![Honeywell Gamewell 7100 Series Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/honeywell/gamewell-7100-series/gamewell-7100-series_installation-and-operating-manual_153484037.webp)
9000-0447 Rev. I
Page 31 of 42
[SELECT] Loop, Address: 1,001
[DEVICE] Key in or use <,>
# keys: enters SLC & address (restriction: Address 200)
<>: Scrolls up or down to next available device.
Main
Config
Inputs
or
Outputs
_______________or_________
Main
I/O
Control
or
Ena/Dis
OK: Accepts address, opens Configure Input Device Menu,
Configure Output Device Menu, Control Output Menu, or
Enable/Disable Device Menu, as appropriate.
[CONFIG] 1: Type 2: Group 3: Verify 4: Sens
[L, AAA] 5: Location 6: View 7: Copy L, AAA
1: Opens Set Input Type Menu.
2: Opens Assign Input To Group Menu.
3: Opens Set Verify/PAS Function Menu (sensors only).
4: Opens Set Sensitivity Menu (Ion, Photo devices only).
5: Opens Set SLC Device Location Menu.
6: Displays all settings for current device.
Main
Config
Inputs
Select
7: Copies all settings of the specified device (last input modified)
[L, AAA] Ion Duct Det
01 (Alarm)
[TYPE ] ^ Key in Input Type # or use <,>
Main
Config
Inputs
Select
Type
<>: scroll through types which match this physical device.
# keys: enter type number (no restrictions; see Type Table)
Shows type and associated Response.
BKSP/EDIT: If selected device type is editable, or if it is not editable
but there is room to create a new user-editable type, opens Add
Type menu (Menu 35). ^indicates that editing is possible.
[L,AAA] Group 007
(00=no group)
[GROUP] Key in Group# or use <,>
Inputs
Select
Group
No restrictions on group assignment.
[L,AAA] 1: Verification (Default)
Input
Select
Verify
Options are: Default, None, Smoke Verify (Ion/Photo only), PAS
[L,AAA] 1: Day Sensitivity (Default)
[SENS ] 2: Night Sensitivity (Default)
1: Scrolls through Day Sensitivity options.
2: Scrolls through Night Sensitivity options.
Inputs
Select
Sens
Options vary by type, may include: Default, 1.00%, …2.00%
[L,AAA] Ion Duct Det
FLR2 Storeroom
Alarm Grp23 Vfy:Default 1.75%
Inputs
Select
View
Shows: SLC and Address, Device Type, Location Label, Device
Response, and I/O Group. Shows Verify/PAS settings and day
sensitivity setting if applicable (if device is set for default sensitivity,
shows default day sensitivity). No changes can be made.