System test
02
0
Back
Done
Next
To begin, press and hold the
▲
and
▼
buttons
until the display changes (about 3 seconds)
Press
▲
or
▼
to check system status
Press
NEXT
to advance to next test
Press
DONE
to terminate system test
02
04
10
20
30
40
70
Wireless test
Return air sensor
Heating system
Emergency
heating system
Cooling system
Fan system
Thermostat
information
(for reference only)
0
Off
1
Test radio signal (after a brief pause, screen displays 1-10
to show signal strength; 5 or higher recommended)
Screen displays return air temperature if device is installed
and working properly (EIM only)
0
Heat and fan turn off
1
Heat turns on
2
Stage 2 heat turns on
3
Stage 3 heat turns on
0
Heat and fan turn off
1
Heat and fan turn on
0
Compressor and fan turn off
1
Compressor and fan turn on
2
Stage 2 compressor turns on
0
Fan turns off
1
Fan turns on
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System Test
System Status
Follow the procedure below to test for proper operation.
System test
number
System
status
CAUTION: EQUIPMENT DAMAGE HAZARD.
Compressor protection (minimum off time)
is bypassed during testing. To prevent equipment damage, avoid cycling the compressor
quickly.