Installation
The Repeat Panel Set consists of:
Parts
Qty
j
Backbox assembly
1
k
Outer door assembly
1
l
Inner door assembly
(with membrane labels for BS panel)
1
m
20 Way ribbon cable
1
n
40 Way ribbon cable
1
Spares pack [Battery lead, Link wire (not used),
1 x 2A Fuse 20mm x 5mm QB,
2 x 3.15A Fuse 20mm x 5mm AB ceramic]
1
Battery 12V 7Ahr
1
Fuses on the Master Repeat Card
Fuse
Rating
FS4
3.15A AS 20mm x 5mm
FS2
3.15A AS 20mm x 5mm
FS3
2A QB 20mm x 5mm
Back box mounting
a
Find the Repeat panel Back box
package and
remove the temporary cover.
b
Secure the back box to the wall with suitable
fixings. If the backbox is to be semi-flushed then
use the optional semi-flush surround.
c
Terminate the cable at the entry point leaving
400mm
tail wire length.
&
If mains supply cable ends are not
required to be connected then ensure the ends are
insulated for safety.
d
Refit the temporary cover to protect the panel
until all building work is complete.
Doors, Cables and Power up
The doors and cables can be installed after the
building work has finished.
a
Remove the protective cover from the backbox.
b
Fit the inner door
to the panel enclosure
remembering to connect the earth lead from the
backbox to the inner door. Fit the outer moulded
door
to the backbox.
c
Wiring the panel:
&
Ensure the mains supply is completely
powered down before wiring the mains cable ends.
•
connect the mains cable to terminal block P9
on the Master Repeat Card.
•
fit battery lead
supplied in the spares to
connector P5 on Master Repeat Card.
•
connect the loop cables to terminal block P16
on the Master Repeat Card.
•
connect the 40 way ribbon cable
to the
Master Repeat Card connector P2 and the
other end to Display Key Card on the top right
edge connector - P1.
•
connect the 20 way ribbon cable
to the
Master Repeat Card connector P1 and the
other end to Display Key Card on the top right
edge connector - P6.
d
Power-up the panel by switching ON the mains
supply and then connect the battery leads to the
battery and note:
•
all the LEDs on the panel are lit for a short
duration and a power up message displayed.
•
the local buzzer sounds
•
the display reads:
Main panel is off Line
•
the
Fault
and
System Fault
LEDs are lit.
Data and installation
Vigilon Repeat panel (EN/BS)
2
4188-839_issue 8_07/14_pt1_EN/BS new Repeat_inst
cL
310mm
115mm
115mm
370mm
285mm
45mm
Floor level
1.65m
Cable entry points
4-off - Back and 4-off - Top
3-off
Earth points
Backbox
Fixing centres
4-off
01 L1 02 L2
0C LC
P9
L
N
N
P17
DANGER
BT+
BT
-
+
RS485
0V 24V
-
WRITE PROTECT
BUZZER
DISABLE
P8
DANGER
DO NOT
REMOVE
L
N
P5
FS2
FS4
P16
P4
P2
P1
SW3
PB2
WD1
P14
P7
USB
FS3
2A(QB)
RESET
DANGER
WARNING
Removal of
cover exposes
live parts.
Repeat Panel
Cross section of the wall to which
the panel is to be semi-flush mounted
Aperture
Flush
Surround
5mm diameter
fixing holes
Aperture Height:
380mm
Aperture Width: 320mm
Aperture depth should
not be less than: 59mm
Repeat panel
semi-flush surround