F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

7

68-0198-2

14.

Connect one wire on air cleaner to power supply wire 
with a wire nut following color code used at remote 
switch.   (White)

15.

Connect the ground wire from the remote switch to a 
ground stud of the wiring compartment cover.(Green) 

16.

Fold wires into wiring compartment. Replace wiring 
compartment cover.

17.

Turn on power to air cleaner at fuse or breaker.

18.

Check operation by turning air cleaner at HIGH, 
MEDIUM, and LOW.  

Note

 that only the remote switch 

will operate the air cleaner.

Lid Assembly

The F111 lid is held in place by two separable hinges and two 
spring loaded plungers. To install the spring loaded plungers 
on the lid follow these steps:

1.

Pull the plunger back and twist a quarter turn to reveal 
the wrench flat on the body of the spring loaded plunger 
(see Fig 7.)

2.

Turn the threaded barrel out of the spring plunger.

3.

Insert the threaded barrel through the hole in the lid and 
turn the spring loaded plunger onto it.

4.

Tighten the assembly with wrenches.

5.

Repeat steps 1 through 4 for the second plunger.

Fig. 7. Lid assembly.

Opening/Closing the Lid

To open the lid, pull the spring loaded plungers back to 
disengage the plunger. Carefully swing the lid open on the 
hinges while supporting the filter and/or adsorbent modules as 
required. To close, swing the lid into the closed position and 
engage the plungers.

Removing /Replacing the Lid

IMPORTANT

The lid is heavy. Make sure that it is supported 
before removing.

To remove the lid, swing it into the open position. Slide safety 
catch to off position. Move the lid to the side to disengage the 
hinge pins. Reverse the procedure to replace the lid. Make 
sure safety catch is in safe position.

OPERATION

The F111 (series 1,2,3) in Ceiling Media Air Cleaner has been 
engineered to improve indoor air quality for commercial and 
industrial applications. The filters are the most practical and 
effective filtering system for removing atmospheric dust, 
pollens, bacteria, viruses, mold spores, smoke, fumes, mists 
and aerosols. Refer to Fig. 8.

Fig. 8. F111 (series 1,2,3) air cleaner operation.

The air cleaner is either operating (power on) or off (power 
off). There are no other operational options available. Even 
when the area is unoccupied, the air cleaner can be operated 
continuously to prevent buildup of airborne contaminants. 
Operate the air cleaner only when the area is occupied when 
specific activities produce contaminants.

The CPZ™ sorbent module has the ability to collect and hold 
gas-phase compounds and vapors typically found in 
commercial and light industrial facilities. These gases and 
vapors frequently appear as odors that, at times, can be 
annoying and irritating. The modules become saturated after 
collecting 25% to 50% of their weight in gaseous odors. The 
quantity of CPZ™ material provides adequate dwell time to 
ensure up to 95% collection efficiency in the first pass. This 
also provides a long maintenance-free service life.

The minimum recommended air exchange rate is 2.5 times 
per hour. In a heavily contaminated area, up to 15 air 
exchanges per hour can be necessary. The factors that 
determine what the rate of air exchange should be are:

generation rates of the various pollutants;

concentration level of the pollutants;

desired contamination reduction level.

Airborne contaminants will always be present in the air where 
contaminant generations take place. Air cleaning systems and 
ventilators do not eliminate airborne contaminants, they 
reduce the excessive accumulation of the contaminants. To 
eliminate the contamination, the source of contamination must 
be removed.

THREADED 

BARREL

SPRING

LOADED

PLUNGER

WRENCH FLAT

WRENCH 

FLAT

M11994

M12651A

CEILING LINE

CLEAN AIR
DISCHARGE

CEILING LINE

CLEAN AIR
DISCHARGE

PARTICLE FILTER

PREFILTER

AIR IN

AIR IN

INTAKE

BLOWER

MOTOR

AIR VENTS

CPZ™
SORBENT 
FILTER
MODULE

CPZ™
SORBENT 
FILTER
MODULE

Содержание F111 Series 1

Страница 1: ...ollen and some cooking smoke from the air circulated through the filter FEATURES High Efficiency Particulate Air HEPA filter models are 99 97 efficient and the hospital grade particle filter models are 95 efficient at 0 3 micron particles Both models are more efficient on particles smaller and larger There is also a 95 ASHRAE model Circulates up to 1250 cfm Designed to overcome the increase in air...

