WARNING

  

Filtrex is not designed to operate in explosive environments.

WIRING INSTRUCTIONS
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of 
the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mis-
takes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.

NOTE: Although the TC8441007A is an intelligent sensor, a separate pair of wires is required for power. This power must be provided 
from a listed fire alarm power supply.
Remove power from the communication line before installing detectors.
All wiring must conform to applicable local codes, ordinances, and regulations.
1.  Wire the sensor base per the wiring diagram, please see Figure 1.
2.  Set the desired address on the sensor address switches, please see Figure 2.
3.  Insert 5-wire connector on mounting base into 5-pin connector on Filtrex unit. Install the detector into the sensor base. Push the 

detector into the base while turning it clockwise to secure it in place. (Please see Figure 5 and INSTALLING FILTREX INTO BASE 
on page 4 for specific directions.)

4.  After all detectors have been installed, turn on the detector power supply, then apply power to the control unit and activate the 

communication line.

5.  Test the detector(s) as described in the

 

TESTING

 

section of this manual.

CAUTION

Dust cover must be removed before the detector can sense smoke. 

TESTING
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable 
the system to prevent unwanted alarms.
All detectors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having Jurisdiction 
(AHJ). Detectors offer maximum performance when tested and maintained in compliance with NFPA 72. 
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)

 

  This detector can be functionally tested with a test magnet. The test magnet electronically simulates smoke in the sensing cham-

ber, testing the detector electronics and connections to the control panel.

  1.  Hold the test magnet in the magnet test area as shown in Figure 3.
  2.  The detector should alarm the panel. Two LEDs on the detector are controlled by the panel to indicate sensor status. Coded 

signals,  transmitted  from  the  panel,  can  cause  the  LEDs  to  blink,  latch  on,  or  latch  off.  Refer  to  the  control  panel  technical 
documentation for detector LED status operation and expected delay to alarm.

B. Smoke Entry: Aerosol Generator 
  Aerosol  generators  for  smoke  entry  testing  are  available  from  a  number  of  third  party  manufacturers  (e.g.,  Gemini  Scientific). 

Following the manufacturer’s instructions, apply aerosol until the panel alarms.

A detector that fails any of these tests should be retested. If the detector still fails any test, have its filter replaced (see instructions 
below) and retested. Finally, if the detector continues to fail after replacing the filter, it must be returned for repair or replacement.
When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in opera-
tion.
TESTING
The unique design of Filtrex eliminates the need for typical detector cleaning. The only maintenance necessary is replacing the fil-
ter, which is signaled by a trouble condition at the panel (see below).
Filtrex has been designed to maximize

 

the amount of time before maintenance is required. Filtrex utilizes a replaceable filter that may 

become

 

clogged over time. Filtrex detector monitors itself

 

to insure that the filter has not become clogged. Because environmental 

conditions can vary significantly, the amount of time before maintenance could vary significantly as well. To fully understand mainte-
nance requirements of Filtrex in its installed location, it is recommended that the 
following test program be conducted.
1.  Install the Filtrex detector in the desired location.
2.  Connect the Filtrex detector to the fire alarm control panel.
3.  Maintain a record for at least 90 days of any maintenance performed on or required by Filtrex.
4.  At the end of the test period, use the record to develop and schedule maintenance. Filtrex should be serviced at regular intervals 

to insure that the fire alarm system provides continuous protection

H400-22-00 

I56-1326-006R

 

 

 

 

 

 

 

      

Содержание Filtrex TC844A1007

Страница 1: ...rborne particulate are pres ent at elevated levels These elevated levels tend to cause false alarms and high maintenance in standard detectors Filtrex provides a protective enclosure for a photoelectric smoke detector chamber and allows smoke detection in areas where heat detection was the only practical alternative for fire sensing Filtrex requires compatible addressable communications to functio...

Страница 2: ...ectronically simulates smoke in the sensing cham ber testing the detector electronics and connections to the control panel 1 Hold the test magnet in the magnet test area as shown in Figure 3 2 The detector should alarm the panel Two LEDs on the detector are controlled by the panel to indicate sensor status Coded signals transmitted from the panel can cause the LEDs to blink latch on or latch off R...

Страница 3: ...f Filtrex while replacing the filter If a clogged filter was the cause of the trouble condition nor mal detector operation should resume automatically within five minutes If the trouble condition persists the detector must be returned for repair or replacement Installing Filtrex into Base 1 Align the detector at a right angle to the base with the five wires and connector adjacent to the connector ...

Страница 4: ...e and install the XLS1000 FireAlarm Control Panel with a 3 AADC Analog Addressable Device Controller as described in form no 95 7545 XLS1000 Installation and Service Manual When configuring the database using the SDU use the TC806 Photoelectric Smoke Detector parameters for setting up the TC844A1007 Filtrex Intelligent Photo Smoke Sensor The TC844A1007 responds to the XLS1000 panel the same as a T...

Отзывы: