How to setup zone for 'Immediate Cause and Effect'
Using this form you can assign immediate zone action on sectors, master alarms and fire relay. You will need to be at access level 3 or above to setup immediate cause and effect.
How to setup zone for 'Delayed Cause and Effect'
Using this form you can assign delayed zone action on sectors, master alarms and fire relay. You will need to be at access level 3 or above to setup delayed cause and effect.
Commissioning instructions
46
4188-949 issue 3_05/10_Nano Comms inst.
How
to
setup
zone
for
'Immediate
C
ause
and
E
ffect'
10:15 Tue 16/02/10
Zone [ 1] Immediate C&E Setup
Sector 01-08 :
[N][N][N][N][N][N][N][N]
Sector 09-16 :
[N][N][N][N][N][N][N][N]
(N=NO ACTION, A=ALERT, E=EVACUATE)
Master Alarms [NO]
Fire Relay [NO]
Save
Quit
Set the Zone’s ‘Immediate Cause and Effect’
action on Sectors to:
‘N’ - NO ACTION (factory default setting)
‘A’ - ALERT
or
‘E’ - EVACUATE
Set the Zone’s ‘Immediate Cause and Effect
action, if required, on ‘Master Alarms’ and
‘Fire Relay’ to - NO (factory default setting)
or YES
Select a ‘Zone’ from a range 1 to 16
Save
Select
Zones
>
Select
Select
Immediate
C&E
Select
Settings
Menu
To scroll range
To move to
next setting
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
10:15 Tue 16/02/10
Zone [ 1] Delayed C&E Setup
Sector 01-08 :
[E][E][E][E][E][E][E][E]
Sector 09-16 :
[E][E][E][E][E][E][E][E]
(N=NO ACTION, A=ALERT, E=EVACUATE)
Master Alarms [YES]
Fire Relay [YES]
Save
Quit
For the selected Zone you can view and change
the delayed action on sectors, master alarms
and fire relay.
Select a Zone from a range 1 to 16
Set the Zone’s ‘Delayed Cause and Effect’ action
on ‘Master Alarms’ and ‘`Fire Relay’to
‘NO’or ‘YES’ (Factory default setting)
Save
Set the Zone’s ‘Delayed Cause and Effect’
action on Sectors to ‘N’- NO ACTION,
‘A’ - ALERT or
‘E’- EVACUATE (factory default setting)
Select
Zones
>
Select
Delayed
C&E
Select
Settings
Menu
To scroll range
To move to
next setting
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.