Honeywell Fire-Lite Alarms ES-50X Скачать руководство пользователя страница 27

ES-50X Series Manual —

 P/N LS10129-000FL-E:D  4/26/2021

27

Remote Synchronization Output

Installation

2.5  Remote Synchronization Output

Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly 
the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential 

hazard to individuals. Devices connected directly to the control panel’s NACs can be synchronized as described in “Type” on page 74.
Notification appliances connected to FCPS NAC power supplies require synchronization with the FACP’s devices. This can be accom-
plished by connecting the Remote Synchronization Output from TB8 of the ES-50X to the sync input of the FCPS-24FS6/8 Power Supply. 

The 24 VDC signal from TB8 follows, that is mimics, the signal on NAC1. This allows the devices connected to the power supply to be syn-
chronized with the devices connected to NAC1 on the FACP.
The Remote Synchronization Output is power-limited and supervised (refer to “UL Power-limited Wiring Requirements” on page 28) and 
can be wired in Class B or Class A. A 4.7 K

Ω

 ELR resistor must be connected to the end of the wiring at the remote power supply for Class 

B wiring. Supervision of the remote synchronization is automatically enabled when the remote sync output is enabled. Supervision will be 
disabled if the output is disabled. For more information on enabling the remote sync output, refer to page 101.        

RTN- OUT-

RTN+

OUT+

C

NO

NC

SUPV

RMT SYNC

NAC1

Figure 2.9  Remote Sync Output

Remote 
Power 
Supply

FACP main 
circuit board

Remote Sync Output

Sync Input

4.7 K

Ω

 ELR

e

s2

0

0s

yn

c.

w

m

f

Optional Class A Return

Содержание Fire-Lite Alarms ES-50X

Страница 1: ...Addressable Fire Alarm Control Panel ES 50X ES 50XC Document LS10129 000FL E Rev D 4 26 2021 ECN 151696 ...

Страница 2: ...eaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire protection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms use...

Страница 3: ...ng or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal This syste...

Страница 4: ...formation Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed manual Brief description of content you think should be improved or corrected Your suggestion for how to correct improve documentation Send email messages to FireSystems TechPubs honeywell com Please note this email address is for documentation feedback only If ...

Страница 5: ...nterface Module 18 ANN I O LED Driver Module 18 ANN LED Annunciator Module 18 ANN RLY Annunciator Module 18 1 7 Getting Started 19 1 8 Telephone Requirements and Warnings 19 1 8 1 Telephone Circuitry 19 1 8 2 Telephone Company Rights and Warnings 19 1 8 3 For Canadian Applications 20 Section 2 Installation 21 2 1 Mounting the Backbox 21 2 2 Power 24 2 2 1 AC Power and Earth Ground Connection 24 2 ...

Страница 6: ...rpose Zone 66 Zones Installed 66 Zones Enabled 66 Zones Disabled 67 Zone Type 67 Zones Available 67 3 5 4 Loop Setup 68 Class 68 Loop Protocol 68 Device Addressing 68 3 5 5 System Setup 68 Function Keys 69 Banner 69 Time Date 70 Timers 71 NACS Notification Appliance Circuits 73 Relays 76 Canadian Option 77 Waterflow Silenceable 77 Auxiliary Power 77 Trouble Reminder 78 Language 78 Charger Enable 7...

Страница 7: ...ration 108 4 12 Programmed Zone Operation 108 4 13 Disable Enable Operation 108 4 14 Waterflow Circuits Operation 108 4 15 Detector Functions 108 4 16 Time Functions Real Time Clock 108 4 17 Synchronized NAC Operation 108 4 18 Coded Operation 109 4 19 Presignal 109 4 20 Positive Alarm Sequence 109 4 21 Special System Timers 110 4 21 1 Silence Inhibit Timer 110 4 21 2 Autosilence Timer 110 4 21 3 T...

Страница 8: ...urrent Load 125 9 4 Calculating the Battery Size 127 9 4 1 NFPA Battery Requirements 127 9 4 2 Selecting and Locating Batteries 127 Appendix A Software Zones 128 A 1 Correlations 128 Appendix B Default Programming 133 Appendix C NFPA Standard Specific Requirements 134 C 1 MBT 1 Municipal Box Trip Silenceable 137 Appendix D Wire Requirements 138 D 1 NAC Wiring 139 Appendix E HVAC Control 140 E 1 Co...

Страница 9: ...ontrol Units for Fire Alarm Systems This Class A digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe A est conforme à la norme NMB 003 du Canada Other Canadian Electrical Code Part I EIA 232E Serial Interface Standard EIA 485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applica...

Страница 10: ... Power Limited Special application 2 5 amps max per circuit ELRs 4 7K 1 2W for Class B wiring Auxiliary Trouble Input CAUTION HIGH VOLTAGE AC Power Supervised Nonpower Limited 120 or 240 VAC 50 60 Hz 3 25 amps Battery 24 VDC supervised nonpower limited 18 AH maximum USB Port J20 for firmware updates local programming using a personal computer and FS Tools utility or a thumb drive To disable ground...

Страница 11: ... 50888 ANN BUS TB9 TB10 SLC Loop TB12 Battery Connector J15 es50annperi wmf ANN 80 LCD Text Annunciator Doc 52749 ANN I O LED Driver Doc 151416 ANN S PG Printer Driver Doc 151417 CHG 75 Charger Doc 51315 ANN R LED LED Display Doc 53032 ANN RLY 10 Form C Relay Card Doc 53033 4XTMF Reverse Polarity Module J12 J13 IPOTS COM POTS and IP Communicator Doc LS10184 000GE E J6 CELL CAB FL GSM Communicator ...

Страница 12: ...e control relay monitor modules totaling 50 50 software zones Two 2 Class B or two 2 Class A NAC Notification Appliance Circuits circuits special application power 3 0 amps total 24 VDC output circuit current in alarm condition Four programmable function keys for ease of maintenance Two programmable relay outputs and one fixed trouble relay Synchronization output for remote power supply applicatio...

Страница 13: ...e is 40 ohms Supervised and power limited circuit Refer to SLC Wiring manual for wiring information Notification Appliance Circuits Special Application Auxiliary Power TB4 TB5 Two 2 Class B NAC circuits or two 2 Class A circuits Special Application filtered power Power limited circuitry NAC wiring requirements refer to NAC Wiring on page 139 Nominal operating voltage 24 VDC Current limit fuseless ...

Страница 14: ...will turn off to conserve batteries Key Panel Mounted on the main circuit board the key panel includes a window for the LCD display and LED indicators as listed below The key panel which is visible with the cabinet door closed has 30 keys including a 16 key alpha numeric pad similar to a telephone keypad TB5 TB8 TB11 Figure 1 1 Current Availability powerdistes50 wmf Refer to the battery calculatio...

Страница 15: ... network It also allows remote programming or interrogation of the control panel using the FS Tools Upload Download utility and a hard wired ethernet IP connection Any personal computer with Windows 7 or greater 32 or 64 bit and FS Tools software may serve as a Service Terminal This allows download of the entire program or upload of the entire program history file walktest data cur rent status and...

Страница 16: ... for a list of compatible addressable modules Refer to the Device Compatibility Document for a list of approved conventional notification and initiating devices 1 4 3 Addressable Device Accessories End of Line Resistor Assembly The End of Line resistors are included with each module Refer to the specific module documentation for specific information Power Supervision Relay The UL listed End of Lin...

Страница 17: ...ES 50X FACP The FACP battery charger must be disabled through user programming when using the CHG 75 The charger and up to 26 AH batteries can be housed in the BB 26 battery box Larger batteries and the charger can be housed in the BB 55F battery box which can be mounted up to 20 feet away from the control panel Refer to the CHG 75 Manual for additional information CHG 120F Battery Charger The CHG...

Страница 18: ...wire RS 485 serial interface employing the ANN BUS communication format The devices are powered via two additional wires from either the host FACP or remote UL listed filtered regulated power supply The function buttons keyswitch and piezo sounder may be individually enabled and disabled through the FACP software Refer to ANN 80 100 Options on page 95 for a description of this feature and programm...

Страница 19: ...h and ahead of all other equipment attached to the same telephone line If there are any questions concerning these instructions consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment Refer to CELL MOD C CELL CAB FL on page 30 for an illustration of the proper installation of this equipment Important The DACT must not be used to dial a pho...

Страница 20: ...r to this equipment or equipment malfunctions may give the telecommunications company cause to request the user to disconnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metallic water pipe system if present are connected together This precaution may be particularly important in rural areas CAUT...

Страница 21: ...2 2 on page 22 2 Install center top fastener in the wall with the screw head protruding 3 Place backbox over the top screw level and secure 4 Mark and drill the left and right upper and lower mounting holes Note Outer holes closest to sidewall are used for 16 O C stud mounting 5 Install remaining fasteners and tighten 6 When the location is dry and free of construction dust install the chassis cir...

Страница 22: ...igure 2 2 ES 50X Cabinet Mounting 9050udencl wmf Semi Flush Mounting Do not recess box more than 3 875 into wall to avoid covering venting holes on top of box Hinge Slot for optional Dress Panel Hinge Slot for optional Dress Panel Semi flush mounting hole Mounting slots for optional Trim Ring ...

Страница 23: ...Mounting the Backbox Installation An optional Trim Ring P N TR CE is also available for semi flush mount installations 6 537 16 6cm 5 207 13 23cm 16 822 42 73 cm 19 26 48 92 cm Figure 2 3 Cabinet Dimensions Height Depth Width Left Side Right Side Top Bottom ...

Страница 24: ...cing the panel s susceptibility to transients generated by lightning and electrostatic discharge Apply AC power to the panel only after the system is completely installed and visually checked Note that AC power must be applied to the panel before installing the battery interconnect cable refer to the following section 2 2 2 Battery Power The batteries must be sealed lead acid type Before connectin...

Страница 25: ...o the Device Compatibility Document for a listing of compatible notification appliances The NACs which are located on the main circuit board may be expanded via the FCPS Series field charger power supplies The following sections describe the configuration and wiring of Class B and Class A Notification Appliance Circuits on the ES 50X main circuit board 24V PWR1 Figure 2 5 Special Application Power...

Страница 26: ... Polarized Horns Polarized Strobes Notification Appliance Circuit polarity shown in alarm state Dummy Load all unused circuit TB5 es50nacy wmf Polarized Strobes circuit number NAC 1 NAC 2 TB4 NAC2 NAC1 2 Class A Notification Appliance Circuits supervised and power limited Polarized Horns Polarized Horns Notification Appliance Circuit polarity shown in alarm state Polarized Bells Polarized Strobes ...

Страница 27: ...S 50X to the sync input of the FCPS 24FS6 8 Power Supply The 24 VDC signal from TB8 follows that is mimics the signal on NAC1 This allows the devices connected to the power supply to be syn chronized with the devices connected to NAC1 on the FACP The Remote Synchronization Output is power limited and supervised refer to UL Power limited Wiring Requirements on page 28 and can be wired in Class B or...

Страница 28: ...rst one installed closest to the backbox A typical wiring diagram for the ES 50X is shown below RTN OUT COMMUNICATOR DISPLAY 24V RTN OUT BATTERY N L2 EARTH H L1 USB A C NO NC C NO NC C NC NO SUPV TRBL ALRM ANN LC SLC RMT SYNC ANN BUS PRI ANN BUS SEC NAC2 NAC1 Figure 2 10 Typical UL Power limited Wiring Requirements Power limited Circuits Class 2 Power limited Circuits Class 2 AC Power Grounding St...

Страница 29: ...ation necessary SW3 2 position dip switch Factory Settings Do not change unless instructed to do so by Honeywell Figure 2 11 Communicator Installation Customer Premises Equipment and Wiring Telephone Line FACP with IPOTS COM mounted internally Network Service Provider s Facilities Network Demarcation Point RJ31X Jack Unused RJ 11 Jack Unused RJ 11 Jack Telephone Telephone Telephone Answering Syste...

Страница 30: ...ng of the monitoring service Local Energy Municipal Box Service NFPA 72 Auxiliary Fire Alarm Systems Supervisory Current 5 0 mA Trip Current 350 mA subtracted from notification appliance power Coil Voltage 3 65 VDC Maximum Coil Resistance 14 6 ohms Maximum allowable wire resistance between panel and trip coil 3 ohms Municipal Box wiring can leave the building Remote Station Service NFPA 72 Remote ...

Страница 31: ...grammed for the factory default settings Alarm Relay 1 Trouble Relay 2 and Supervisory Relay 3 8 When the installation has been complete enable the 4XTMF module by sliding the disconnect switch to the left 9 Test system for proper operation Figure 2 15 4XTMF Transmitter Module Connect to FACP J12 J13 Disconnect Switch shown in disconnect position TBL Jumper Remote Alarm power limited Remote Troubl...

Страница 32: ...Standoff 4XTMF FACP main circuit board es2004xtmf wmf Jumper JS3 NOTE When a 4XTMF is installed enable supervision in panel programming Jumper JS3 on the FACP main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module Relay 3 at TB3 must be programmed as a supervisory relay Jumpering pins 2 3 on JS3 will allow the 4XTMF to generate a trouble if the s...

Страница 33: ...rallel Printer Interface Module The total worst case current is calculated as follows Wiring Configuration Figure 2 17 illustrates the wiring between the FACP s Primary ANN BUS and ANN BUS devices Maximum Resistance Ohms 2 0 Volts Total Worst Case Current Draw amps Maximum Wire Length feet Maximum Resistance Ohms x 500 6 000 feet maximum Rpu where Rpu Ohms per 1 000 feet for various Wire Gauges se...

Страница 34: ...iliary Power Supply Figure 2 19 illustrates the powering of ANN BUS devices from an auxiliary power supply such as the FCPS 24FS6 8 when the total ANN BUS power requirements exceed the panel s DC Power Output capability TB1 4 3 2 1 Figure 2 18 Secondary ANN BUS wiring to ANN BUS Device ANN BUS Device ES 50X ANN BUS and power wiring are supervised and power limited 24 VDC nonresettable Secondary AN...

Страница 35: ...location Installation Ensure that all power AC and DC has been removed from the FACP before installing the annunciator Opening Closing Annunciator The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches refer to figure below 1 Turn the key switch to the ON Unlocked position by turning the key counter clockwise 2 Push in the snap...

Страница 36: ... can be used as a guide to wire the annunciator Make certain all power has been removed from the FACP prior to annun ciator installation 1 Route wires from hole in backplate through wiring channel and then to ANN 80 terminal block TB1 2 Remove appropriate amount of wire insulation 3 Connect the wiring from the FACP ANN BUS to annunciator TB1 terminals 3 A 4 B Make certain to connect A to A and B t...

Страница 37: ... every 10 seconds Note that the FACP will provide no indication of an ANN 80 trouble To clear the ANN 80 trouble condition enable the ANN BUS and program the address corresponding to the address set on the ANN 80 at the FACP ANN 100 Remote Fire Annunciator Specifications Operating Voltage 24 VDC Current Standby 20 mA Alarm 25 mA Ambient Temperature 32 F to 120 F 0 C to 49 C Max Wiring Distance fro...

