Honeywell FIRE-LITE ALARMS TS540/1 Скачать руководство пользователя страница 4

2. 

Press  the  “c”  key  followed  by  the  ENTER.    You  will  be  asked  for  the  gateway  IP 
address.  Insert the value indicated for the parameter and then press ENTER.   

 

OK

  should  now  appear  on  the  PC  display  which  will  then  show  the  list  of 

parameters that appear in option c) the value that has just been entered. 

3. 

Press 

d

  followed  by  the 

ENTER 

key.

 

  You  will  be  asked  for  the  client  subscriber 

number.  Enter the value indicated for the parameter and then press 

ENTER

.  

OK

 

should  now  appear  on  the  PC  display  which  will  then  show  the  list  of  parameters 
that appear in option 

d)

 the value that has just been entered. 

4. 

Press 

e

  followed  by  the 

ENTER

  key.    You  will  be  asked  for  the  VisorALARM 

receiver  IP  address.    Enter  the  value  indicated  for  the  parameter  and  then  press 

ENTER

.  

OK

 should now appear on the PC display which will then show the list of 

parameters that appear in option 

e)

 the value that has just been entered. 

5. 

Press 

h

  followed  by  the 

ENTER

  key.    You  will  be  asked  for  the  VisorALARM 

receiver  UDP  port.    Enter  the  value  indicated  for  the  parameter  and  then  press 

ENTER

.  

OK

 should now appear on the PC display which will then show the list of 

parameters that appear in option 

h)

 the value that has just been entered. 

6. 

Press 

j

 followed by the 

ENTER

 key to reboot the device so these changes activate.  

You  will  be  asked  for  a  password.    Enter 

24680

,  which  is  the  default  factory 

password value.  After a few second, the IPDACT will reboot. 

7. 

After rebooting, you will be asked for a password.  Enter 

24680

 again and the initial 

menu will appear in the PC display. 

8. 

Type 

c

 and 

ENTER

 to access the 

Quick Install

 menu once more. 

9. 

Type 

i

 and 

ENTER

 so the IPDACT register procedure in the VisorALARM receiver 

is carried out.  You will be asked for a password.  Enter the installer password you 
have  been  given  and  press 

ENTER

.    The 

OK

  message  should  appear  after  a 

maximum of a few seconds and the IPDACT must then switch the relays and light 
up the LED located next to these.  This indicates that the IPDACT is active and  has 
correct connectivity with the VisorALARM receiver. 

10. 

Should  any  problem  occur,  an 

ERROR

  message  will  appear  instead  of  the  OK.  

This will be followed by a number which indicates the following: 

a. 

Error on answer

: Received data incorrect. Try again. If the error 

persists contact the technical service. 

b. 

VA  unreachable

:  There  is  a  problem  in  the  local  network.  The 

network  cable  may  be  disconnected  or  the  IP  address  for  the 
IPDACT or gateway is incorrectly configured. 

c. 

No  answer

:  There  is  a  problem  in  the  connection  with  the 

VisorALARM. This possibly is a problem in the client’s connection 
to Internet, Internet or the network on the central side. 

 

 

Содержание FIRE-LITE ALARMS TS540/1

Страница 1: ...c IP address always the same or a dynamic IP address could be different every time a connection is made are possible 2 Checklist a IPDACT console access password default is 24680 b Installer password required to execute the register command c IP address subnet mask and gateway for IPDACT 2 d IPDACT account number or client number e IP address and UDP Port number of the VisorALARM central station 1...

Страница 2: ...e Alarm Panel or other electric supply This should be 24 VDC from Fire Alarm Panel Ethernet Network RJ45 To a broadband modem router or a network switch hub for internet access 4 IPDACT Default Configuration Through a short circuit in the IPDACT P2 jumper during the start up process you can configure the IPDACT with the default factory settings The process for this is as follows 1 switch off the I...

Страница 3: ...by pressing c and then ENTER The menu displayed in the second figure will be presented All the parameters to install the device are found in this menu The steps to complete the installation are as follows 1 If in the LAN network where the IPDACT is installed you have address assignment through DHCP go to step 3 If this is not the case carry out the following steps I Press the b key followed by ENT...

Страница 4: ...lowed by the ENTER key to reboot the device so these changes activate You will be asked for a password Enter 24680 which is the default factory password value After a few second the IPDACT will reboot 7 After rebooting you will be asked for a password Enter 24680 again and the initial menu will appear in the PC display 8 Type c and ENTER to access the Quick Install menu once more 9 Type i and ENTE...