A 300mA ALRM 3 50A 3 50A 3 50A 12Ah 24V STBY 2 00A N A N A ALRM 3 50A N A N A 17Ah 24V STBY 2 00A 200mA N A ALRM 3 50A 3 50A N A 55Ah 24V STBY 3 50A 1 50A 300mA ALRM 3 50A 3 50A 3 50A UL Listing UL294 UL603 UL294 UL603 UL1481 UL1...

Страница 5: ...HP400ULM Installation Document P N 52390 A 1 05 06 5 Continued on next page ...

Страница 6: ...00ULM Installation Document P N 52390 A 1 05 06 For additional information Visit our website at http www honeywellpower com Contact Technical Support at 1 877 HPP POWR E mail us at hpp techserv honeywell com ...

Отзывы: