Visual and audible indication of 'Find Device'
Sensors and MCP
¨
A
S-Quad fire sensor
or
manual call point
will operate its LED for 0.5 second
On
and 0.5 second
Off
repeated.
Sounders and S Cubed
¨
Each
S cubed or S-Quad with sounder
device will provide an audible tone and/or visual indication for 0.5 second
On
and 0.5 second
Off
repeated. If the device operates in voice
mode then the pre-tone followed by a full test message will be played.
Interface units
&
Ensure Interface outputs are not connected to external equipment at this stage of commissioning. These must be tested in accordance with project
recommendations.
¨
Each
interface output
will in turn be activated for 0.5 second
On
and 0.5 second
Off,
this will repeat.
How to 'Print' the Loop map
You can print the loop map to a local printer connected to the panel. You will need to be at access level 4.
"
A printout will only print the first 15 characters of a label due to the limit of 40 characters per line on the handheld printer.
4188-949 issue 3_05/10_Nano Comms inst.
27
Nano panel based system
How
to
'Print'
the
Loop
map
10:15 Tue 16/02/10
Warning! Selecting this option will
cause the complete loop map to be
printed out on the serial printer.
ARE YOU SURE YOU WISH TO PROCEED?
Yes
No
Menu
Select
Loop
>
Select
Select
Engineering
Map
Select
Devices 2 and 3 are on a Spur
A ‘
’ after the device number
indicates the device is
SAFE addressed.
+
Select
Addr Prev Next Spur Loc. Label
1
END1
4
2
LOOP Device 1
2
1
3
SPUR Device 2
3
2
O/C
SPUR Device 3
4
1
5
O/C
LOOP Device 4
5
4
6
LOOP Device 5
6
5
END2
LOOP Device 6
Typical printout