Channel modes

Unused

This option sets the channel as not used.

Output

This option sets the channel for either relay or LED output. As a relay output it provides a set of normally
open or normally closed contacts. As an LED output it can be set to normally On (lit) or normally Off (not lit)
drive for an LED load.

Supervisory I/P

This option sets the channel as a 'non fire' Supervisory input for general switching. The acceptance of the
input signal can be delayed until it has remained active for a set period of time.

"

Settings for Supervisory, Fault and Fire inputs are similar.

Fault I/P

This option sets the channel as a fault input. The acceptance of the input signal can be delayed until it has
remained active for a set period of time.

Fire I/P

This option sets the channel as a fire input. The acceptance of the input signal can be delayed until it has
remained active for a set period of time.

Commissioning information

Interfaces (Low voltage)

2

4188-873.02_Pt.2_04/07_DRAFT6_S4 LV Interfaces

A delay duration after which the input is accepted,

for example to account for input switch

contact bounce.

The input can be either be a normally
open or normally closed input.

Содержание GENT S4-34410

Страница 1: ...4 interface modules can be mounted in other equipment housings using the DIN rail mount brackets S4 34491 A module can also be fitted into a plastic box S4 34490 or metal box S4 34492 The boxes have cable termination points on the enclosure for incoming cables 4188 873_issue 4_Pt 1_02 09_S4 LV Interfaces 1 Data and Installation Interface Modules for Vigilon Low voltage LV Input Output by Honeywell...

Страница 2: ...odule can be configured to provide any combination of up to four inputs or outputs An output of either normally open or normally closed relay contacts can be used to control a load of up to 1A 30Vdc ac Optionally an output can be configured to provide 1 5mA at 24V dc to drive an LED that can be normally On or normally Off An input can be programmed as a fire fault supervisory or confirmation input...

Страница 3: ...inimum with End of line capacitor Can be configured as LED output The cable screens must be connected to an on the chassis or in the metal box If a module is mounted on a then the DIN rail must electrically connected to the earth terminal DIN rail loop cable screen via the earth terminal EOL 10K 10K 121110 9 8 7 6 5 4 3 2 1 Confirmation Input Optional NC COM NO Output Relay contact rating 1A 30V a...

Страница 4: ...nfirmation input is not seen within predefined period of the output action Confirmation function is not a feature of the single input module Output mode A relay output of either NO or NC set of contacts rated 1A 30Vac dc resistive load A relay output of change over contacts NC COM and NO rated 1A 30Vac dc resistive load LED output 1 5mA at 24Vdc Normally On or Normally Off Load Factor 1 4 switch i...

Страница 5: ...ck the LV icon on the tool bar 2 Select the required interface to be configured from the list box 3 Ensure the Number of keyswitches option is set to 0 because this feature is for future use Ensure only the applicable channel is configured when configuring the S4 34415 or S4 34420 type interfaces 4 Select a mode from the drop down menu All applicable channels must be set see next page for details ...

Страница 6: ...ctive for a set period of time Settings for Supervisory Fault and Fire inputs are similar Fault I P This option sets the channel as a fault input The acceptance of the input signal can be delayed until it has remained active for a set period of time Fire I P This option sets the channel as a fire input The acceptance of the input signal can be delayed until it has remained active for a set period ...

Страница 7: ...output will operate within 1s of the input being accepted design must also allow for any input delay settings 4188 873 02_Pt 2_04 07_DRAFT6_S4 LV Interfaces 3 Interfaces Low voltage Commissioning information The associated channel cannot be the same channel as the channel Input Confirmation O P 8 7 6 5 Ch 2 Ch 2 Confirmation Output External equipment Ch 1 Input Ch 1 4 I O Interface module External...

Страница 8: ...allows the fire alarm system to monitor external equipment Keyswitch mode This feature is a future option Commissioning information Interfaces Low voltage Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1...

Отзывы: