LCD-SLP Product Installation Document —
P/N LS10045-000GF-E:E 12/16/2019
3
2.4 Circuit Ratings and Specifications
Table 2.4.1 lists the LCD-SLP circuit ratings and specifications.
2.5 LCD-SLP Installation
1. Remove the unit from its static-shield bag, observing proper static protection measures.
2. Visually inspect the unit for damage.
If any components are damaged, notify the shipping carrier immediately. Report missing components to the Gamewell-FCI
Customer Service.
3. Use the Hardware Kit provided with the unit.
4. The LCD-SLP is installed in the S3 Series, SLP-BB cabinet and E3 Series cabinets.
To determine the installation that you require, refer to the following documents and Section 2.6 thru Section 2.8.
– S3 Series (Small Addressable Fire Alarm Control Panel), UL Listing Document, P/N: LS10005-051GF-E
Specifications
LCD-SLP
Operating Voltage:
+24 VDC
Operating Current:
0.030 A
Alarm Current:
0.065 A
Ground fault test impedance:
Zero Ohms
Impedance values and ground faults are annunciated:
GND Fault LED or LCD-SLP
Relative Humidity:
0 to 93%, non-condensing at 90
°
F (32
°
C)
Operating Temperature:
32
°
to 120
°
F (0
°
to 49
°
C)
Circuit Supervision:
Supervised
Circuit Class 2 Power-Limited:
Table 2.4.1 Circuit Ratings and Specifications
Figure 2.5.1 illustrates the LCD-SLP installed in the S3 Series,
SLP-BB cabinet.
Figure 2.5.1 LCD-SLP Installed in an SLP-BB Cabinet
Figure 2.5.2 illustrates the LCD-SLP installed in the E3 Series,
Cabinet B.
Figure 2.5.2 LCD-SLP Installed in E3 Series Cabinet B