Страница 38: ...e feature allows the programmer to quickly bring all installed ANN BUS modules online refer to Auto Configure on page 94 5 Connect a printer to the ANN S PG Parallel or Serial connectors refer to Figure 2 21 Only one printer can be connected Specifications Operating Voltage 24 VDC Current Alarm and Standby 45 mA Ambient Temperature 32 F to 120 F 0 C to 49 C Max Wiring Distance from FACP 6 000 ft 1...

Страница 39: ... DB 25 cable One end of the cable will plug into the DB 25 connector on the PRN printer and the other end plugs into the parallel connector on the ANN S PG module Note that the 9 pin DB 9 port on the ANN S PG is used to connect a serial printer The 25 pin port is used for a Centronics parallel printer cable Connect either a serial or parallel printer but not both at the same time Setting Printer O...

Страница 40: ...ecting LEDs and the DIP switch for selecting the ANN BUS ID number Specifications Max ANN BUS Voltage 24 VDC Max Current Alarm 200 mA Standby 35 mA Each LED 10 mA Operating Temperature 32 F to 120 F 0 C to 49 C For indoor use in a dry location only 1 10 11 20 21 30 31 40 LED Out LED Power not used LED Out LED Power not used LED Out LED Power not used LED Out LED Power not used ANN BUS ID Address D...

Страница 41: ... Internal resistors are sized so that there is approximately 10 mA of current for each LED No series resistors are required LED outputs can be mapped to output circuits Refer to the programming section titled ANN I O Options on page 88 of this manual The LEDs are wired as illustrated in Figure 2 24 Note that the illustration depicts only connectors P1 and P2 Wiring is identical for P3 LEDs 21 30 a...

Страница 42: ...nn ioleds2 wmf LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED Power no connection Pin 1 2 3 4 5 6 7 8 9 10 11 12 LED11 LED12 LED13 LED14 LED15 LED16 LED17 LED18 LED19 LED20 LED Power no connection P1 P2 Cathode LEDs Anode Cathode LEDs Anode Pin 1 2 3 4 5 6 7 8 9 10 11 12 Figure 2 25 ANN LEDs shown in possible stacked configuration ann ledstacked wmf ...

Страница 43: ...Refer to the ANN LED Installation Document 53032 for more information ANN LED Board Layout and Connection to FACP Figure 2 27 illustrates the ANN LED board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN BUS ID number Figure 2 26 Exploded View of ANN LED ann led wmf TB1 J1 SW1 JP2 ANN BUS 1 2 3 4 5 6 7 8 Figure 2 27 ANN LED Board Layout an...

Страница 44: ...is or inside the ROME Series enclosure Refer to the ANN RLY Installation Document 53033 for instructions on chassis mounting or to the ROME Series Installation Document 53530 for mounting in the separate backbox mounting holes mounting hooks through mounting slots grounding wire ANN RLY ANN MBRLY mounting bracket mounting holes mounting holes FACP Backbox Installation using ANN MBRLY mounting brac...

Страница 45: ...o ANN BUS Setup on page 87 for programming information Printer Configuration Refer to the documentation supplied with the printer for pertinent information about printer setup Set the printer s options as listed in the following table TB1 J1 SW1 JP2 ANN BUS 1 2 3 4 5 6 7 8 TB6 TB3 TB5 TB4 TB2 Figure 2 29 ANN RLY Board Layout and Connection to FACP ANN RLY Primary ANN BUS 24 VDC 24 VDC ANN BUS and ...

Страница 46: ...formation out to next SLC device Figure 2 30 W GATE SLC Connection es50toWG wmf ES 50X W GATE mounting plate NOTE The W GATE as part of the wireless network has been tested for compliance with the Federal Communications Commission FCC requirements of the United States Government It has not been evaluated for use outside the USA Use of this system outside the USA is subject to local laws and rules ...

Страница 47: ...age 72 Control Module Delay 0 factory default no delay in Control Module activation Control Module Delay 1 180 delays control module activation from 1 180 seconds Control Module Delay 0 for no delay in control module activation Cellular Ethernet Supervision Options Y Refer to Supervision Settings on page 83 and page 84 NFPA 2010 Dual Path Supervision Interval 24 Hours NFPA 2010 Sole Path Supervisi...

Страница 48: ... to Read Status on page 111 for a detailed description of this feature Pressing 2 will select user Programming Mode which may only be accomplished by an authorized person After pressing 2 a screen will prompt for a password After entering the correct password the user may select from a list of programming options Pressing 3 will select FS Tools Up Download which allows the user to enable the remot...

Страница 49: ...llowed to view all option choices 3 4 Programming and Passwords There are two factory set programming passwords which will access the Programming screens as indicated in the following examples From either of the screens access to specific system and device features or programming may be obtained All user programming entries are stored in nonvolatile memory The factory set passwords can be changed ...

Страница 50: ...the following When Autoprogramming is completed the control panel will display the type and quantity of each device installed on the SLC loop similar to the following display In the preceding example the display indicates that the SLC Loop has 55 addressable detectors 35 monitor modules and 30 control modules installed Pressing the ESC key will return the display to Programming Screen 1 3 5 2 Poin...

Страница 51: ...llowing screen will be displayed The programmer can continue adding detectors by pressing the ESC key which will return the display to the Add Detector Screen Delete Detector Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the programmer to delete a specific detector A flashing cursor will appear in the position of the first asterisk to the left The programme...

Страница 52: ...gramming for the displayed detector press the keypad down arrow key to view the Edit Detector screens In the preceding example Normal indicates that the detector with the selected address is physically installed on the SLC and communicating with the control panel enabled ADJ NOUN represents the adjective and noun which have been programmed describing the location of the displayed device ZNNN repre...

Страница 53: ...cation Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and not a false alarm This feature is selected by pressing 3 while viewing the Edit Detector Screen 2 so that the display reads Verification On Each time the 3 key is pressed the display will toggle between Verification On and Verification Off For a detailed description refer to Alarm Verificati...

Страница 54: ...to a control module which may be used to activate a sounder or indicator which the installer designates as a Presignal indication do not use a Notification Appliance Circuit for this purpose To enable the Pre signal fea ture press 3 while viewing Edit Detector Screen 3 until the display reads Pre signal Yes Each press of the 3 key will cause the display to toggle between Pre signal Yes and Pre sig...

Страница 55: ... Control Module Auto Silence timer expires The Fire Coding feature allows the programmer to select the type of output that the sounder base will generate when activated Pressing 3 while viewing Sounder Base Screen 1 will cause the following displays to appear The programmer can select the sounder base output by pressing the number corresponding to the desired output The coding selections are Stead...

Страница 56: ...e control panel using the FS Tools utility These descriptors are selected as described in the previous sections CAUTION VERIFY SOUNDER BASE MODEL NUMBER USE OF THE SOUNDER BASE PROGRAMMING OPTIONS REQUIRES THE USE OF THE B200S SOUNDER BASE WHILE THE B200SR SOUNDER BASE IS COMPATIBLE IT DOES NOT ALLOW FOR SPECIAL PROGRAMMING OPTIONS IF USING THE B200SR SET THE SOUNDER BASE OPTION TO NO IF SET TO YE...

Страница 57: ... the information The display will return to the Edit Detector Screen 5 displaying the new information at the bottom of the screen Module Programming Pressing 2 while viewing Point Program Screen 2 will allow the programmer to add delete or change the pro gramming of an addressable module The following screen will be displayed by the control panel Add Module Pressing 1 while viewing the Modules Scr...

Страница 58: ...s been added to programming and a module such as a monitor module with the selected address is physically installed on the SLC and is communicating with the control panel the following screen will be displayed To change the programming for the displayed module press the keypad down arrow key to view the following Edit Monitor screens In the preceding example Normal indicates that the module with t...

Страница 59: ... previous standard types in the list thus allowing a variety of user defined types and responses To select the type of mon itor module being programmed press the 2 key while viewing the Edit Monitor Screen 2 This will cause the control panel to display the following Monitor Type Screens Pressing the down arrow key will display additional Monitor Type screens While viewing one of the Monitor Type s...

Страница 60: ...rnado Alert 1 General Purpose Signaling latching User Defined 9 same as previous Tornado Alert Phone Active Phone LCD display only User Defined 10 same as previous Phone Tamper Supervisory nonlatching tracking User Defined 11 same as previous Tamper Supervisory Supervisory latching User Defined 12 same as previous Supervisory Supervisory AR 2 2 For entries ending in AR AR refers to AutoResettable ...

Страница 61: ...es to the next Z designation Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00 When all desired changes have been made press the Enter key to store the zone assignments The display will return to the Edit Monitor Screen 4 Noun Adjective The Noun Adjective selection allows the programmer to enter specific descriptors about the monit...

Страница 62: ...s the Enter key to store the information The display will return to the Edit Monitor Screen 4 displaying the new information at the bottom of the screen Edit Module Screen for Control Modules The programmer can change a module s existing or factory default programming by pressing 3 in the Modules Screen The following screen will be displayed A flashing cursor will appear in the position of the fir...

Страница 63: ...isplay to toggle between Silenceable Yes and Silenceable No When set to Canadian mode of operation a third silenceable type appears Silenceable Auto When set to Auto the control module will automatically silence after the Control Module Auto Silence timer expires Walktest The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel...

Страница 64: ...essed to see all the Noun screens Press the number corresponding to the noun that is to be used as a descriptor for the location of the control module currently being programmed Pressing 3 or 4 while viewing the Noun Adjective Screen will display screens similar to the previous Adjective and Noun Screens The new screens will list Custom Adjectives and Nouns which have been programmed into the cont...

Страница 65: ...elay time The control module must first be set to Silenceable No to enable the Delay Timer Wireless The Wireless selection will update automatically if the system recognizes a wireless device If the module is wireless the display reads Wireless Yes If the module is wired the display will read Wireless No 3 5 3 Zone Setup Pressing 3 while viewing Programming Screen 2 will access the Zone Setup scre...

Страница 66: ...046 to activate By assigning Zone 046 to a control module in the Programming Zone Assign ment Screen an output device connected to the control module can be used to indicate a local alarm condition in the control panel Local Alarm Zone alarms are not reported to the Central Station When the panel is set to Canadian mode pressing 2 while viewing the Special Purpose Zone Screen 2 will cause the disp...

Страница 67: ...ype for zone Z002 in the screen illustrated above press 3 The following screens will be displayed To change the zone type for Z002 to Pull Station scroll the display until Zone Type Program Screen 2 is displayed Press 2 to program zone Z002 as a Pull Station zone The display will return to the Zones Installed Screen showing zone Z002 and the Pull Station program type Repeat the procedure for each ...

Страница 68: ...12 hr date and daylight savings time feature into the FACP memory Timers This option allows the programmer to set the PAS Positive Alarm Sequence time delay Pre Signal time delay and Waterflow time delay NACs This feature allows the programmer to configure the control panel Notification Appliance Circuits for a variety of options such as circuit type silenceable nonsilenceable autosilence coding s...

Страница 69: ...ed by function key and No not controlled by function key for each onboard NAC circuit The Remote Synchronization TB8 on the FACP s main circuit board can also be disabled through program ming of a function key To disable remote synchronization press the 3 key while viewing the Function Keys Screen 2 Each press of the key will toggle the screen between Rem Sync Disb Yes and Rem Sync Disb No Banner ...

Страница 70: ...screen will be displayed Time To change the time press 1 while viewing the Time Date Screen The following screen will be displayed A flashing cursor is located toward the top left of the display Below the cursor is the current time To change the time enter the two digit hours followed by the two digit minutes The cursor will move one position to the right each time a digit is entered After the las...

Страница 71: ...fourth week and 5 will select the last week of the selected month Timers Timer delays for PAS Pre signal and waterflow activation can be programmed by pressing 1 while viewing System Setup Screen 2 The following screen will be displayed PAS Positive Alarm Sequence Delay The factory default setting for PAS is 000 for no delay To select a PAS delay of 001 to 180 seconds for all devices programmed fo...

Страница 72: ...oss Delay Screen 1 will display the following A flashing cursor will appear in the lower left corner of the display Type the two digit AC loss reporting delay in hours 00 to 23 hour delay When the second digit is entered the display will return to AC Loss Delay Screen 1 Refer to the table on page 47 for permissible settings Control Module Delay The control module delay feature if enabled will dela...

Страница 73: ...n Canadian mode of operation When enabled this feature will resound all outputs and NACs that were silenced by the In Suite Silence timer if there is an unacknowledged fire alarm on the panel after a programmed length of time Once the Suite Resound Timer occurs additional fire alarms on the system will not restart the In Suite Silence timer Pressing 2 while viewing Timer screen 3 will display the ...

Страница 74: ...e is selected Silence or Autosilence will turn off both audi ble and visual devices Auto Silence The Auto Silence feature when enabled automatically silences all main circuit board silenceable notification appliances after a programmed length of time To enable this feature and program the time delay before Auto Silence activation press 1 while viewing NAC Screen 2 The following screens will be dis...

Страница 75: ...een pressed the Alarm LED will turn from flashing to steady Any NACs currently in 1st stage activation will remain in 1st stage Pressing the Acknowledge switch does not affect NACs already in 2nd stage activation 5 If an F3 button in pressed the NACs will progress to the second stage 6 If another alarm point is activated and the countdown timer is counting the alarm point will have no effect on th...

Страница 76: ...operation there is also a limit to the number of strobes that can be attached to each circuit Relays Pressing 3 while viewing System Setup Screen 2 will allow the programmer to configure two main circuit board Form C relays from the following screen To program Relay 1 or Relay 3 press the number corresponding to the selected relay Note that Relay 2 is fixed as a Trouble relay Selecting Relay 2 wil...

Страница 77: ...atic alarm signal cancel in two stage NAC operation when pressed This prevents the NAC from advancing to the second stage alarm The F3 function key is automatically configured to force active two stage NACs into the second alarm stage If NACs are set up for two stage operation the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes AlarmNet supervision settings are fixed at 3 ...

Страница 78: ...e to 4XTM Supv Enab Yes which means there is a 4XTMF installed Each press of the 2 key will cause the display to toggle between 4XTM Supv Enab No and 4XTM Supv Enab Yes Refer to the table on page 47 for permissible settings Remote Sync Enable Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same ...

Страница 79: ...nes are used to contact central station Pressing 2 while viewing the Communicator Screen 1 will display the following POTS Line X If telephone lines are connected to the IPOTS COM board at J4 Line 1 and J5 Line 2 their settings can be configured by pressing 1 or 2 respectively Pressing 1 or 2 will display the following screen The programming options for Line 1 and Line 2 are identical Phone Line X...

Страница 80: ... viewing the Communicator Screen 1 will display the following DHCP Enabled If the internet router used by the IPOTS COM is configured for DHCP Dynamic Host Configuration Protocol where addresses are auto matically assigned press 1 while viewing the IP Settings Screen to change the display to Enabled Yes Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No If ...

Страница 81: ...ary and Secondary Communication Path screens are used to configure the methods primary and backup for reporting to central station Pressing 1 for Pri or 2 for Sec will display the following screens Note that the following information must be entered for both the Primary and Secondary Communication Paths POTS To configure the communication method to contact central station as a telephone line selec...

Страница 82: ...on or consult our factory representatives For any format chosen the control panel automatically programs all of the event codes Select the Communication Format by pressing the corresponding number key while viewing the Comm Format screen The following table describes each format Test Time Interval The test report sent to the Central Station phone number may be sent once every 1 2 3 4 6 8 12 or 24 ...

Страница 83: ...e used Select Sole Path when only Ethernet or Cellular is used NFPA 2010 Dual Path Supervision Interval 24 Hours NFPA 2010 Sole Path Supervision Interval 5 min NFPA 2013 Dual Path Supervision Interval 6 Hours NFPA 2013 Sole Path Supervision Interval 1 Hour Cellular To configure the communication method to contact central station as a GSM Cellular connection select 3 for Cellular from the Comm Path...

Страница 84: ...efer to the table on page 47 for permissible settings Report Style Pressing 1 while viewing Communicator Screen 3 will cause the Report Style display to toggle between Point and Zone Setting the Report Style to Point will program the Communicator to report individual point status to the Central Station The control panel is capable of monitoring a total of 50 addressable devices Setting the Report ...

Страница 85: ...t ID SIA Active Zone Point Active Restoral PULL STATION 115 Zone Point FA FH MON USER DEF 1 115 Zone Point FA FH WATERFLOW 113 Zone Point SA SH MON USER DEF 2 113 Zone Point SA SH SMOKE PHOTO 111 Zone Point FA FH DET USER DEF 1 111 Zone Point FA FH SMOKE ION 111 Zone Point FA FH DET USER DEF 2 111 Zone Point FA FH HEAT DETECT 114 Zone Point KA KH DET USER DEF 3 114 Zone Point KA KH SMOKE DUCT P 11...

Страница 86: ...ON USER DEF 17 000 Zone Point 00 00 POINT FAULT 380 Zone Point FT FJ POINT DISABLE 570 Zone Point FB FU MANUAL EVACUATION 110 000 000 00 00 AC_FAIL 301 000 000 AT AR DRILL 604 000 000 FI FK SLC 1 SHORT A 372 000 000 ET ER SLC 1 SHORT B 372 000 000 ET ER SLC 1 OPEN A 371 000 000 ET ER SLC 1 OPEN B 371 000 000 ET ER SLC 1 GND FAULT POS 310 000 000 ET ER SLC 1 GND FAULT NEG 310 000 000 ET ER SLC 1 CO...

Страница 87: ... XXX Enabled Yes and ANN XXX Enabled No PRI ANN CLASS A 333 000 000 ET ER REMOTE SYNC DIS 520 000 000 ET ER NAC 1 DISABLE 521 001 001 ET ER NAC 2 DISABLE 522 002 002 ET ER MEMORY FAULT 304 000 000 CHARGER FAULT 300 000 000 YP YQ OPTION CARD 1 FAULT 331 000 000 ET ER REMOTE SYNC FAULT 300 000 000 OU OV ZONE DISABLE 570 000 000 FB FU AUX 1 CLASS A FAULT 300 000 000 YP YQ ANN BUS COMM FAULT 333 000 0...

Страница 88: ...dress information or Zone information Each press of the 1 key will toggle the display between Zone and Point Pressing 1 while viewing the ANN I O Address Screen 3 will select the Point range to be annunciated refer to the tables in ANN I O Zone Option on page 89 and ANN I O Point Option on page 90 If Point has been selected each press of the 2 key for Range will change the points to be annunciated...

Страница 89: ...ne 032 4 Trouble Zone 033 5 Alarm Silenced Zone 034 6 Earth Fault Zone 035 7 Battery Fault Zone 036 8 Charger Fault Zone 037 9 NAC Fault Zone 038 10 Disabled Zone 039 11 Zone 000 Zone 040 12 Zone 001 Zone 041 13 Zone 002 Zone 042 14 Zone 003 Zone 043 15 Zone 004 Zone 044 16 Zone 005 Zone 045 17 Zone 006 Zone 046 18 Zone 007 Zone 047 19 Zone 008 Zone 048 20 Zone 009 Zone 049 21 Zone 010 Not Used 22...

Страница 90: ... 032 Active Alarm 13 Point 003 Active Alarm Point 033 Active Alarm 14 Point 004 Active Alarm Point 034 Active Alarm 15 Point 005 Active Alarm Point 035 Active Alarm 16 Point 006 Active Alarm Point 036 Active Alarm 17 Point 007 Active Alarm Point 037 Active Alarm 18 Point 008 Active Alarm Point 038 Active Alarm 19 Point 009 Active Alarm Point 039 Active Alarm 20 Point 010 Active Alarm Point 040 Act...

Страница 91: ...1 020 021 030 031 040 or 041 050 Five ANN LED modules are required to annunciate all points in this configuration ANN RLED Zone Option Alarm Only If Zone is selected as the module option and the module is programmed to annunciate alarms only the first ten LEDs on the ANN RLED module will display the system status information The remaining 30 LEDs on the first module and the last 30 LEDs on the sec...

Страница 92: ...005 Active Alarm Zone 006 Active Alarm Zone 007 Active Alarm Zone 008 Active Alarm Zone 009 Active Alarm Zone 005 Trouble Zone 006 Trouble Zone 007 Trouble Zone 008 Trouble Zone 009 Trouble Zone 005 Supervisory Zone 006 Supervisory Zone 007 Supervisory Zone 008 Supervisory Zone 009 Supervisory Table 3 6 ANN LED Module 1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Us...

Страница 93: ...m Point 050 Active Alarm Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used First ANN LED Module Point Range 001 010 Alarm Silenced NAC 1 Fault NAC 2 Fault Not Used Not Used Earth Fault Battery Fault Charger Fault Disabled Maintenance Point 001 Active Alarm Point 002 Active Alarm Point 003 Active Alarm Point 004 Active Alarm Point 005 Active Alarm Point 001 T...

Страница 94: ... the device type and address into the system For the Auto Configure to work the selected ANN BUS must be enabled the annunciators must be connected powered and a unique address must be set on each annunciator Pressing 3 while viewing ANN BUS XXX Screen 1 will begin the Auto Config ure process and cause the following screen to be displayed Class A This option applies to the Primary ANN BUS only The...

Страница 95: ... to select whether the piezo sounder on any installed ANN LED module will ever sound Pressing 1 while viewing the ANN LED Options Screen causes the display to toggle between Piezo Enable Yes and Piezo Enable No The Lamp Test Enable LMP TST ENABLE option allows the programmer to select whether the Lamp Test button on any installed ANN LED annunciator will function normally or always be ignored Pres...

Страница 96: ...o toggle between Drl Btn Enable Yes Drill button functions normally and Drl Btn Enable No Drill button never functions In Canadian mode the Drill feature is unavailable The programming option will change to SND BTN ENABLE in Canadian applications Pressing 3 while viewing the ANN 80 100 Options Screen 2 causes the display to toggle between Snd Btn Enable Yes the ANN 100 will perform a test of its l...

Страница 97: ...s other circuits with no input or output correlations Pressing 3 while viewing Programming Screen 4 will cause the following screen to be displayed Pressing 1 while viewing the Program Check Screen will display an NAC screen similar to the following The example above indicates that NAC 1 has been programmed to Zones 005 010 012 015 and 017 but no input devices have been pro grammed to any of these...

Страница 98: ...wn in the following screen 3 6 1 Disable Point Pressing 1 for Point Program while viewing Maintenance Screen 1 will cause the following screens to be dis played Select the device type by pressing 1 for an addressable detector or 2 for an addressable module The operator will be prompted to enter the three digit device address as shown in the following example for a detector A flashing cursor will a...

Страница 99: ...er to view the zones which have been programmed to the Notification Appliance Circuits on the control panel but have not been programmed to Initiating Devices as well as other circuits with no input or output correlations Press ing 1 while viewing Program Check screen will cause a screen similar to the following to be displayed The example above indicates that NAC 1 has been programmed to Zones 00...

Страница 100: ...hange to indicate the latest event All stored events can be scrolled on the screen by pressing the up or down arrow keys To return to the first event press the 1st Event key Pressing 2 for View Points while viewing the Unit In Walktest screen will display one of the following screens If the system has no points installed the first screen will be displayed If points are installed the second screen ...

Страница 101: ...igit day and two digit year The cursor will move one position to the right after each entry When the fourth digit of the year has been entered the display will return to the Time and Date Screen which will show the new date The clock can be configured to display 12 hour AM PM or 24 hour military time Pressing 3 while viewing the Time Date screen will cause the display to toggle between 12HR and 24...

Страница 102: ... to indicate a PAS condition in the control panel Do not assign Zone 047 to a Notification Appliance Circuit when using this zone to indicate a PAS condition Pressing 2 will cause the display to change to Pre signal 48 On Each press of the 2 key will cause the display to toggle between Pre signal 48 On and Pre signal 48 Off When Zone 048 is programmed On a Pre signal activation of any device will ...

Страница 103: ...auses a RESET IN SYSTEM message to be displayed on the LCD and sends the same message to the printer and history file It also per forms a lamp test by turning on all LEDs except the Ground LED piezo sounder and LCD display segments after the Reset key is released Any alarm or trouble that exists after a reset will resound the system 4 1 5 Function Keys F1 F4 The four function keys are user program...

Страница 104: ...ion of a trouble will cause the following The piezo to pulse 1 second On and 1 second Off The system Trouble LED to flash one second On and one second Off The trouble relay to activate TROUBL with device type noun adjective address and trouble description will appear on the LCD display The same message along with the time and date is sent to the optional printer and the history buffer Communicate ...

Страница 105: ...nter and history file If all troubles clear and there are no supervisory or fire conditions active in the system the system returns to normal mode operation and the System Normal message is shown on the LCD display and sent to the history and printer files The auto restore feature will restore cleared troubles even if the troubles were never acknowledged Note that pressing the Alarm Silence key wh...

Страница 106: ...ng a CO alarm condition Device type identifier in this example CAR MONOXIDE indicates a CO detector Second line in display ADJ refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC NOUN refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC Third line in display Z002 in...

Страница 107: ...d to software zones 4 9 Hazard Tornado Condition Operation Hazard Tornado operation is intended for Manual activation Hazard Tornado Condition operation will initiate the following events The piezo sounder pulses 1 4 second On 1 4 second Off The LCD displays a hazard message along with the device name type address adjective noun associated zones and time date Communicate the hazard condition to th...

Страница 108: ...detector is monitored by the control panel for its maintenance status If a detector is near but below the allowed alarm limit a maintenance alert message will automatically be displayed signaling that the detector is in need of servicing Automatic Test Operation An automatic test of an addressable detector is performed each minute resulting in a complete SLC loop test in approximately 5 hours if t...

Страница 109: ...ACs and control modules of associated zones will be inhibited from activating for a user programmed time delay of up to three minutes second alarm occurring anytime during the time delay will cause immediate activation of all associated outputs Presignal does not affect monitor modules programmed as waterflow supervisory process monitoring or remote switches Presignal operation requires the approv...

Страница 110: ...n is automatically reset There will be no alarm indication at the FACP during the Retard period A confirmation period of 60 seconds follows during which a subsequent alarm from the same detector will cause the panel to immediately activate the appropriate outputs and indicate the alarm condition at the FACP If a different detector alarms any time during the first detector s verification period the...

Страница 111: ... change opera tions The alarm relay is not activated 4 23 Read Status Read Status functions do not require a password The control panel will continue to provide fire protection while in Read Status mode This mode can be entered while the control panel is in alarm or trouble If a new alarm or trouble occurs during these functions the Read Status is exited to prevent confusion Read Status Entry When...

Страница 112: ... for detectors and monitor modules Zone Assignments five maximum Chamber Value Adjective Noun descriptor Silenceable Yes No for control modules Wireless Yes No for detectors only Sounder Base Yes No for detectors only Sounder Base Values and Zone Assignments for detectors only 4 23 2 Zones Pressing 2 while viewing Read Status Screen 1 will cause the following screens to be displayed From the prece...

Страница 113: ...Relays Pressing 1 while viewing Read Status Screen 3 will display the following screen The operator can view the programmed option for each relay by pressing the corresponding number key 4 23 7 Program Check Pressing 2 while viewing Read Status Screen 3 will cause a screen similar to the following to be displayed Pressing 1 while viewing Program Check screen 1 will display a screen which will indi...

Страница 114: ... for ANN 80 100 Options while viewing ANN BUS Screen 2 will display the options selected for the installed ANN 80 or ANN 100 annunciators 4 23 10 Communicator Pressing 2 while viewing Read Status Screen 4 will display the following screens The Communicator Screen 1 indicates if an IPOTS COM has been installed Yes or No Pressing 2 for POTS Settings while viewing Communicator Screen 1 will display s...

Страница 115: ...ad Status Screen 5 The following screens will be displayed Pressing 1 while viewing Print Screen 1 allows the user to print the History file which will detail all of the system activities since the file was last cleared from memory Pressing 2 while viewing Print Screen 1 allows the user to print the Walktest log which will detail all of the system activations during walktest since the log was last...

Страница 116: ...o automatically perform the periodic sensitivity measurements required by NFPA Standard 72 The FACP software also provides filters to remove transient noise signals usually caused by electrical interference Maintenance Alert The software determines when the drift compensation for a detector reaches an unacceptable level that can compromise detector perfor mance When a detector reaches an unaccepta...

Страница 117: ...creen 6 indicates whether the onboard battery charger is enabled or disabled 4 23 14 4XTM Supervision Read Status Screen 6 indicates whether 4XTMF Supervision is enabled or disabled 4 23 15 Remote Sync Read Status Screen 6 indicates whether remote synchronization is enabled or disabled READ STATUS 1 FUTURE USE 2 PRINT 3 TIME DATE Read Status Screen 5 DAYLIGHT SAVINGS ENABLED YES START MONTH MAR ST...

Страница 118: ...ine Two phone numbers must be programmed the primary Central Station phone number and the secondary Central Station phone number All system reports will be transmitted to the primary Central Station phone number Reports will automatically be sent to the secondary Central Station phone number if attempts to transmits to the primary Central Station phone number are unsuccessful If 10 total attempts ...

Страница 119: ...1 01 03 7 With software V1 86 8 With software V1 72 9 With DSP4016 and V1 6 Line Card 10 With software V3 9 IMPORTANT It is the installer s responsibility to ensure that the Digital Alarm Communicator Transmitter is compatible with the Central Station Receiver utilized by the monitoring service prior to installation The Compatibility Table provides a list of compatible receivers and associated sof...

Страница 120: ... the main menu screen as shown below Pressing 3 for FS Tools Download while viewing the main menu will cause the following screen to be displayed The FS Tools Download password default 22222222 must be entered to access the FS Tools Download feature Note that the default password can be changed using the Password Change option refer to Password Change on page 96 Entering the correct password will ...

Страница 121: ...g of the secret code is pro hibited at the control panel Prior to allowing an upload or download of data the control panel will verify the secret code transmitted by the Service Terminal Time out at Control Panel Upon answering an incoming call on the primary Central Station phone line the control panel will listen for a modem connection signal If this signal is not received within 50 seconds the ...

Страница 122: ...rd The USB Download option can be selected from the main menu screen as shown below Pressing 4 for USB Up Download while viewing the main menu will cause the following screen to be displayed The USB Upload Download password default 22222222 must be entered to access the USB Upload Download feature Note that the default password can be changed using the Password Change option refer to Password Chan...

Страница 123: ...disable any further downloads to a flash drive Also following 30 minutes of inactivity including up downloading the Accept Download screen will time out causing the display to return to the System Normal screen Important The program database created by the FS Tools programming utility will be called FS_50 cfg on the USB flash drive Before loading the new database into the fire panel the existing d...

Страница 124: ...llowing screen to be displayed Before upgrading any software the panel will give the option to save current programming to a flash drive Press 1 for No to bypass pro gramming backup or press 2 for Yes to save a copy of the current programming to the flash drive The USB thumb drive must be in FAT32 file system format This is typically the default format An error message will display if there is not...

Страница 125: ...e primary AC power is applied The continuous sys tem current load is highest during a fire alarm condition To calculate the fire alarm load on the internal power supply use Calculation Column 1 in Table 9 3 on page 126 The secondary power source batteries must be able to power the system under both standby and fire alarm conditions upon loss of pri mary AC power To calculate the fire alarm load on...

Страница 126: ...lays4 X X X CP350 CP355 maximum alarm draw for all devices 0 200 maximum alarm draw for all devices 0 200 X 0 00030 SD350 SD355 X 0 00030 SD365 X 0 00020 SD355CO X 0 00030 SD365CO X 0 00020 SD350T SD355T X 0 00030 SD365T X 0 00020 AD350 AD355 X 0 00030 AD365 X 0 00020 H350 H355 X 0 00030 H365 X 0 00020 H350R H355R X 0 00030 H365R X 0 00020 H355HT X 0 00030 H365HT X 0 00020 D350P D350PL X 0 00030 D...

Страница 127: ...n board with display only 2 If using the Reverse Polarity Alarm output add 0 005 amps if using the Reverse Polarity Trouble output add another 0 005 amps 3 Refer to the Device Compatibility Document for standby current 4 Must use compatible listed Power Supervision Relay Use the current values listed in the device documentation 5 Maximum alarm current for each sounder base is 0 015 amps which must...

Страница 128: ...ice can be assigned to a maximum of five software zones Each software zone however may have from 1 to 50 addressable input and output devices assigned to it Monitor modules control modules and detectors comprise a group of 50 addresses each device having a unique address from 1 to 50 Be careful not to duplicate addresses between devices Refer to the following page for an example of zoning In the e...

Страница 129: ...s which are shown graphically above are also presented in Table A 1 on page 130 Input Devices Zones Output Devices ZONE 01 ZONE 02 ZONE 03 smoke 01 smoke 02 monitor 03 monitor 04 monitor 05 smoke 15 smoke 16 smoke 22 smoke 24 smoke 25 monitor 30 control 10 control 07 control 13 control 11 control 20 control 21 control 31 control 32 control 06 ...

Страница 130: ... 06 control module 1 07 control module 1 08 09 10 control module 1 11 control module 1 2 3 12 13 control module 1 14 15 smoke detector 2 2ND FLOOR 16 smoke detector 2 ROOM 210 17 18 19 20 control module 2 21 control module 2 22 smoke detector 3 3RD FLOOR 23 24 smoke detector 3 MEZZANINE 25 smoke detector 3 MECH ROOM 26 27 28 29 30 monitor module 3 31 control module 3 32 control module 3 33 34 35 3...

Страница 131: ...ftware Zones ADDRESSABLE DEVICE ZONE ASSIGNMENTS Address Device Type Zone Number ADJ NOUN 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Table A 2 Blank Programming Sheet ...

Страница 132: ...Correlations ADDRESSABLE DEVICE ZONE ASSIGNMENTS Address Device Type Zone Number ADJ NOUN 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Table A 3 Blank Programming Sheet ...

Страница 133: ...ED Secondary Comm Format Ademco Contact ID Trouble Reminder 24 Hr ANN Primary Enabled No Banner ANN Primary Modules Addr 1 8 None Time Format 12 Hr ANN Secondary Enabled No Hours Setting 12 ANN Secondary Modules Addr 1 8 None Minutes Setting 00 ANN S PG Port Serial Second Settings 00 ANN S PG Baud 9600 AM PM Setting AM ANN S PG Data Bits 7 Month Setting 01 ANN S PG Parity Even Day Setting 01 ANN S...

Страница 134: ...tion to the RS82 Remote Station Receiver See Figure C 2 Remote Station Connection Using 4XTMF Module on page 135 for installation instructions for this unit NFPA 72 Auxiliary Fire Alarm System 4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box This unit must be installed as illustrated in the section titled 4XTMF Transmitter Module Installation on page 30 and...

Страница 135: ...Installation on page 30 for detailed information RS82 Remote Station Receiver UL listed Refer to Instruction Manual for Remote Station Receiver Model RS82 Polarity Shown is Normal Standby 4XTMF Transmitter Module Cutting TBL Jumper allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists Power limited Figure C 2 Remote Station Connection Using 4XTMF ...

Страница 136: ...ich will automatically activate on any Trouble condition Form C Alarm contact programmed to activate on General Alarm ES 50X Main Board ES 50X Addressable Fire Control Panel Notes 1 Connection between the ES 50X and the transmitter are supervised by the transmitter 2 This ES 50X Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System 3 Potter Electric Model EFT ...

Страница 137: ...RBL ALRM SLC RMT SYNC ANN BUS PRI ANN BUS SEC NAC2 NAC1 24V FACP Main Circuit Board CMF 300 Control Module 24 VDC Nonresettable SLC Loop B B red black MBT 1 brown wire white wire EOLR 1 Power Supervision Relay Alarm polarity shown To next device on SLC Loop The addressable Control Module must be programmed as Silenceable and General Alarm Gamewell Model M34 56 Local Energy Municipal Box Note 10Ω m...

Страница 138: ...980 m 12 AWG 3 25 mm2 Genesis 4410 Signal 98230 Belden 9583 WPW999 14 AWG 2 00 mm2 Genesis 4408 4608 Signal 98430 Belden 9581 WPW995 16 AWG 1 30 mm2 Genesis 4406 4606 Signal 98630 Belden 9575 WPW991 Direct Burial Cable Isotec NP713110VNQ S 18 AWG 0 75 mm2 Genesis 4402 4602 Signal 98300 Belden 9574 WPW975 Direct Burial Cable Isotec NP714110VNQ S LITESPEED MODE Twisted unshielded pair 40 ohms maximu...

Страница 139: ...tex brand notification appliances the UL Max current rating published in their data sheets must be used in order to maintain performance under low battery conditions with the maximum wire resistances shown in the table above NAC Load Amps Max allowable total loop resistance ohms CLASS B Max allowable wire pair length feet CLASS A Max allowable wire pair length feet AWG 12 solid AWG 14 solid AWG 16...

Страница 140: ...splay HVAC SHUTDOWN When a shutdown event occurs the control module will both shut down the fans and activate the monitor module When the control module is active the monitor module will indicate a trouble condition at the FACP along with the label HVAC SHUTDOWN If using a NAC control module for HVAC shutdown monitor the state of the control module using an addressable monitor module programmed fo...

Страница 141: ...AC OVRRIDE type code to the monitor module which will be used to override the HVAC SHUTDN control module and prevent the fans from turning off refer to Type Monitor under the section titled Edit Module Screen for Monitor Module on page 58 The HVAC OVRRIDE monitor module does not latch when activated Activating a switch connected to the monitor module will over ride all HVAC SHUTDN control relay mo...

Страница 142: ...1 for point address 1 up to 99 for point address 99 F 2 Ademco Contact ID Typical Printout A typical printout from a Central Station receiver such as the Ademco 685 of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows Notes 1 11 is an example of a Receiver Line Card showing which receiver and line card the message was transmitted to 2 Q which is the Event Qualifier for...

Страница 143: ...PANIC Audible Panic Burglar Alarms 130 130 Burglary BURG Burglary 131 Perimeter BURG Perimeter 132 Interior BURG Interior 133 24 Hour BURG 24 Hour 134 Entry Exit BURG Entry Exit 135 Day Night BURG Day Night 136 Outdoor BURG Outdoor 137 Tamper BURG Tamper General Alarms 140 140 General Alarm ALARM General Alarm 141 Polling loop open ALARM Polling Loop Open 142 Polling loop short ALARM Polling Loop ...

Страница 144: ... System Low Battery 303 RAM checksum bad TROUBLE RAM Checksum restore not applicable 304 ROM checksum bad TROUBLE ROM Checksum restore not applicable 305 System reset TROUBLE System Reset restore not applicable 306 Panel program changed TROUBLE Prog Change restore not applicable 307 Self test failure TROUBLE Self Test Failure 308 System shutdown TROUBLE System Shutdown 309 Battery test failure TRO...

Страница 145: ...ENING Group User CLOSING Group User 403 Automatic Open Close OPENING Automatic CLOSING Automatic 404 Late Open Close OPENING Late CLOSING Late 405 Deferred Open Close Opening not used Closing not used 406 Cancel OPENING Cancel CLOSING Cancel 407 Remote arm disarm OPENING Remote CLOSING Remote 408 Quick arm Opening not applicable CLOSING Quick Arm 409 Keyswitch Open Close OPENING Keyswitch CLOSING ...

Страница 146: ... 572 24 Hour zone bypass BYPASS 24 Hour Bypass 573 Burglar bypass BYPASS Burg Bypass 574 Group bypass BYPASS Group Bypass Test Misc 600 601 Manual trigger test TEST Manually Triggered restore not applicable 602 Periodic test report TEST Periodic restore not applicable 603 Periodic RF transmission TEST Periodic Radio restore not applicable 604 Fire test TEST Fire Test restore not used 605 Status re...

Страница 147: ... 047 047 006 006 020 020 034 034 048 048 007 007 021 021 035 036 049 049 008 008 022 022 036 036 050 050 009 009 023 023 037 037 051 not used 010 010 024 024 038 038 011 011 025 025 039 039 through 012 012 026 026 040 040 013 013 027 027 041 041 014 014 028 028 042 042 159 not used Table G 1 Addressable DETECTORS CS Report Module Address CS Report Module Address CS Report Module Address CS Report ...

Страница 148: ... Non Emergency ES 50X Y Y Y Y Y Y ES 50XC Y Y Y Y Y Y IPOTS COM pre installed communicator Y 4XTMF O Y O 2 2 One of the indicated modules is required when the IPOTS COM is not employed O O 2 O DP ES R O O O O O O BB 55F 3 3 Listed separately O O O O O O ANN LED 3 O O O O O Y ANN 80 3 O O O O O Y ANN S PG 3 O O O O O Y ANN I O 3 O O O O O Y ANN RLED 3 O O O O O Y ANN RLY 3 O O O O O Y Where Y Yes N...

Страница 149: ...trip values and restoral values for the NAC circuits on the FACP Output Circuit Terminal Trip Resistance in ohms Remote Sync 360K Remote Sync 330K NAC 1 2 360K NAC 1 2 320K ANN Bus A 270K ANN Bus B 265K Aux Power 370K Aux Power 320K SLC 125K SLC 320K Table I 1 Earth Fault Trip Values Circuit Trip Resistance in ohms Restore Value NAC 1 2 Shorts below 1 75K 2K NAC 1 2 Opens above 25K 23K Table I 2 N...

Страница 150: ...nction key is automatically configured to perform a manual alarm signal activation when pressed The F2 function key is automatically configured to perform an automatic alarm signal cancel in two stage NAC operation This prevents the NAC from advancing to the second stage alarm The F3 function key is automatically configured to force active two stage NACs into the second alarm stage It advances NAC...

Страница 151: ...ve ANN LED Annunciators ANN LEDs FACP ANN LED ANN I O ANN S PG ANN RLY es50c annled5 wmf Secondary ANN BUS data on connector TB10 power on TB11 Terminals 5 6 with power programmed as non resettable Primary ANN BUS data on connector TB9 non resettable power on TB11 Terminals 1 2 in metal conduit adjacent to FACP ANN 100 ...

Страница 152: ...00 and the MMF 300 must be mapped to the same zone which is programmed for supervisory operation 2 No other device can be mapped to that supervisory zone 3 Wire gauge must be 18AWG minimum red black violet violet 47KΩ resistor TB12 SLC Loop Output Figure J 3 Alternate Transmission for Supervisory Signals es50revpol wmf T10 Comm2 T9 N C 2 T8 N O 2 T7 Comm1 T6 N C 1 T1 SLC T2 SLC T5 N O 1 CRF 300 Te...

Страница 153: ...24 battery box 17 BB 26 16 battery charger 17 disable 13 68 enable 101 external 17 BB 26 16 BB 55F see also battery box 16 17 C cabinet dimensions 22 23 cabinet mounting 21 calculate system current draw 125 calculating the battery size 127 Canadian Applications 150 Canadian applications 20 Canadian Option 150 Canadian option 68 77 CELL CAB FL 16 30 CELL MOD 16 30 cellular fault 81 central station ...

Страница 154: ...lation 21 intelligent 12 invalid password 96 inventory 12 INVREP 116 IP settings 80 K key control enable 96 key panel 14 function keys 15 service program keys 15 L lamp test 15 language 68 78 LCD display 12 14 LED AC power 103 alarm silenced 104 battery 103 CO alarm 103 communication 104 disabled 104 fire alarm 103 ground 103 maintenance 104 see also indicators 15 supervisory 103 trouble 103 LED d...

Страница 155: ... 38 printer module 13 18 38 printer options 39 process monitor 107 PROCMON AR 76 program check 97 check correlations 97 clear 97 program check maintenance level 99 program keys see also key panel 15 programming 48 annunciators 87 autoprogramming 48 exiting 48 factory default 133 level 1 48 level 2 48 manual 48 master level 1 50 modules 57 off line computer 48 programming levels 48 programming scre...

Страница 156: ...ransmitter module 30 see also 4XTMF module 13 16 trouble 104 trouble display 104 trouble relay 12 trouble reminder 68 110 112 trouble responses 105 two stage operation 66 75 102 type control module 63 detector 53 monitor module 59 NAC 74 type code control module 63 supervision 108 verification 12 U UL power limited wiring requirements 28 see also power limited and nonpower lim ited 25 upload 120 1...

Страница 157: ...Starting at the center of the keypad next to the Function Keys slide each label into the groove towards the outer edge Function Keys F1 and F3 are not programmable in Canadian applications Those keys must use the pre printed labels below Slide in Labels AUTOMATIC ALARM SIGNAL CANCEL ALARM SIGNAL ON TWO STAGE ALARM SIGNAL ON ACTIVATION DU SIGNAL D ALARME Slide in Labels for Canadian Applications ...

Страница 158: ...158 ES 50X Series Manual P N LS10129 000FL E D 4 26 2021 ...

Страница 159: ...will prevent silencing of NACs for five minutes after an alarm see manual To test the indicators LCD display and piezo Press and release the RESET button and check all indicators LEDs Every indicator LED should be on LCD shows all pixels on piezo sounder beeps For more information refer to the ES 50X Series Manual Document LS10129 000FL E It is kept in the following location ______________________...

Страница 160: ...Cut along dotted line ...

Страница 161: ...PLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the onl...

Страница 162: ...One Fire Lite Place Northford CT 06472 1601 USA USA Phone 203 484 7161 Canada Phone 905 856 8733 www firelite com ...

Отзывы: