Maximum cable usage per circuit

&

Cable usage per circuit of:

£

Zone circuit - 100 metres maximum.

£

Clean contact Input circuit - 300 metres maximum

£

LED output - 30 metres maximum

£

Relay output - unlimited.

End-of-line (EOL) devices

¨

An input circuit require in series with the contacts
a 10K resistor plus a 10K EOL resistor (supplied).

¨

A zone input circuit is monitored with an EOL
capacitor unit (supplied).

Zone input functionality

A zone input can have conventional detectors and
manual call points (MCPs) connected. All MCPs must
have a 470 Ohms or 3V9 zener diode in series with
normally open contacts. The zone input can take a
maximum load of up to 2mA at 24V nominal (with
minimum operating voltage of 18V). The zone circuit
must be terminated with an EOL capacitor unit.

Confirmation Input / Output functionality

An input and an output of a module can be paired to
operate in a confirmation mode. External equipment
can send an acknowledgement upon receiving a
signal from the module, this is called 'confirmation
input'. External equipment can also receive an
acknowledgement from the module upon sending it a
signal, this is called 'confirmation output'.

S4 1-Input Interface

The single input interface module monitors a circuit of
either normally open or closed contacts. The input
can be programmed as a fire, fault, supervisory or
confirmation input. Optionally it is also possible to
configure the input for a zone of conventional
detectors and MCPs. In all input modes the interface
will detect short and open circuit faults.

S4 4-Input /Output Interface

The quad input/output interface module can be
configured to provide any combination of up to four
inputs or outputs. An output of either normally open
or normally closed relay contacts can be used to
control a load of up to 1A @ 30Vdc/ac. Optionally an
output can be configured to provide 1.5mA at 24V dc
to drive an LED that can be normally On or normally
Off. An input can be programmed as a fire, fault,
supervisory or confirmation input. Additionally it is
possible for channel 1 to be used as a Zone input,
which allow connection of conventional detectors and
MCPs to this module. Zone input can be configured
to have alarm validation feature and configurable
reset time. The alarm validation feature can be used

to minimise false alarms by suppressing a fire input
for a period of time defined during commissioning.
The zone reset period can be extended to allow for
different types of fire detectors.

Configure the links to the required mode.

S4 1-Output & 1-Input Interface

This interface module can be used to control a
resistive load of up to 1A @ 30Vdc/ac via a set of
single pole change over contacts, see wiring
diagrams. In addition there is an input to allow the
monitoring of the external equipment. In this
application the input must be configured as a
confirmation input. A confirmation input generates a
fault if a change of state is not seen within the
predefined period of a specific output.

Configuration

"

Use the Commissioning Tool

Version 1.21 or greater to commission these
interface modules.

Data and Installation

Interfaces (Low voltage)

2

4188-873_issue 4_Pt.1_02/09_S4 LV Interfaces

Removable
terminal blocks

Light pipe

Other
modes

Confirmation
Input
Zone input
Switch input
LED Output
modes

Relay Output
mode
(factory settings)

Link Configurations

Channel

4

Channel

2

Channel

3

Channel

1

Содержание GENT S4-34410

Страница 1: ...4 interface modules can be mounted in other equipment housings using the DIN rail mount brackets S4 34491 A module can also be fitted into a plastic box S4 34490 or metal box S4 34492 The boxes have cable termination points on the enclosure for incoming cables 4188 873_issue 4_Pt 1_02 09_S4 LV Interfaces 1 Data and Installation Interface Modules for Vigilon Low voltage LV Input Output by Honeywell...

Страница 2: ...odule can be configured to provide any combination of up to four inputs or outputs An output of either normally open or normally closed relay contacts can be used to control a load of up to 1A 30Vdc ac Optionally an output can be configured to provide 1 5mA at 24V dc to drive an LED that can be normally On or normally Off An input can be programmed as a fire fault supervisory or confirmation input...

Страница 3: ...inimum with End of line capacitor Can be configured as LED output The cable screens must be connected to an on the chassis or in the metal box If a module is mounted on a then the DIN rail must electrically connected to the earth terminal DIN rail loop cable screen via the earth terminal EOL 10K 10K 121110 9 8 7 6 5 4 3 2 1 Confirmation Input Optional NC COM NO Output Relay contact rating 1A 30V a...

Страница 4: ...nfirmation input is not seen within predefined period of the output action Confirmation function is not a feature of the single input module Output mode A relay output of either NO or NC set of contacts rated 1A 30Vac dc resistive load A relay output of change over contacts NC COM and NO rated 1A 30Vac dc resistive load LED output 1 5mA at 24Vdc Normally On or Normally Off Load Factor 1 4 switch i...

Страница 5: ...ck the LV icon on the tool bar 2 Select the required interface to be configured from the list box 3 Ensure the Number of keyswitches option is set to 0 because this feature is for future use Ensure only the applicable channel is configured when configuring the S4 34415 or S4 34420 type interfaces 4 Select a mode from the drop down menu All applicable channels must be set see next page for details ...

Страница 6: ...ctive for a set period of time Settings for Supervisory Fault and Fire inputs are similar Fault I P This option sets the channel as a fault input The acceptance of the input signal can be delayed until it has remained active for a set period of time Fire I P This option sets the channel as a fire input The acceptance of the input signal can be delayed until it has remained active for a set period ...

Страница 7: ...output will operate within 1s of the input being accepted design must also allow for any input delay settings 4188 873 02_Pt 2_04 07_DRAFT6_S4 LV Interfaces 3 Interfaces Low voltage Commissioning information The associated channel cannot be the same channel as the channel Input Confirmation O P 8 7 6 5 Ch 2 Ch 2 Confirmation Output External equipment Ch 1 Input Ch 1 4 I O Interface module External...

Страница 8: ...allows the fire alarm system to monitor external equipment Keyswitch mode This feature is a future option Commissioning information Interfaces Low voltage Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1...

Отзывы: