Checking the lower threshold value
The setting for underpressure, resp. diaphragm fracture protection, has to be checked
as follows.
Pressurise the pressure converter. Choose a pressure value between the lower
and higher threshold values.
Let the pressure in the pressure converter decrease slowly.
When the lower threshold value has been reached, the system has to switch.
Bring the pressure in the pressure converter back to a value between the lower
and the higher threshold values.
Bring the pressure above and below the valve in equilibrium, by means of the
bypass.
Lock the HON HSV (see chapter 4.4).
Run this check several times.
Checking the higher threshold value
Bring the pressure in the pressure converter to a value between the lower and
higher threshold values.
Let the pressure in the pressure converter increase slowly.
When the higher threshold value has been reached, the system has to switch.
Bring the pressure in the pressure converter back to a value between the lower
and the higher threshold values.
Bring the pressure above and below the valve in equilibrium, by means of the
bypass.
Lock the HON HSV (see chapter 4.4).
Run this check several times.
Checking the emergency button
Build up the normal initial pressure in the pressure converter.
Press the emergency button of the SVC086 (red button at the top of the SVC086)
The system should now switch.
Bring the pressure above and below the valve in equilibrium, by means of the
bypass.
Release the HON HSV (see chapter 4.4).
Run this check several times.