GSMV4G/GSMVCN4G Installation and Setup Guide
3-12
PROMPTS
ZONE
TRIG.
4204/
2-4204
OPTIONS
DESCRIPTION
16
Direct Wire Y/N
(N)_
X
[Y], [N]
Applies only to
VISTA-128BP/250BP and FBP
Series control panels.
If [N], and if Prompt 15: Remote Access is disabled,
skip to Prompt 18: "Supervision."
17
Keypad Address
(28)_
X
[01-30]
This address must be programmed if using either
the Remote Access feature or Direct Wire
downloading.
NOTES:
1. This address must be programmed as an alpha
keypad in the control panel (Device Programming
Mode). If using Remote Access, the keypad must
also be enabled as an AUI (advanced user
interface) keypad. DO NOT connect an actual
keypad (or any other device) assigned to this
address.
2. This address must be unique from the "Device
Address" entered in Prompt 14, and cannot equal
that device address plus 1 (one) if using 2-4204
mode.
18
Supervision
(24 Hours)_
X
X
•
30 Day
•
24 Hrs
•
None
The AlarmNet network must hear at least one
supervisory message from the communicator during
this supervision period; otherwise, AlarmNet
notifies the central station that a communication
failure has occurred. (If the supervision period is
changed after registration, you must re-register the
communicator.)
Press the [space] key to scroll through choices.
UL/ULC: Must be set to 24 hours.
19
Old Alarm Time
10 Minutes_
X
X
•
10 Min
•
15 Min
•
30 Min
•
1 Hr
•
2 Hrs
•
4 Hrs
•
8 Hrs
•
12 Hrs
•
24 Hrs
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
UL/ULC: Must be set to 10 minutes.
20
GSM Flt Time
(00 mins)_
X
X
[00-99]
[00] = not used
In the event the communicator detects a
communication path failure, enter the time delay (in
minutes) before the communicator notifies the
control panel with a trouble message (and trips the
Fault Output if used (terminal 11); see next
question). The control panel can then notify the
central station.
UL/ULC: Must be one (01) minute.
21
Flt Rel ON Y/N
(N)_
X
X
[Y], [N]
If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a communicator fault.
For conditions that trip the fault relay refer to
Supervision Features
in Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring the Fault Relay
in Section 2.
UL/ULC: Must be set to "Y".
Содержание GSMV4G
Страница 2: ......
Страница 40: ...GSMV4G GSMVCN4G Installation and Setup Guide 4 4 ...
Страница 46: ...GSMV4G GSMVCN4G Installation and Setup Guide 5 6 ...
Страница 47: ...A 1 Appendices Appendix A Summary of LED Operation ...
Страница 48: ...GSMV4G GSMVCN4G Installation and Setup Guide A 2 ...
Страница 50: ...GSMV4G GSMVCN4G Installation and Setup Guide B 2 ...
Страница 52: ...GSMV4G GSMVCN4G Installation and Setup Guide C 2 ...
Страница 53: ...NOTES ...
Страница 54: ...NOTES ...
Страница 55: ...NOTES ...
Страница 56: ...NOTES ...
Страница 57: ...NOTES ...
Страница 58: ...NOTES ...
Страница 59: ...NOTES ...
Страница 60: ...NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...NOTES ...