10
Section 3
Site Selection and Preparation
3.1 SITE SELECTION
NOTE:
The generator can be placed under decks or structures as long as all clearances are met and local building codes are followed.
18 in (457 mm)
Minimum Distance
36 in
(914 mm)
36 in
(914 mm)
36 in
(914 mm)
60 in (1524 mm)
60 in (1524 mm)
Existing Wall
No operable windows or openings in the wall permitted
within 5 ft (1.52 m) from any point of the generator.
Top of Generator
60 in (1524 mm)
Minimum
60 in (1524 mm)
Recommended
Minimum From Ends
18 in
(457 mm)
Minimum
Generator
Clearance from operable
windows, doors or any
openings in the wall.
Clearance from the ends and front of the generator
must be 36 in (914 mm). This would include shrubs,
bushes or trees. Clearance at the top should be a
minimum of 60 in (1524 mm) from any structure,
overhang or projections from the wall. The generator
should not be placed under a deck or other structure
that is closed in and would limit or constrain air flow.
NOTE:
Removable fence panels for servicing cannot be
placed less than 18 in (457 mm) in front of the
generator.
These guidelines are based upon fire
testing of the generator enclosure and
the manufacturer’s requirement for air
flow for proper operation. Local codes
may be different and more restrictive
than what is described here.
Figure 3.1 – Installation Guidelines