This leaflet covers commissioning information for:

¨

S4-34410 1-Input Interface Module

¨

S4-34420 1-Output & 1-Input Interface Module

¨

S4-34450 4-Input/Output Interface Module

Full Compatibility

The S4 Interface modules are

fully

compatible for

use in Vigilon and 34000 systems where the panel
is fitted with MCC/MCB and LPC cards having the
following firmware:

¨

MCC/MCB - version 3.94 / 4.37

¨

LPC - version 3.93 / 4.35

For further information on upgrade requirements
contact Gent by Honeywell.

Links on S4-34450

Configuration

The S4 interface modules can only be configured
with Commissioning tool software version 1.21.

The commissioning tool version 1.21 has a new
icon and menu option to allow configuration of the
S4 I/O Interface Modules.

1)

Click

Configuration

on the menu bar and

select

LV Interface

or alternatively click the

LV

icon on the tool bar.

2)

Select the required interface to be configured
from the list box.

3)

Ensure the 'Number of keyswitches' option is
set to

'0'

, because this feature is for future use.

"

Ensure only the applicable channel is

configured when configuring the S4-34415 or S4-34420
type interfaces.

4)

Select a mode from the drop down menu. All
applicable channels must be set, see next
page for details.

5)

If required check the sectored box.

6)

Configure other LV interface modules and
save the configuration.

4188-873.02_Pt.2_04/07_DRAFT6_S4 LV Interfaces

1

Commissioning information

Interface Modules for Vigilon

Low Voltage (LV) Input/Output

by Honeywell

1a

LV interfaces..

Configuration

1b

1

Menu selection

Icon selection

3

2

Unused
Output
Confirmation O/P
Confirmation I/P
Supervisory I/P
Fault I/P

Zone I/P

4

Removable
terminal blocks

Light pipe

Other
modes

Confirmation
Input
Zone input
Switch input
LED Output
modes

Relay Output
mode
(factory settings)

Link Configurations

Channel

4

Channel

2

Channel

3

Channel

1

Содержание GENT S4-34410

Страница 1: ...4 interface modules can be mounted in other equipment housings using the DIN rail mount brackets S4 34491 A module can also be fitted into a plastic box S4 34490 or metal box S4 34492 The boxes have cable termination points on the enclosure for incoming cables 4188 873_issue 4_Pt 1_02 09_S4 LV Interfaces 1 Data and Installation Interface Modules for Vigilon Low voltage LV Input Output by Honeywell...

Страница 2: ...odule can be configured to provide any combination of up to four inputs or outputs An output of either normally open or normally closed relay contacts can be used to control a load of up to 1A 30Vdc ac Optionally an output can be configured to provide 1 5mA at 24V dc to drive an LED that can be normally On or normally Off An input can be programmed as a fire fault supervisory or confirmation input...

Страница 3: ...inimum with End of line capacitor Can be configured as LED output The cable screens must be connected to an on the chassis or in the metal box If a module is mounted on a then the DIN rail must electrically connected to the earth terminal DIN rail loop cable screen via the earth terminal EOL 10K 10K 121110 9 8 7 6 5 4 3 2 1 Confirmation Input Optional NC COM NO Output Relay contact rating 1A 30V a...

Страница 4: ...nfirmation input is not seen within predefined period of the output action Confirmation function is not a feature of the single input module Output mode A relay output of either NO or NC set of contacts rated 1A 30Vac dc resistive load A relay output of change over contacts NC COM and NO rated 1A 30Vac dc resistive load LED output 1 5mA at 24Vdc Normally On or Normally Off Load Factor 1 4 switch i...

Страница 5: ...ck the LV icon on the tool bar 2 Select the required interface to be configured from the list box 3 Ensure the Number of keyswitches option is set to 0 because this feature is for future use Ensure only the applicable channel is configured when configuring the S4 34415 or S4 34420 type interfaces 4 Select a mode from the drop down menu All applicable channels must be set see next page for details ...

Страница 6: ...ctive for a set period of time Settings for Supervisory Fault and Fire inputs are similar Fault I P This option sets the channel as a fault input The acceptance of the input signal can be delayed until it has remained active for a set period of time Fire I P This option sets the channel as a fire input The acceptance of the input signal can be delayed until it has remained active for a set period ...

Страница 7: ...output will operate within 1s of the input being accepted design must also allow for any input delay settings 4188 873 02_Pt 2_04 07_DRAFT6_S4 LV Interfaces 3 Interfaces Low voltage Commissioning information The associated channel cannot be the same channel as the channel Input Confirmation O P 8 7 6 5 Ch 2 Ch 2 Confirmation Output External equipment Ch 1 Input Ch 1 4 I O Interface module External...

Страница 8: ...allows the fire alarm system to monitor external equipment Keyswitch mode This feature is a future option Commissioning information Interfaces Low voltage Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1...