ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
61
Master Programming Level
Programming
Pre-signal
To enable the Pre-signal feature, press
1
while viewing Edit Monitor Screen #3 until the display reads
Pre-signal
Yes
. Each press of the
1
key will cause the display to toggle between
Pre-signal Yes
and
Pre-signal No
. Refer
to“Presignal” on page 109 for additional information.
Wireless
The Wireless selection will update automatically if the system recognizes a wireless device. If the module is
wireless, the display reads
Wireless Yes
. If the module is wired, the display will read
Wireless No
. Fore more
information on the SWIFT wireless network,
refer to the SWIFT manual
, #LS10036-000FL-E.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the
control panel after each device activation. To enable devices, which are connected to a monitor module, for the
Walktest feature, press
1
while viewing the Edit Monitor Screen #4 until the display reads
Walktest Yes
. Each
press of the
1
key will cause the display to toggle between
Walktest Yes
and
Walktest No
. Refer to “Walktest” on
page 110 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing
2
while viewing Edit Monitor Screen #4 dis-
plays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first
0
to the left. Enter the three digit number corresponding to the zone that is to be
assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones can be
left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module
currently being programmed. Pressing
1
while viewing Edit Monitor Screen #5 will cause the following screen
to be displayed:
Pressing
1
while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note
that the keypad
down
arrow key must be pressed to see all the Adjective screens. Press the number correspond-
ing to the adjective that is to be used as a descriptor for the location of the monitor module currently being pro-
grammed.
EDIT MONITOR
1=PRE-SIGNAL NO
WIRELESS NO
Edit Monitor Screen #3
EDIT MONITOR
1=PRE-SIGNAL NO
WIRELESS NO
Edit Monitor Screen #3
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
000
444
444
444
444
Edit Monitor Screen #4
Zone Assignment Screen
ZONE ASSIGNMENT
Z000
Z
444
Z
444
Z
444
Z
444
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
4444444444444444
Edit Monitor Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
44444444444444444444
1=NORTH
2=SOUTH
3=EAST
Adjective Screen #1
44444444444444444444
1=WEST
2=FRONT
3=CENTER
Adjective Screen #3
44444444444444444444
1=REAR
2=UPPER
3=LOWER
Adjective Screen #5
44444444444444444444
1=MAIN
2=FIRST
3=2ND
Adjective Screen #7
44444444444444444444
1=3RD
2=4TH
3=5TH
Adjective Screen #2
44444444444444444444
1=FLOOR 4
2=FLOOR 5
3=ROOM
Adjective Screen #6
44444444444444444444
1=FLOOR 1
2=FLOOR 2
3=FLOOR 3
Adjective Screen #4