ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
49
Programming Screens Description
Programming
After completing the wiring of addressable devices to the SLC, apply power to the control panel. If the addressable devices have not yet been
programmed into the FACP, their LEDs will not flash and the following trouble message will be displayed.
3.3 Programming Screens Description
The options available when the
Enter
key is pressed are: Read Status, Programming. The Read Status and Programming options have multi-
ple functions or features which may be chosen. To view all of the choices, it is necessary that the programmer scroll through a number of
additional
subscreens
. These selections are displayed on multiple screens to make them more readable for the programmer. Refer to “Master
Programming Level” on page 50, for additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the programmer’s convenience. If additional sub-
screens exist, an Up or Down arrow will be displayed in the upper right corner of the screen being viewed. The programmer can then press
the keypad Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the programmer presses the keypad
numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen. The same process, as detailed in the pre-
vious paragraphs, is followed to view all option choices.
3.4 Programming and Passwords
There are two factory set programming passwords which will access the Programming screens as indicated in the following examples. From
either of the screens, access to specific system and device features or programming may be obtained. All user programming entries are stored
in nonvolatile memory. The factory set passwords can be changed by the user as described in “Password Change” on page 96. If an invalid
password in entered, the blinking cursor will return to the first password character position. To exit Programming or Read Status mode at any
time, press the
ESC
(Escape) key repeatedly. Note that Programming mode must be exited using the
ESC
key in order to store the program
data entered during this mode. If the
Reset
key is pressed or power is lost before exiting Programming mode, the data just entered will not be
saved.
To access user Programming mode, press the
Enter
or
Mode
key. The LCD will display the following.
To enter the user Programming mode, press
2
. The display will read as follows:
Entering the
Master
level password (default
00000000
) will cause the following screen to appear:
If the
Maintenance
level password (default
11111111
) is entered, the following screen will appear:
Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the
keypad down arrow key.
TROUBL IN SYSTEM
NO DEVICES INSTALLED
09:03A 080516
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FSTOOL UP/DOWNLOAD
4=USB UP/DOWNLOAD
PROGRAMMING
ENTER PASSWORD
44444444
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK