LCD-SLP Product Installation Document —
P/N LS10045-000GF-E:E 12/16/2019
15
Section 5: LCD-SLP Releasing Application
The LCD-SLP display panel includes optional audio/visual signaling capabilities for the E3 Series Releasing application. The E3
Releasing application contains an RS-485 circuit to support the connection of up to fifteen LCD-SLP displays. The following five
LEDs can be configured to appear on the LCD-SLP display panel to signal the stages of the E3 Series Releasing process.
When a Releasing event occurs, the persistent text indicator, Release, appears on the LCD-SLP display panel. Figure 5.1 illustrates
the screen that appears when you program in CAMWorks for Releasing applications.
Figure 5.1 LCD-SLP Releasing Touchscreen LEDs and Switches
5.1 LCD-SLP Releasing Panel Operator Interface LED Indicators
In compliance with UL Standard 864, at least one LCD-SLP display panel must be configured in CAMWorks as a Releasing panel
operator interface. Table 5.1.1 lists the switches, LEDs and a description of how the switches and LEDs operate when the LCD-SLP
is configured for Global Reporting as a Releasing panel operator interface.
• Standby
• Pre-Alarm
• Pre-Release
• Release
• Abort
LCD-SLP Releasing Switches
Switches
Description
Standby
Color GREEN: Indicates that the Releasing Zone to which this display belongs is in a normal
condition.
Pre-Alarm
Color RED: Indicates that at least one device in the Releasing Zone went into alarm, but not
enough devices went into alarm to trigger the Pre-Release Timer.
Pre-Release
Color RED: Indicates that a pre-programmed number and the type of initiating devices in the
Releasing Zone have gone into alarm to activate the Pre-Release Timer. After the timer
expires, a release occurs.
Release
Color RED: Indicates that the Pre-Release Timer expired and a release occurred.
Abort
Color YELLOW: Indicates that it is in the Abort state.
Note:
After the LCD-SLP display is assigned to the Releasing Zone, the Releasing Zone Indicators are enabled.
LCD-SLP Releasing LED Indicators
LEDs
Description
Note 1: RELEASING PANEL OPERATOR INTERFACE REQUIREMENT:
For Releasing Applications: In CAMWorks, you must configure at least one LCD-SLP as a Releasing Panel.
Note 2:
Operator Interface, so that the LED1 through LED5 indicators light as follows:
Standby
LED1 turns ON (GREEN) when all nodes in the region/or system are in a Normal Condition.
Pre-Alarm
LED2 turns ON (RED) when any node in the region/or system has any Releasing Zone in
Pre-Alarm condition.
Pre-Release
LED3 turns ON (RED) when any node in the region/or system has any Releasing Zone in
Pre-Release condition.
Release
LE4 turns ON (RED) when any node in the region/or system has any Releasing outputs that
are turned ON.
Abort
LED5 Turns ON (YELLOW) when any node in the region/or system has any Releasing Zone
in the Abort condition.
Table 5.1.1 LCD-SLP Releasing Panel Operator Interface LED Indicators
A C PO W ER
SILEN C ED
M EN U
D R ILL
R ESE T
STANDBY PRE-ALARM P-RELEASE RELEASE ABORT
FIR E A LA R M H A ZA R D SU P ER VISO R Y TR O U B LE