background image

Zone indicators

The zone indicators are not used on a BS Repeat panel. The
links that disable the zone indicators are located on the bottom
edge of the DKC and must be set to

'Without zone indicators'

position. The links are factory set for EN Repeat panel that is
'With zone indicator', see illustration on the right.

Display selection

"

The rotary switch SW3 is located on the Master

Repeat Card and must be set in the correct position for
the type of display used, factory set to position 4.

SW3

position Panel

0

A2/A3/A4 Mimic Panel only

1

3400 Repeat panel
(having a 4 line display)

2

32000 Repeat panel
(having a 16 line display)

3

Vigilon Repeat panel
(having a 16 line display)

4

Vigilon Repeat panel
(having an 8 line display)

5 to F

Not used

Write protect link

The

write protect link

P4 on the Master Repeat Card is factory

set to protected. Normally it is not necessary to change the link
from the factory set position, see the diagram above.

Contrast and Emergency controls

The

display contrast

is set using Pot RV1 on the DKC and is

factory set for optimum contrast.
The

emergency control

buttons must always be left in an

enabled state, with the control buttons link fitted.

At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.

Do not dispose of with your normal household waste.
Do not burn.

WEEE Directive:

At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.

P9

L

N

N

P17

DANGER

BT+

BT

-

DANGER
NO NOT
REMOVE

3.15A(T)

mains fuse

L

N

P5

FS2

FS4

P2

P1

SW3

01 L1 02 L2

LC

P16

WRITE PROTECT

P8

P4

RESET

0C

+

RS485

0V 24V

-

BUZZER
DISABLE

PB2

WD1

P14

P7
USB

FS3

2A(QB)

SW3

Write Protected
(Factory setting)

P4

NOT Write Protected

P4

Buzzer
Disable

Buzzer Not
Disable

P14

P14

SW1

RV1

Sound Alarms

Silence Alarms

Reset

Verify

Control buttons

Inner door

1

2

3

4

17

18

19

20

Zones

With Zone
indicators

For keyswitch
application only.
Link is NOT USED
leave link fitted.

Display and
keyboard Card (DKC)

Without Zone
indicators

P6

P1

Buttons
enabled

Buttons
disabled

Factory setting
is with link fitted

8
7
6
5
4
3
2
1

ON

SW1

RV1

LCD Contrast adjust

OFF

Clockwise -
Darker

Anti-Clockwise -
Lighter

SW1
Leave all
switches
in the OFF
position

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание GENT VIG-RPT-72

Страница 1: ...o 45ºC Relative humidity Non condensing Up to 90 temperature 5 C to 45 C Battery 12V 7Ah sealed lead acid Mains operating voltage 230V 15 10 50 60Hz Rated Current 0 2A Emission BS EN61000 6 3 2001 Immunity BS EN50130 4 1996 Part 4 LVD BS EN 60950 2006 Ingress protection IP31 estimated Colour Door Pantone 422 Back box Graphite Grey RAL 7024 Controls with door closed Access level 1 Next and Previous...

Страница 2: ...o terminal block P9 on the Master Repeat Card fit battery lead supplied in the spares to connector P5 on Master Repeat Card connect the loop cables to terminal block P16 on the Master Repeat Card connect the 40 way ribbon cable to the Master Repeat Card connector P2 and the other end to Display Key Card on the top right edge connector P1 connect the 20 way ribbon cable to the Master Repeat Card co...

Страница 3: ...e Loop COM Master Repeat Card 01 L1 02 L2 0C LC P9 L N N P17 DANGER BT BT RS485 0V 24V WRITE PROTECT BUZZER DISABLE P8 DANGER DO NOT REMOVE L N P5 FS2 FS4 P16 P4 P2 P1 SW3 PB2 WD1 P14 P7 USB FS3 2A QB RESET DANGER WARNING Removal of cover exposes live parts mains electrical supply Loop OUT Previous Next Spur Connection XXXXX Fire Alarm System GENT 2007 Designed to EN54 Pt 2 4 Panel healthy 15 45 1...

Страница 4: ...control buttons must always be left in an enabled state with the control buttons link fitted At the end of their useful life the packaging product and batteries should be disposed of via a suitable recycling centre and in accordance with national or local legislation Do not dispose of with your normal household waste Do not burn WEEE Directive At the end of their useful life the packaging product ...

Страница 5: ...r sounds Cancel the buzzer using the local Cancel buzzer button Test functions When operating the SOUND ALARMS button it will activate the alarm sounders in the system Display test to ensure all LEDs are working Sound Alarms Silence Alarms Display of Fire events Reset Operation of U1 U4 Function keys as configured at the control panel Verify as configured at the control panel 4188 839_issue 7_08 1...

Страница 6: ...configuration of the system To create or change an existing Engineer PIN You will need to be at Access level 3 if an Engineer PIN is already set up Press the Menu On Off button and select Test Eng UserCode then momentarily press etc to select Config New Pass and then type a new PIN or change an existing PIN and press the Enter key will appear if a PIN is already setup It is recommended that the PI...

Страница 7: ...ith Mk4 MRC Menu map Control E C Q Key E Enter C Cancel Q Quit Verify etc Params 0 3 E C Q Timeslot etc Params 1 16 Delay On Params HH MM SS On E C Q Off Off DelayBlk Params 1 16 Delayed E C Q Params MM SS 0 10min End E C Q Stop Group EN BS EN BS Option for BS Repeat panel only Option for EN Repeat panel only Sector Build Params 1 255 E C Q Aux Rly Params 1 2 E C Q Params 1 32 E C Q Enable Disable...

Страница 8: ... Params 0 100 Signal C Q E Params 16 100 C Q E Params 0 255 Params 1 100 C Q E etc State enable Params 1 8 Params 0 15 C Q E Params 0 15 State disable TimeBlok etc Voice Tone number Set Up Loop Params 1 207 Device It is important to back up the data at the main control panel following any changes using the in Setup menus at the repeat panel Menus accessible with panel door open and AL2 password Ac...

Страница 9: ...8 C Q E N C P R 1 100 Loop Params 1 207 E Params 0 15 Q C E E Params C Q 1 207 Loop Params Fault Disable Exceptions Sub Faults HistFire etc etc Warning Device 1 4 1 32 Params Loop Params 1 255 E C Params Q MCP IO Line Device Device Sector Card etc Params 1 207 C Q E 1 8 Device Params Q E etc Active Historic Events Label UserCode TimeAvg Status etc Loop Map Control Set Up Info Test Eng EN BS Repeat...

Отзывы: