background image

ROME Series Installation Document —

 P/N 53530:B  9/14/2009

3

Mounting an Optional Second Relay Module in the ROME Series

„

ANN-MBRLY Mounting Bracket Installation

An optional second Relay Module can be mounted inside the ROME Series using the ANN-MBRLY mounting bracket.  
Two holes must be drilled in the enclosure to secure the ANN-MBRLY as described in the following steps:

1. Place the ANN-MBRLY mounting bracket flat against the inside back wall of the ROME Series, while positioning 

two oblong holes over the mounting studs as shown in the following illustration.

2. Make a mark on the ROME Series back wall using the two holes that will be used to secure the ANN-MBRLY as a 

guide.

3. Remove the ANN-MBRLY from the ROME Series and drill two 3/32” (dia. 0.093”) holes in the locations marked in 

step 2.  Note that these holes will be used to secure the ANN-MBRLY using the two supplied self-tapping screws.

4. Place the ANN-MBRLY mounting bracket oblong holes in position over the mounting studs and install the two 

supplied nuts, but do not tighten at this time.

5. Install the two supplied self-tapping screws in the locations indicated and secure the ANN-MBRLY to the ROME 

Series using the holes drilled in step 3.

6. Tighten the two nuts installed in step 4.

self-tapping screw

oblong mounting hole

mounting stud 
(with nut)

drill 3/32” (dia. 0.093”) 
hole in ROME Series for 
self-tapping screw

    

ANN-MBRLY 

Mounting Bracket

self-tapping screw

oblong mounting hole

mounting stud 
(with nut)

drill 3/32” (dia. 0.093”) 
hole in ROME Series for 
self-tapping screw

  

 ROME Series

Содержание Fire-lite ROME Series

Страница 1: ...more detailed programming information refer to the appro priate FACP installation manual Relay Module Specifications Relay Designations and Terminals The relay numbers and terminal designations are illustrated in the following illustration Operating Voltage 24 VDC Max Current 24 VDC Alarm 75 mA Standby 15 mA Operating Temperature 32 to 120 F 0 to 49 C Max Wiring Distance from FACP with 12 AWG wire...

Страница 2: ...e in appropriate FACP manual for wire gauge and distance limitations Setting Relay Module DIP Switches Each ANN BUS device requires a unique address Relay Module DIP switch SW1 is used to set the address for the mod ule A maximum of 8 devices can be connected to the FACP ANN BUS communication circuit ANN BUS device addresses do not need to be sequential and can be set to any number between 01 and ...

Страница 3: ...s a guide 3 Remove the ANN MBRLY from the ROME Series and drill two 3 32 dia 0 093 holes in the locations marked in step 2 Note that these holes will be used to secure the ANN MBRLY using the two supplied self tapping screws 4 Place the ANN MBRLY mounting bracket oblong holes in position over the mounting studs and install the two supplied nuts but do not tighten at this time 5 Install the two sup...

Страница 4: ...odule on the ANN MBRLY mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket 2 Secure the Relay Module to the ANN MBRLY mounting bracket with the four supplied screws 3 Set the SW1 DIP switches and connect the wiring as described in the previous sections mounting hole mounting hole mounting hole mounting hole ROME Series Optional Relay Modul...

Страница 5: ...KT as a guide 3 Remove the MULTIMOD BRKT from the ROME Series and drill two 3 32 dia 0 093 holes in the locations marked in step 2 Note that these holes will be used to secure the MULTIMOD BRKT using the two supplied self tapping screws 4 Place the MULTIMOD BRKT mounting bracket oblong holes in position over the mounting studs and install the two supplied nuts but do not tighten at this time 5 Ins...

Страница 6: ... and flat against the bracket as illustrated below 8 Install the addressable Multi Module on the MULTIMOD BRKT mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket 9 Secure the addressable Multi Module to the MULTIMOD BRKT bracket with the four supplied mounting screws as illustrated below standoff standoff standoff standoff mounting screw ...

Отзывы: