5. Serial Port Programming 

In  order  to  use  the  serial  port,  you  need  to  connect  the  cable  designed  to  this  end  which 
must  be  obtained  either  from  Firelite  or  from  an  authorized  distributor.    The  following 
figures show the cable and the connection mode to the IPDACT. 
 

  

 

 
Connect the serial cable to the IPDACT as shown above, the other end to a PC serial port 
and  use  a  terminal  emulation  program  (Windows  HyperTerminal  for  example)  configuring 
the serial port to 9600 bps, 8 data bits, 1 stop bit, without parity and no flow control.  When 
you connect the terminal emulation program, you will be asked for a password.  The factory 
default value is 

24680.  

Enter this and the following menu will appear. 

 
 
 
 
This  deals  with  an  options  menu  where 
each  option  is  represented  by  a  letter 
preceding the title.  Each option accesses 
a  submenu  or  contains  a  parameter 
value.  To select an option, enter the letter 
representing this and press 

ENTER

For  device  installation,  access  the 

Quick 

Install

  menu  by  pressing 

c

  and  then 

ENTER

.    The  menu  displayed  in  the 

second  figure  will  be  presented.    All  the 
parameters to install the device are found 
in  this  menu.    The  steps  to  complete  the 
installation are as follows: 
 
 
 
 

 

1. 

If in the LAN network where the IPDACT is installed, you have address assignment 
through DHCP, go to step 3.  If this is not the case, carry out the following steps: 

I.  Press  the  “b”  key  followed  by 

ENTER

.    You  will  be  asked  for  the  IP 

address.  Enter the IP address you have been given and press 

ENTER

II.  You  are  now  asked  for  the  mask.    Enter  the  IP  mask  you  have  been 

given and press 

ENTER

III. 

OK

 should now appear on the PC display which will then show the list of 

parameters  that  appear  in  option 

b)

  the  parameters  that  have  just  been 

entered. 

Password Accepted 
 
     - Main Menu - 
 
  Configuration 
    a) Generic MIP config 
    b) Transmission Parameters 
    c) Quick Install 
 
  Monitoring 
    d) General Info 
    e) Remote Monitor 
    f) Events 
    g) IP Connectivity 
 
    z) Exit 
 
     option: c 
 
OK 
 
  -- Quick Install -- 
 a) DHCP client: ON 
 b) IP addr: 192.168.0.100 mask: 255.255.255.0 
 c) Gateway IP: 192.168.0.200 
 d) Account Number: 0 
 e) Supervisory Main: 
 f) Supervisory Backup: 
 g) Maintenance: 
 h) Port: 80 
 i) Register MIP 
 j) Reset 
 k) AutoRegister MIP 
 
 z) Exit 

Содержание FIRE-LITE ALARMS TS540/1

Страница 1: ...c IP address always the same or a dynamic IP address could be different every time a connection is made are possible 2 Checklist a IPDACT console access password default is 24680 b Installer password required to execute the register command c IP address subnet mask and gateway for IPDACT 2 d IPDACT account number or client number e IP address and UDP Port number of the VisorALARM central station 1...

Страница 2: ...e Alarm Panel or other electric supply This should be 24 VDC from Fire Alarm Panel Ethernet Network RJ45 To a broadband modem router or a network switch hub for internet access 4 IPDACT Default Configuration Through a short circuit in the IPDACT P2 jumper during the start up process you can configure the IPDACT with the default factory settings The process for this is as follows 1 switch off the I...

Страница 3: ...by pressing c and then ENTER The menu displayed in the second figure will be presented All the parameters to install the device are found in this menu The steps to complete the installation are as follows 1 If in the LAN network where the IPDACT is installed you have address assignment through DHCP go to step 3 If this is not the case carry out the following steps I Press the b key followed by ENT...

Страница 4: ...lowed by the ENTER key to reboot the device so these changes activate You will be asked for a password Enter 24680 which is the default factory password value After a few second the IPDACT will reboot 7 After rebooting you will be asked for a password Enter 24680 again and the initial menu will appear in the PC display 8 Type c and ENTER to access the Quick Install menu once more 9 Type i and ENTE...

Отзывы: