9000-0447 Rev. I
Page 41 of 42
Table 6-1 7100 Series Device Types and Functions
#
Device Type
Physical
Response
Action in Alarm Condition
1 Ion
Sensor
2
Ion Duct Sensor
Ion
3 Photo
Sensor
4
Photo Duct Sensor
5 Photo/Thermal
Photo
Smoke
Alarm
6 Thermal
Thermal
7
8 Smoke
Det
Alarm
9
Manual Station
Manual Alarm
10 Plenum
Det
11 N.O.
Contact
12 Heat
Det
13 SubLoop
14 Waterflow
Silenceable
15 Beam
Det
16 Duct
Det
17 FACP
Alarm
18 Remote
Zone
19 Smoke/Heat
AMM
Alarm
Trips ALARM LED and
ALARM Relay
Trips other outputs per
Day Alarm or Night
Alarm Response, or by
group.
Smoke Alarm may be
verified or PAS;
Manual Alarm may be
PAS.
Alarm condition latches,
trouble condition is
restorable.
20 Supervisory
Switch
(Non Latching)
AMM
Supervisory NL
Alarms and Troubles
restore.
21
Tamper Switch (Latching)
Supervisory L
Trips general supervisory
outputs, SUPERVISORY
LED, TROUBLE Relay.
Alarms latch,
Trouble restore.
22
Waterflow NonSilenceable
AMM
Waterflow NS
Same as ALARM but inhibits panel silence.
23 Non-Reporting
Actuator
Latch
Alarms latch
24
Non-Reporting Actuator
Nonlatch
AMM
25
Non-Reporting Ion Non latch
Ion
26
Non-Reporting Photo Non latch
Photo
Non-Report
Activates group, but
produces no other
response.
Alarms restore
27 Ion
Multilevel Ion
28 Photo
Multilevel Photo
Multilevel
Produces “Alert”, “Action”, or “Alarm” response
depending on global %-of-alarm settings
29 Signal
Silence
Silence
30 Reset
Reset
31 Drill
Fire
Drill
32
Alarm Acknowledge
Alrm Ack
33
Trouble/Supv Acknowledge
Trbl/Supv Ack
34 Aux
AMM
Aux
Non-latching
Produces the specified function
35
End-Of-Line
AMM
EOL
Used for address M99 only
36 Silenceable
Signal
37 Nonsilenceable
Signal
Signal
AOM
Produces “Short” indication
38 Silenceable
Contacts
39 Nonsilenceable
Contacts
Form C
AOM
(Output)
No “Short” indication
40
49
User-Defined Device Types
AMM
Choice of Alarm,
Supervisory NL,
Tamper L,
Waterflow NS
Per selected response