HE105, HE205 WHOLE HOME BYPASS HUMIDIFIER

33-00229EF—01

4

7.

Make sure the humidifier housing is level, then posi-
tion it in the opening so the plastic tabs are in place 
on the 

lower sheet metal edge

 of the opening. Use 

pliers, as necessary, to flatten cut edges. See Fig. 5.

8.

Secure the humidifier housing to the opening at the 
top and bottom using sheet metal screws.

9.

Reassemble humidifier side plates to customize the 
orientation for your specific install. The side plate 
with the humidifier port needs to be on the side of 
the humidifier that is closest to the bypass ducting. 
Be sure to open the bypass flap for use and close it 
when the humidifier is not used. See Fig. 6.

Fig. 5. Installing humidifier on duct.

10.

Slide bypass duct over the humidifier port on the 
HE105/HE205, making sure that the flex duct 
advances past the raised plastic tabs on the port. 
These tabs will help to hold the flex duct in place. 
Verify that the damper blade has adequate clear-
ance to move back and forth between the closed and 
open positions. Secure the flex duct in place with the 
plastic connector strap.

11.

Seal the duct connections with foil tape. Seal both 
1) the connection between the starter collar end of 
the flex duct and the home's duct work and 
2) the end of the flex duct to the humidifier over the 
top of the connector strap.

12.

Reinstall the humidifier pad assembly in the humidi-
fier housing.

13.

Hinge the cover in place and secure with the thumb-
screw located at the bottom of the cover.

Fig. 6. Connecting bypass ducting.

Connecting the Plumbing

1.

Hot or cold water, either hard or softened, can be 
used in the humidifier. Cut the water line so it 
reaches from the humidifier to the main water 
supply tap.

2.

Turn off water supply and tap into a water line.
• Consult local codes for proper plumbing.
• Use an approved saddle valve or a T-fitting and 

manual shutoff valve to tap into the water line.

• Refer to the literature included with the valve you 

chose and the local plumbing codes. Use proper 
technique for the valve.

• Connect the other end of the humidifier water line 

to the water valve.

• Use 1/4 in. O.D. copper tubing and connect  to 

inlet side of solenoid valve via a compression 
fitting or Honeywell Quick Connect fitting.

• Place brass compression nut over copper tubing.

NOTE:

Do not over tighten compression nut.

• Moderate tightness prevents leaking.
• Slide the brass ferrule over the tubing.
• Insert tubing into solenoid valve fitting and 

support the valve while tightening the 
compression nut.

3.

Connect a water drain line.

• Consult and follow local plumbing codes for 

drain pipe size and flow requirement.

• The ideal installation is directly to the main 

floor drain using a rubber drain hose.

a. Slide a drain clamp over the tubing.
b. Push the tubing over the drain nipple on the 

humidifier.

c. Route the drain hose to the floor drain. The hose 

must have a continuous downward slope.

d. Direct the hose outlet into the floor drain. Secure 

the hose to reduce the risk of water pooling or 
splashing as it drains from the humidifier. See 
Fig. 7.

DUCT

LEVEL

S

HEET METAL

S

CREW

S

 (4)

PLA

S

TIC

TAB

S

 (2)

DRAIN TUBIN

G

M36295

OPENIN

G

TO AIR DUCT

M36298

HUMIDIFIER PORT

CONNECTOR 

S

TRAP

Содержание HE105

Страница 1: ...me honeywell com or call Honeywell Customer Care toll free at 1 800 468 1502 PREPARING FOR THE INSTALLATION Be sure to identify all the required Table 1 accessories included and make sure the appropriate tools are available before beginning the installation Included in the box Humidifier H8908 Humidistat Plug in transformer Canadian C models also include 6 in dia bypass ducting 24 in 18 gauge ther...

Страница 2: ... cause property or equipment damage Locate humidifier where ambient temperature is between 41 and 113 F 5 to 45 C Do not install humidifier where freezing temperatures could occur Be sure supply plenum static pressure is no greater than 0 4 in wc and water pressure is no greater than 120 psi CAUTION Sharp Edges Installation Hazard Can cause personal injury Wear gloves and safety glasses IMPORTANT ...

Страница 3: ...RTANT Be sure the mounting template is level before marking Use of a small level is recommended 3 Locate the template form number 33 00210 included in the box For the HE105 model cut out the template along the dotted line For the HE205 model use the entire sheet as a template 4 Tape the template in position and trace around the template 5 Remove the template and carefully cut the rectangular openi...

Страница 4: ...f the cover Fig 6 Connecting bypass ducting Connecting the Plumbing 1 Hot or cold water either hard or softened can be used in the humidifier Cut the water line so it reaches from the humidifier to the main water supply tap 2 Turn off water supply and tap into a water line Consult local codes for proper plumbing Use an approved saddle valve or a T fitting and manual shutoff valve to tap into the w...

