10260A Series Actuators Installation, Operations, and Maintenance Manual
8
10260A Series Actuators – Installation, Operations, and Maintenance
2/03
Physical
Output Torque/Full Travel
Stroking Time
Model #
10261A
10262A
10264A
10266A
10267A
10268A
10269A
10263A
10265A
Torque
Lb.-ft N-M
10
15
20
27
40
55
60
80
40
55
80
110
150 200
200 270
300 400
Output Shaft Speed sec/90
°
@ 60Hz @ 50Hz
10
12
20
24
40
48
60
72
20
24
40
48
60
72
40
48
60
72
Electrical
Power Input
120 Vac single phase, 50 or 60 Hz
240 Vac single phase, 50 or 60 Hz
Motor
Instant start/stop, non-coasting, non-burnout, continuous duty permanent magnet
synchronous induction motor. Can be stalled up to 100 hours without damage.
Motor Current
= No load = full load = locked rotor
Model
No.
10261A, 62A, 64A, 66A
10263A, 10265A
10267A, 68A, 69A
120 V, 50/60 Hz
0.4 A (48 VA)
1.0 A (120 VA)
0.8 A (96 VA)
240 V, 50/60 Hz
0.3 A (24 VA)
1.0 A (60 VA)
0.3 A (36 VA)
Loss of Power
Stays in Place
Local Auto/Manual Switch
Optional - allows local and automatic operation of the actuator.
Limit Switches
Standard - Two SPDT end of travel limits rated (10 A at 125 Vac, 5 A at 250 Vac).
Auxiliary Switches
Optional - Up to 4 additional SPDT switches rated (10 A at 125 Vac, 5 A at 250 Vac)
Certifications
CE Compliance
89/336/EEC EMC Directive, 73/23/EEC Low Voltage Directive.
NEMA 4
Optional
Torque Settings of Crank Arm Bolts
Clamp Bolt
Standard Arm (p/n 087449) (1-7/16–5 in. adjustment): 85 lb.-ft.
Optional Long Arm (p/n 154007) (0–12 in. adjustment): 85 lb.-ft.
Rod End Bolt
Standard and long arms: 30-35 lb.-ft
Содержание HercuLine 10260A
Страница 10: ...x 10260A Series Actuators Installation Operations and Maintenance 2 03 ...