F58F DUCT MOUNTED ELECTRONIC AIR CLEANER
Fig. 4. Schematic for wiring W8600F to F58F.
J
Attach the cabinet securely to the furnace. The unit can
be attached directly as shown in Fig. 5, or a starting
collar can first be fitted in the furnace opening. Either
drill holes and fasten with sheet metal screws or rivets,
or use slip joints. If drilling holes, use locking pliers to
help hold the unit in place during drilling.
Fig. 5. Fasten cabinet to furnace.
Install Turning Vanes
J
Mount turning vanes inside the elbow or angle fitting
that is directly against the air cleaner cabinet.
M3678
Fasten Cabinet To Ductwork
J
Install a transition if the opening in the air cleaner
cabinet and the duct are different sizes. See Fig. 2.
J
Fasten the other side of the cabinet to the elbow using
sheet metal screws, rivets, or slip joints as appropriate.
See Fig. 6.
Install Optional W8600F Air Cleaner Monitor
Choose a location for the W8600F if it is part of the
installation. The W8600F is designed to mount next to your
thermostat, or in any convenient visible area (such as
utility room) where it can be seen as it monitors the air
cleaner performance. It shares no electrical connections
with the thermostat. To install the W8600F, see Fig. 4 and
refer to the Installations Instructions, form 69-1200,
included with the air cleaner monitor.
Seal Joints
J
Seal all joints in the return air system between the air
cleaner and the furnace to prevent dust from entering
the clean airstream.
Disable Unused Prefilter Guide
J
Crimp the end of the downstream (closest to the
furnace) prefilter guide to prevent incorrect prefilter
installation following cleaning. See Fig. 6.
Fig. 6. Crimping the prefilter guide.
Position Cell Key
The electronic cell must always be installed so the ionizer
section is on the upstream side. A factory-installed cell key
on the bottom of the cabinet allows the cell to be inserted
in only one direction. As long as the arrow molded into the
plastic key points in the same direction as the airflow, the
ionizer will always be on the upstream side.
If the position of the key must be reversed, proceed as
follows:
1. Remove electronic cell.
2. Remove the screw holding the cell key in place.
See Fig. 7.
M5640A
ELECTRONIC AIR CLEANER
M11974
TERMINAL STRIP
ON POWER BOX
THREE-WIRE
THERMOSTAT CABLE
GREEN
RED
BLUE
1
2
3
4
G
Y
R
B
1
1
CONNECT TO W8600F TERMINALS BEFORE CONNECTING TO
POWER BOX.
ELECTRONIC AIR CLEANER
W8600F
1
3
4