Страница 5: ...ng steps to check the humidifier operation 1 Turn on the power and the water supply 2 Ensure the saddle valve or T valve fitting is fully opened by turning the handle to the left counter clockwise until there is resistance 3 Turn the H8908 Humidistat to On and turn on the heat by setting the thermostat to 10 ºF 6 ºC above room temperature 4 Make sure that water is flowing out of the drain hose If ...

Страница 6: ...use either hard or soft water in your humidifier but hard water mineral deposits are more difficult to clean than soft water deposits IMPORTANT Never oil any part of the humidifier End of Humidification Season Clean the humidifier and shut it off at the end of the heating season Turn the water off at the saddle valve or T valve fitting by turning the handle to the right clockwise until the water s...

Страница 7: ...ier Remove cover and verify that water flows into distribution tray Drain tubing Verify no obstructions Air leakage Check duct joints Seal with foil tape Low humidity Furnace blower not operating Reset circuit breaker or check for blown fuse Check that the furnace power is on Check all external wiring connections Check the humidity control setting Call a professional heating contractor Rapid air c...

Страница 8: ... is shown by Honeywell that the defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer Honeywell s sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM...

Страница 9: ...e de Honeywell au 1 800 468 1502 PRÉPARATION À L INSTALLATION Veiller à identifier tous les accessoires inclus répertoriés dans le tableau 1 et s assurer que les outils appropriés sont disponibles avant de commencer l installation Inclus dans la boîte Humidificateur Humidistat H8908 Transformateur enfichable Les modèles C canadiens incluent également Conduit de dérivation de 6 po de dia 24 po Fil ...

Страница 10: ...a température ambiante est comprise entre 5 C et 45 C 41 F et 113 F Ne pas installer l humidificateur dans un endroit où des températures inférieures ou égales à 0 C 32 F peuvent être présentes S assurer que la pression statique de l alimentation dans le plénum ne dépasse pas 0 4 po c e et que la pression de l eau ne dépasse pas 120 psi MISE EN GARDE Danger de bords coupants durant l installation ...

Страница 11: ...Il est recommandé d utiliser un niveau de petite taille 3 Repérer le gabarit formulaire n 33 00210 inclus dans la boîte Pour le modèle HE105 couper le gabarit le long de la ligne pointillée Pour le modèle HE205 utiliser la feuille entière comme gabarit 4 Fixer le gabarit à l emplacement requis avec du ruban adhésif et en tracer le contour 5 Enlever le gabarit et couper avec soin une ouverture rect...

Страница 12: ...couvercle et le fixer avec la vis de serrage à main située en bas du couvercle Fig 6 Connexion du conduit de dérivation Connexion de la plomberie 1 L humidificateur fonctionne avec de l eau dure ou de l eau douce L eau peut être chaude ou froide Couper la canalisation d eau de façon à ce qu elle s achemine de l humidificateur à la prise d arrivée d eau principale 2 Fermer l arrivée d eau et accéde...

Страница 13: ...eau à l intérieur de l humidificateur est connectée au plateau de distribution d eau PerfectFLO Après l installation procéder aux étapes suivantes pour vérifier le fonctionnement de l humidificateur 1 Mettre sous tension et ouvrir l arrivée d eau 2 S assurer que la vanne à étrier ou le raccord de vanne en T est complètement ouvert e avec la poi gnée tournée à gauche sens antihoraire jusqu à sentir...

Страница 14: ...es dépôts minéraux de l eau dure sont plus difficiles à nettoyer que les dépôts d eau douce IMPORTANT Ne jamais huiler une pièce quelle qu elle soit de l humidificateur Fin de la saison d humidification Nettoyer l humidificateur et l éteindre à la fin de la session de chauffage Couper l eau au niveau de la vanne à étrier ou du raccord de vanne en T en tournant la poignée à droite sens horaire jusq...

Страница 15: ...ifier que l eau s écoule dans le plateau de distribution Tube d évacuation Vérifier qu il n y a pas d obstruction Fuite d air Vérifier les joints des conduits Sceller avec du ruban en aluminium Basse humidité La soufflante de l appareil de chauffage ne fonctionne pas Réenclencher le disjoncteur ou rechercher un fusible grillé Vérifier que l appareil de chauffage est alimenté en courant Vérifier to...

Страница 16: ...eur l avait en sa possession La responsabilité exclusive de Honeywell se limite à réparer ou à remplacer le produit conformément aux modalités susmentionnées HONEYWELL N EST EN AUCUN CAS RESPONSABLE DES PERTES OU DOMMAGES Y COMPRIS LES DOMMAGES INDIRECTS OU ACCESSOIRES DÉCOULANT DIRECTEMENT OU INDIRECTEMENT D UNE VIOLATION QUELCONQUE D UNE GARANTIE EXPRESSE OU TACITE APPLICABLE AU PRÉSENT PRODUIT ...

Отзывы: