3. Physical Connections
FROM AP
PHONE
PSTN
TO AP
OUT NC
OUT NO
INPUT
TAMPER
GND+12/24V
RJ45
ETHERNET
Female JACK
1K EOLR
Connect to the
+24VDC
Nonresetable
Power Supply
Connect to
custormer’s supplied
network equipment
(Cat 5 cable)
MALE PLUG
CONNECTOR
RJ-31, PRIMARY FIRE
PANEL PHONE LINE
NON RST
POWER
NOTE: Connections to
the TO AP terminal
are interchangeable
IPDACT
Connects to…
TO AP
To the PRIMARY FIRE PANEL PHONE LINE.
The connections to the TO AP terminal are interchangeable.
INPUT
Connect the supplied 1K resistor
GND / +24V
To the 24 VDC power supply from the Fire Alarm Panel (or other
electric supply) This should be 24 VDC from Fire Alarm Panel
Ethernet Network
(RJ45)
To a broadband modem/router or a network switch/hub for internet
access.
4. IPDACT Default Configuration
Through a short circuit in the IPDACT P2 jumper during the start up process, you can
configure the IPDACT with the default factory settings. The process for this is as follows:
1)
switch off the IPDACT
2)
short circuit the jumper with the supplied berg header,
3)
switch on the device,
4)
maintain the jumper short circuited during the first A-D LEDs burst (the LEDs
turn on and off) and undo the short circuit during the second burst.
If the process has executed successfully, the IPDACT will display a third burst indicating the
default configuration has been activated.