Страница 2: ...ect drive forward curve Dimensions See Fig 1 for dimensions Table 1 F111 Series 3 Description a For single speed and three speed systems set to High b F111C1061 has a new model number F111C1012B To Order F111 with a Black Grill Replace the W with a B to any model number in Table 1 Model Voltage Efficiency Gas V O C and Odor Control Modules 2 Air Volumea in cfm m3 hr Particulates at 0 3 Micron DOP ...

Страница 3: ...f any questions should arise concerning determining the number of air cleaners needed for an area consult your distributor or local Honeywell Commercial Air Cleaner Distributor Table 4 Determining the Minimum Number of Air Cleaners Needed for a Space Model Voltage Particulates at 0 3 Micron DOP Test Gas V O C and Odor Control Modules 2 Higha in cfm m3 hr Medium in cfm m3 hr Low in cfm m3 hr F111A1...

Страница 4: ...ed air up from the center of the area See Fig 2 When multiple air cleaners are installed the allotted areas to be cleaned should be equal The air throw in one direction is approximately 55 ft 17m Air velocity at 90 ft per minute 27m per minute is considered end of throw IMPORTANT Never hang the air cleaner higher than 16 ft 5m above the floor INSTALLATION WARNING Explosion Hazard Possible Can caus...

Страница 5: ...g diagram Fig 4 Typical F111 Series 3 only 120V 60 Hz or 230V 50 Hz wiring diagram Mount Air Cleaner Cabinet The air cleaner can be mounted in a drop ceiling system or hung in an open area Both mounting methods require the air cleaner to be level and positioned facing downward for correct operation 1 Remove the door grille from the carton and set it aside 2 Remove all filters 3 Fit the cabinet int...

Страница 6: ...te location 3 Attach 3 4 extension ring to outlet box 4 Run five conductor color coded 18 gauge wires from the remote switch location to the air cleaner 5 Use three wire nuts to connect three color coded lead wires on the remote switch to three color coded wires from the air cleaner Red Blue Violet 6 Use one wire nut to connect white color coded lead wire from the air cleaner to single color coded...

Страница 7: ...mmercial and industrial applications The filters are the most practical and effective filtering system for removing atmospheric dust pollens bacteria viruses mold spores smoke fumes mists and aerosols Refer to Fig 8 Fig 8 F111 series 1 2 3 air cleaner operation The air cleaner is either operating power on or off power off There are no other operational options available Even when the area is unocc...

Страница 8: ...h hands Slide the filter toward you 3 Place spent filter in a plastic trash bag and dispose of properly 4 Inspect the motor brackets for loose fasteners and tighten as necessary 5 Install the new filter noting the direction of airflow arrow 6 For Series 1 and 2 only Fasten the filter tabs Be sure there is a snapping sound when they are fastened The tabs are commercial Velcro and require more force...

Страница 9: ...1 32000265 4 Motor 120 V 60 Hz Series 1 1 32000270 Motor 208 230V 50 60 Hz Series 1 1 32000263 Motor 120 V 60 Hz Series 2 1 32002415 001 Motor 208 230V 50 60 Hz Series 2 1 32002415 002 Motor 120 V 3 Speed 60 Hz Series 3 1 32002415 004 Motor 230V 3 Speed 50Hz Series 3 1 32002415 005 5 99 97 HEPA media filter 3 Series 1 and 2 1 32000204 001 99 97 HEPA media filter 4 5 Series 3 1 32000204 002 95 hosp...

Страница 10: ...vised 5 09 10 CABINET ASSEMBLY LID ASSEMBLY WITH HINGES AND LATCHES PREFILTER MEDIA FILTER MOTOR MOTOR CAPACITOR BLOWER WHEEL SORBENT MEDIA MODULE 2 REQUIRED M11995E 1 6 3 4 5 7 2 Fig 9 Exploded view of F111 series 1 2 3 in Ceiling Media Air Cleaner components ...

Страница 11: ...F111 SERIES 1 2 3 IN CEILING MEDIA AIR CLEANER 11 68 0198 2 NOTES ...

Страница 12: ...OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PROD UCT Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation may not apply to you THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND AIR PURE SYSTEMS EXPRESSLY DISCLAIMS A...

Отзывы: