background image

6

ROME Series Installation Document —

 P/N 53530:B  9/14/2009

7. Install the supplied module insulating pad on the MULTIMOD-BRKT bracket by aligning the four outer holes with 

the four standoffs on the bracket and pressing the pad onto the standoffs and flat against the bracket as illustrated 
below.

8. Install the addressable Multi-Module on the MULTIMOD-BRKT mounting bracket by positioning the four module 

mounting holes over the four standoffs on the mounting bracket.

9. Secure the addressable Multi-Module to the MULTIMOD-BRKT bracket with the four supplied mounting screws as 

illustrated below.

  

            

standoff

standoff

standoff

standoff

mounting screw

mounting screw

mounting screw

mounting screw

Содержание Fire-lite ROME Series

Страница 1: ...more detailed programming information refer to the appro priate FACP installation manual Relay Module Specifications Relay Designations and Terminals The relay numbers and terminal designations are illustrated in the following illustration Operating Voltage 24 VDC Max Current 24 VDC Alarm 75 mA Standby 15 mA Operating Temperature 32 to 120 F 0 to 49 C Max Wiring Distance from FACP with 12 AWG wire...

Страница 2: ...e in appropriate FACP manual for wire gauge and distance limitations Setting Relay Module DIP Switches Each ANN BUS device requires a unique address Relay Module DIP switch SW1 is used to set the address for the mod ule A maximum of 8 devices can be connected to the FACP ANN BUS communication circuit ANN BUS device addresses do not need to be sequential and can be set to any number between 01 and ...

Страница 3: ...s a guide 3 Remove the ANN MBRLY from the ROME Series and drill two 3 32 dia 0 093 holes in the locations marked in step 2 Note that these holes will be used to secure the ANN MBRLY using the two supplied self tapping screws 4 Place the ANN MBRLY mounting bracket oblong holes in position over the mounting studs and install the two supplied nuts but do not tighten at this time 5 Install the two sup...

Страница 4: ...odule on the ANN MBRLY mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket 2 Secure the Relay Module to the ANN MBRLY mounting bracket with the four supplied screws 3 Set the SW1 DIP switches and connect the wiring as described in the previous sections mounting hole mounting hole mounting hole mounting hole ROME Series Optional Relay Modul...

Страница 5: ...KT as a guide 3 Remove the MULTIMOD BRKT from the ROME Series and drill two 3 32 dia 0 093 holes in the locations marked in step 2 Note that these holes will be used to secure the MULTIMOD BRKT using the two supplied self tapping screws 4 Place the MULTIMOD BRKT mounting bracket oblong holes in position over the mounting studs and install the two supplied nuts but do not tighten at this time 5 Ins...

Страница 6: ... and flat against the bracket as illustrated below 8 Install the addressable Multi Module on the MULTIMOD BRKT mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket 9 Secure the addressable Multi Module to the MULTIMOD BRKT bracket with the four supplied mounting screws as illustrated below standoff standoff standoff standoff mounting screw ...