GSMV4G/GSMVCN4G Installation and Setup Guide
3-16
PROMPTS
ZONE
TRIG.
4204/
2-4204
OPTIONS
DESCRIPTION
41
Rpt Zn3 ONLY if
Armed (N)_
X
X
[Y], [N]
Reports alarms on zone 3 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 3.
4204 mode: If any zone is programmed to "Report
Only if Armed," skip to Prompt 52: "Enable Zn6."
42
Zn4 Trigger Type
(V+)_
X
•
(EOLR)
•
(V+)
•
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
43
Invert Zn4 Y/N
(N)_
X
[Y], [N]
Inverts the alarm and normal states of the zone 4
trigger; otherwise uses normal input signal.
44
Restore Zn4 Y/N
(Y)_
X
X
[Y], [N]
Enables restore reporting for zone 4.
UL/ULC: Must be set to “Y.”
45
Delay Zn4 (secs)
(00)
X
X
[01-15]
[00] = no delay
Defines the reporting delay in seconds for
zone 4.
UL/ULC: Must be set to “00.”
46
Rpt Zn4 ONLY if
Armed (N)_
X
2-
4204
only
[Y], [N]
Reports alarms on zone 4 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-4204
mode) is triggered (armed).
If [N], always reports alarms on zone 4.
47
Zn5 Trigger Type
(V+)_
X
•
(EOLR)
•
(V+)
•
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
48
Invert Zn5 Y/N
(N)_
X
[Y], [N]
Inverts the alarm and normal states of the zone 5
trigger; otherwise uses normal input signal.
49
Restore Zn5 Y/N
(Y)_
X
2-
4204
only
[Y], [N]
Enables restore reporting for zone 5.
UL/ULC: Must be set to “Y.”
50
Delay Zn5 (secs)
(00)_
X
2-
4204
only
[01-15]
[00] = no delay
Defines the reporting delay in seconds for
zone 5.
UL/ULC: Must be set to “00.”
51
Rpt Zn5 ONLY if
Armed (N)_
X
2-
4204
only
[Y], [N]
Reports alarms on zone 5 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-4204
mode) is triggered (armed).
If [N], always reports alarms on zone 5.
52
Enable Zn6 Y/N
(N)_
4204
only
[Y], [N]
Enables alarm reporting for zone 6.
If [N], skip to Prompt 58: "Enable Zn7."
53
Zn6 Trigger Type
(V+)_
X
4204
only
•
(EOLR)
•
(V+)
•
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
54
Invert Zn6 Y/N
(N)_
X
4204
only
[Y], [N]
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
55
Restore Zn6 Y/N
(Y)_
X
X
[Y], [N]
Enables restore reporting for zone 6.
UL: Must be set to “Y.”
56
Delay Zn6 (secs)
(00)_
X
X
[01-15]
[00] = no delay
Defines the reporting delay in seconds for
zone 6.
UL/ULC: Must be set to “00.”
Содержание GSMV4G
Страница 2: ......
Страница 40: ...GSMV4G GSMVCN4G Installation and Setup Guide 4 4 ...
Страница 46: ...GSMV4G GSMVCN4G Installation and Setup Guide 5 6 ...
Страница 47: ...A 1 Appendices Appendix A Summary of LED Operation ...
Страница 48: ...GSMV4G GSMVCN4G Installation and Setup Guide A 2 ...
Страница 50: ...GSMV4G GSMVCN4G Installation and Setup Guide B 2 ...
Страница 52: ...GSMV4G GSMVCN4G Installation and Setup Guide C 2 ...
Страница 53: ...NOTES ...
Страница 54: ...NOTES ...
Страница 55: ...NOTES ...
Страница 56: ...NOTES ...
Страница 57: ...NOTES ...
Страница 58: ...NOTES ...
Страница 59: ...NOTES ...
Страница 60: ...NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...NOTES ...