9000-0447 Rev. I
Page 33 of 42
[CONFG] 0:Options 1:Line1 2:Line2
[DACT ] 3:Account1 4:Account 2
0: Opens DACT Options Menu.
1: Opens Phone Line Options Menu for Line 1.
2: Opens Phone Line Options Menu for Line 2.
3: Opens Account Options Menu for Account 1.
Main
Config
DACT
(opens only if DACT is installed)
4: Opens Account Options Menu for Account 2.
[ACCTn] 1: Format
2: Reporting
[OPTS ] 3: AccountID
4: CIC & Phone#
1: Opens Communications Format Menu Account n.
2: Opens Reporting Options Menu for Account n.
3: Opens Account ID Menu for Account n.
Main
Config
DACT
Account
Options
4: Opens Account CIC / Phone Number Menu for Account n.
[
ACCTn ] 1:Alarms (Must) 2:Test (Can)
[REPRT] 3: Trbl (Can) 3:Spvsry (Off)
1: Selects reporting option for Alarms [Off, Can, Must].
2: Selects reporting option for Test [Off, Can, Must].
3: Selects reporting option for Troubles [Off, Can, Must].
Main
Config
DACT
Account
Options
Reporting
Options
4: Selects reporting option for Supervisory [Off, Can, Must].
[ACCTn] 000000
[ID # ] Type all 6 digits (leading 0s)
# keys: enters account ID number for account n.
BKSP, <,> not operational.
Main
Config
DACT
Account
Options
Account
ID
Options
Note: all 6 digits must be entered, with leading zeroes if necessary.
[ACCTn ] CIC:SSSSSSSS #:SSSSSSSSSSSSSSSS
[CIC, #] Type digits, BKSP/EDIT,
# keys: enters CIC (dialing prefix) or phone number for account n.
<,>: moves backward or forward through numbers.
BKSP: Scrolls through special characters S (no digit), *, #, comma
(2 sec. Pause), and @ (dial Tone Select) without advancing cursor.
When desired character appears, press “>” to advance.
Main
Config
DACT
Account
Options
CIC
Number
- and -
Phone Number
Note: Cursor is on first digit of phone # when menu opens.
[LINEn] 1: Dialing Mode (0)
[OPTS ] 2: Line Monitor (ON)
1: Scrolls through Dialing Mode options for Line n [0…4]
0=USA Tone or rotary (40/60), 1=USA Rotary only, 2=Tone only,
3=Tone or European Rotary (33/67), 4=European Rotary only.
2: Toggles Line Monitoring ON/OFF for Line n.
Main
Config
DACT
Line
Options
Note: periodic line test is enabled when either line’s Line Monitor
setting is 1.
[ACCTn] 1:Format (0)
[FORMT]
Main
Config
DACT
Account
Options
Comm
Format
1: Scrolls through communication format options for Account n
[0…6]
0=SIA DCS 8, 1=SIA DCS 20, 2=Ademco Contact ID, 3=4/2
1400 Hz, 4=3/1 1400 HZ, 5=3/1 2300 HZ, 6=4/2 2300 HZ
[DACT] 1: DACT (OFF) :FirstTest 00:00 Config
[OPTS] 2:ACDelay (10) 3:Tests/day (1)
1: Toggles DACT operation ON/OFF.
2: Toggles AC Fault reporting delay (0, 10, 20 hours).
3. Scrolls through number of lines tests per day [1…4].
Main
Config
DACT
Account
Options
Comm
Format
<,>: Scrolls First Line Test Time setting (15-minute steps).