31
Section 9
Quick Reference Guide
Problem
LED
Things to Check
Active Alarm
Solution
Unit running in AUTO but no
power in house.
GREEN
Check MLCB.
NONE
Check MLCB if the MLCB is in the ON position. If it is in
the ON position contact the servicing dealer.
Unit shuts down during
operation.
RED
Check the LED’s / Screen for
alarms.
HIGH TEMPERATURE
Check ventilation around the generator, intake, exhaust
and rear of generator. If no obstruction contact serving
dealer.
Unit shuts down during
operation.
RED
Check the LED’s / Screen for
alarms.
OVERLOAD REMOVE
LOAD
Clear alarm and remove household loads from the
generator. Put back in AUTO and restart.
Unit was running and shuts
down, attempts to restart.
RED
check the LED’s / Screen for
alarms.
RPM SENSE LOSS
Clear alarm and remove household loads from the
generator. Put back in AUTO and restart. It may be a fuel
issue so contact the servicing dealer.
Unit will not start in AUTO with
utility loss.
NONE
See if screen says unit not
activated.
NOT ACTIVATED
Refer to activation section in owners manual.
Unit will not start in AUTO with
utility loss.
GREEN
Check screen for start delay
countdown.
None
If the start up delay is greater than expected, contact
servicing dealer to adjust from 2 to 1500 seconds.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
LOW OIL PRESSURE
Check Oil Level / Add Oil Per Owners Manual. If oil level
is correct contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
RPM SENSE LOSS
Clear alarm. Check the battery using the control panel
under the MAIN menu using the BATTERY MENU
option. If it states battery is GOOD contact servicing
dealer. If it states CHECK BATTERY replace the battery.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
OVERCRANK
Check fuel line shutoff valve is in the ON position. Clear
alarm. Attempt to start the unit in MANUAL. If it does not
start or starts and runs rough, contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
LOW VOLTS REMOVE
LOAD
Clear alarm and remove household loads from the
generator. Put back in AUTO and restart.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
FUSE PROBLEM
Check the 7.5 Amp fuse. If it is bad replace it with an
ATO 7.5 Amp fuse, if not contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
OVERSPEED
Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
UNDERVOLTAGE
Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
UNDERSPEED
Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
STEPPER
OVERCURRENT
Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
MISWIRE
Contact servicing dealer.
Unit will not start in AUTO with
utility loss.
RED
Check the LED’s / Screen for
alarms.
OVERVOLTAGE
Contact servicing dealer.
Yellow LED illuminated in any
state.
YELLOW
Check the screen for
additional information.
LOW BATTERY
Clear alarm. Check the battery using the control panel
under the MAIN menu using the BATTERY MENU
option. If it states battery is GOOD contact servicing
dealer. If it states CHECK BATTERY replace the battery.
Yellow LED illuminated in any
state.
YELLOW
Check the screen for
additional information.
BATTERY PROBLEM
Contact servicing dealer.
Yellow LED illuminated in any
state.
YELLOW
Check the screen for
additional information.
CHARGER WARNING
Contact servicing dealer
Yellow LED illuminated in any
state.
YELLOW
Check the screen for
additional information.
SERVICE A
Perform SERVICE A maintenance, hit ENTER to clear.
Yellow LED illuminated in any
state.
YELLOW
Check the screen for
additional information.
SERVICE B
Perform SERVICE B maintenance, hit ENTER to clear.
Yellow LED illuminated in any
state.
YELLOW
Check the screen for
additional information.
Inspect Battery
Inspect Battery, hit ENTER to clear.
Содержание G0062610
Страница 35: ...33 Section 11 Notes ...
Страница 38: ...36 Section 13 Installation Diagram 13 1 INSTALLATION DRAWING 0J9945 D ...